INSTALLATION | Preparing to install the appliance
16
www.ochsner.com | 982000-AIR-M2-M4-EN03.1
9.3.2 Laying strip foundations
11_04_200_504_002
C
A
1100
150
B
200
4
2
1
3
1 Pipe liner for the connecting lines (where installed
underground)
2 Gravel bed
3 Drainage pipe (frostproof)
4 Strip foundations
A
B
C
AIR 7
1400
300
≥ Ø160
AIR 11
1400
300
≥ Ø160
AIR 18
1400
300
≥ Ø160
AIR 23
2250
320
≥ Ø200
AIR 29
2250
320
≥ Ø200
AIR 41
2250
350
≥ Ø250
When laying strip foundations we recommend the following
approach:
11_04_200_504_005
≥ 1600
≥ 800
»
Dig out the foundation trench.
»
Place a drainage pipe along the base of the trench.
11_04_200_504_006
≥ 300
2
3
4
1
1 Reinforced strip foundation
2 Pipe liner for underground connecting lines
3 Drainage pipe (frostproof)
4 Gravel bed
»
In the case of underground connecting lines, allow for
the pipe liner.
»
Fill the foundation trench with coarse gravel. If the
pipe liner (with refrigerant lines) is to be installed at
a later point, in the case of underground connec-
tion lines, this must be allowed for in the foundation
trench.
»
Construct the two reinforced strip foundations.
9.3.3
Installing on flat roofs
WARNING: Risk of falling
Working on a flat roof without fall protection con
-
stitutes a risk.
»
When working on a flat roof, observe the laws
relating to occupational safety in your region.
»
Always be aware of the open edge.
i
Information
Avoid installing the outdoor unit on the roof above
residential buildings or on car ports attached to res-
idential buildings, due to the risk of structure-borne
noise transmission.
Loads and stresses on roof structure
»
Note that when outside temperatures are very low,
ice can form beneath the outdoor unit.
»
In terms of roof structure loads, allow for an
ice load
of 400 kg/m²
in addition to the dead weight of the
outdoor unit.