OPERATION | Making settings
18
www.ochsner.com | BIA-EUROPA Mini IWP-EN12
Symbol
Parameter
Designation
Description
Set
Fan speed
Here, the fan speed (0-100%) is set in ventilation mode.
44 = default setting
1day
1. Weekday start time
The days for the 1st start time is defined.
day1 = Monday to day7 = Sunday
off = default setting
1 on
1. Start time
The time from which the operating mode is enabled is set here.
00:00 = default setting
2day
1. Weekday stop time
The days for the 1st Stop time defined.
day1 = Monday to day7 = Sunday
off = default setting
2off
1. Stop time
The time from which the operating mode is disabled is set here.
23:59 = default setting
3day
2. Weekday start time
The days for the 2nd start time is defined.
day1 = Monday to day7 = Sunday
off = default setting
3 on
2. Start time
The time from which the operating mode is enabled is set here.
00:00 = default setting
4day
2. Weekday stop time
The days for the 2nd Stop time defined.
day1 = Monday to day7 = Sunday
off = default setting
4off
2. Stop time
The time from which the operating mode is disabled is set here.
23:59 = default setting
Pset
PA1
b15
Function of input E3
12 = start ventilation mode
Contact E3 open = ventilation switched off
Contact E3 closed = fan runs at set speed
For the external wiring to work, mode selection must be set to “Auto”.
13 = Default setting
1 Heat pump is running
2
Heat pump switched off, fan is running
3 Fan speed
4.6.1 External ventilation control
The ventilation can be switched on and off externally via
input E3 (parameter B15=12).
Note
The time program for ventilation mode has a higher
priority than control via an external floating contact.
Note
For this function, the fan operating program must
be set to “Auto” and enabled via the time program.