3.1.2 TCP_CLIENT pattern
1. Open Google browser, and enter 192.168.1.254 to log in to the webpage
configuration interface.
Network Setting: IP address 192.168.1.254, Device port: 502, Wok mode: TCP client,
set the Destination IP/DNS to the server IP address to be connected: 192.168.1.51 (IP
address of the local NIC), and remote port number: 6001.
Serial port device parameters: 19200bps, N81.The Serial Port test tool Serial Port
Utility is used to simulate Serial Port devices.
Multiple Host Config: Select Modbus TCP to RTU mode as the conversion protocol.
Click Submit when the Settings are completed.