OTS_EN | www.ochsner.com 61
Expert mode
»
Select “Settings”.
The parameters can be found under the following menu
item: “Smart Grid”
»
Make the required settings.
»
Return to the main screen.
27.5.2
Parameters for the buffer tank
Priority mode
Parameters
Description
Unit
Buffer tank
target temper-
ature increase
The selected “Target buffer tank temper-
ature” is increased by the value specified
here if the following apply:
K
The heat pump is in heating mode
Smart Grid is in priority mode
Buffer tank
target temper-
ature reduction
The selected “Target buffer tank temper-
ature” is reduced by the value specified
here if the following apply:
K
The heat pump is in cooling mode
Smart Grid is in priority mode
The increase/decrease can be adjusted via the menu.
»
Open the menu.
»
Select “Heat management”.
»
Select “Settings”.
The parameters can be found under the following menu
item: “Smart Grid”.
»
Make the required settings.
»
Return to the main screen.
Forced draw-off
Parameters
Description
Unit
Buffer tank
target temper-
ature increase
for forced
draw-off
The selected “Target buffer tank temper-
ature” is increased by the value specified
here if the following apply:
K
The heat pump is in heating mode
Smart Grid is in the Forced draw-off op-
erating mode
Buffer tank
target temper-
ature reduction
for forced
draw-off
The selected “Target buffer tank temper-
ature” is reduced by the value specified
here if the following apply:
K
The heat pump is in cooling mode
Smart Grid is in the Forced draw-off op-
erating mode
The increase/decrease can be adjusted via the menu.
»
Open the menu.
»
Select “Heat management”.
»
Select “Settings”.
The parameters can be found under the following menu
item: “Smart Grid”
»
Make the required settings.
»
Return to the main screen.
27.6 Status
In addition to the standard settings, other settings are also
possible under “Status” in expert mode.
Parameters
Description
Unit
Height above
sea level
The height above sea level of the heat
pump system is defined here.
m
Unlocking the
system
In the case of recurring or critical faults,
the system is locked. This parameter al-
lows the system to be unlocked again.
-
Material damage
Operating the heat pump with critical faults can
cause damage to the system.
»
Unlock the system only in consultation with
your service partner.
27.7 Screed drying program
For drying screed it is possible to select a screed drying
program.
Note
The screed drying program cancels the bivalent
point. If an external auxiliary energy generator has
been installed, it is switched on in accordance with
the screed drying program.
If no auxiliary energy generator is installed, the
electric auxiliary heater is switched on in accord-
ance with the screed drying program.
27.7.1 Activating the screed drying program
»
Open the menu.
»
Select the heating circuit for which you would like to
use the screed drying program.
»
Select “Operating program”.
»
Select “Operating program heating circuit”.
»
Select “OFF”.
Содержание AIR FALCON 212
Страница 7: ...BA 982018 AIR FALCON sh EN www ochsner com 7...
Страница 9: ...00_400_200_202_01_split_Funktionsweise EN www ochsner com 9 How split systems work...
Страница 65: ...OTS_EN www ochsner com 65 Expert mode...
Страница 77: ...OTS_ZSM_EN www ochsner com 77...
Страница 85: ...BA 982018 AIR FALCON EN07 www ochsner com 85...
Страница 86: ...Notes...
Страница 87: ...Notes...