OCEANIC SYSTEMS NMEA2000®

AC MODBUS GATWAY

Part Numbers: 3155

USER MANUAL

Document revision 1.21

Содержание NMEA2000 3155

Страница 1: ...OCEANIC SYSTEMS NMEA2000 AC MODBUS GATWAY Part Numbers 3155 USER MANUAL Document revision 1 21...

Страница 2: ...ers 6 3 2 Modbus Slave Address 7 3 3 Modbus Termination Resistor 7 3 4 NMEA Device Instance 7 3 5 The Device Setup Process 7 4 Front Panel Indicators and Switches 8 5 Fault Finding Troubleshooting 9 5...

Страница 3: ...ters 32 7 13 AC Instance 4 Registers 33 7 14 AC Instance 5 Registers 34 7 15 Battery Bank Registers 35 7 16 Battery Charger Instance 0 Registers 37 7 17 Battery Charger Instance 1 Registers 39 7 18 Ba...

Страница 4: ...manual Please read and follow the installation and setup instructions carefully to achieve the best results 1 1 PRODUCT FEATURES The 3155 NMEA2000 to Modbus Gateway has the following features RS485 M...

Страница 5: ...in an engine room providing the ambient temperature does not exceed 50 C 125 F 3 The location needs to allow for connection to the NMEA2000 interface cable and the RS485 Modbus cable 2 3 MOUNTING THE...

Страница 6: ...ce cable on the unit should be connected to a nearby NMEA2000 Tee connector part number 3802 2 The male end of the cable should be inserted into the female Tee connection noting the position of the ke...

Страница 7: ...to the default then the DefCm green led will NOT be illuminated The unit can be reset to the default values at any time by pressing the Set DefCom push button when the unit has power on and the ADDR...

Страница 8: ...the Modbus Communication line 3 4 NMEA DEVICE INSTANCE NMEA2000 requires a unique Device Instance for each 3155 NMEA2000 to Modbus Gateway on a single network This is settable from device instance 0 t...

Страница 9: ...ee 3 1 To 3 3 above The pushbutton is used to capture the default communications protocol from the rotary switch LED Name Description NMRx Receiving an NMEA2000 message NMTx Transmitting an NMEA2000 m...

Страница 10: ...MODBUS MESSAGE ERROR LED If the MoFlt led is lit this means that the unit received a Modbus message that it could not carry out This indicates that the communications protocol is probably correct but...

Страница 11: ...59 Because it is easy to misunderstand base numbering system it is being shown in this document decimal base 10 values are shown thus 10 decimal value of ten Hexadecimal base 16 values are shown thus...

Страница 12: ...individually or collectively Read access to all registers can only be made using the Modbus Function Code 04 Read Input Register command There is NO write access to any input registers except the Swit...

Страница 13: ...conds Resolution 1 second 0x0007 0007 Engine Coolant Pressure Unsigned 16 bit integer Range 0 6 553 200 Pa Resolution 1 x 10E 2 Pa 0x0008 0008 Fuel Pressure Unsigned 16 bit integer Range 0 65 532 000...

Страница 14: ...x xxxx Reserved x1xx xxxx xxxx xxxx Reserved 1xxx xxxx xxxx xxxx Reserved 0x000B 0011 Percent Engine Load Percent Engine Torque 2x Unsigned 8 bit integers Range 124 Resolution 1 MSB Load LSB Torque 0x...

Страница 15: ...r Range 0 4 295x10E 9 seconds Resolution 1 second 0x0018 0024 Engine Coolant Pressure Unsigned 16 bit integer Range 0 6 553 200 Pa Resolution 1 x 10E 2 Pa 0x0019 0025 Fuel Pressure Unsigned 16 bit int...

Страница 16: ...ngine Coolant Pressure Unsigned 16 bit integer Range 0 6 553 200 Pa Resolution 1 x 10E 2 Pa 0x0019 0025 Fuel Pressure Unsigned 16 bit integer Range 0 65 532 000 Pa Resolution 1x10E 3 Pa 0x001A 0026 En...

Страница 17: ...x Reserved 1xxx xxxx xxxx xxxx Reserved 0x001C 0028 Percent Engine Load Percent Engine Torque 2x Unsigned 8 bit integers Range 124 Resolution 1 MSB Load LSB Torque 0x001D 0029 Engine Speed Unsigned 16...

Страница 18: ...2 bit integer Range 0 4 295x10E 9 seconds Resolution 1 second 0x0029 0041 Engine Coolant Pressure Unsigned 16 bit integer Range 0 6 553 200 Pa Resolution 1 x 10E 2 Pa 0x002A 0042 Fuel Pressure Unsigne...

Страница 19: ...xxxx Reserved xx1x xxxx xxxx xxxx Reserved x1xx xxxx xxxx xxxx Reserved 1xxx xxxx xxxx xxxx Reserved 0x002C 0045 Percent Engine Load Percent Engine Torque 2x Unsigned 8 bit integers Range 124 Resolut...

Страница 20: ...Resolution 0 004 0x003A 0x003B 0058 0059 Tank Capacity 0058 MSW 0059 LSW Unsigned 32 bit integer Range 0 4 296x10E 5 cu m Resolution 1x10E 4 cu m Fuel Tank Instance 3 Registers 0x003C 0060 Fluid Leve...

Страница 21: ...0 004 0x0046 0x0047 0070 0071 Tank Capacity 0070 MSW 0071 LSW Unsigned 32 bit integer Range 0 4 296x10E 5 cu m Resolution 1x10E 4 cu m Fuel Tank Instance 7 Registers 0x0048 0072 Fluid Level Signed 16...

Страница 22: ...056 Resolution 0 004 0x0052 0x0053 0082 0083 Tank Capacity 0082 MSW 0083 LSW Unsigned 32 bit integer Range 0 4 296x10E 5 cu m Resolution 1x10E 4 cu m Fresh Water Tank Instance 3 Registers 0x0054 0084...

Страница 23: ...0 004 0x005E 0x005F 0094 0095 Tank Capacity 0094 MSW 0095 LSW Unsigned 32 bit integer Range 0 4 296x10E 5 cu m Resolution 1x10E 4 cu m Fresh Water Tank Instance 7 Registers 0x0060 0096 Fluid Level Sig...

Страница 24: ...31 056 Resolution 0 004 0x006A 0x006B 0106 0107 Tank Capacity 0106 MSW 0107 LSW Unsigned 32 bit integer Range 0 4 296x10E 5 cu m Resolution 1x10E 4 cu m Grey Water Tank Instance 3 Registers 0x006C 010...

Страница 25: ...0 004 0x0076 0x0077 0118 0119 Tank Capacity 0118 MSW 0119 LSW Unsigned 32 bit integer Range 0 4 296x10E 5 cu m Resolution 1x10E 4 cu m Grey Water Tank Instance 7 Registers 0x0078 0120 Fluid Level Sign...

Страница 26: ...0x0083 0126 0127 Tank Capacity 0126 MSW 0127 LSW Unsigned 32 bit integer Range 0 4 296x10E 5 cu m Resolution 1x10E 4 cu m Oil Tank Instance 3 Registers 0x0084 0128 Fluid Level Signed 16 bit integer R...

Страница 27: ...0 004 0x008E 0x008F 0142 0143 Tank Capacity 0142 MSW 0143 LSW Unsigned 32 bit integer Range 0 4 296x10E 5 cu m Resolution 1x10E 4 cu m Oil Tank Instance 7 Registers 0x0090 0144 Fluid Level Signed 16 b...

Страница 28: ...09B 0154 0155 Tank Capacity 0154 MSW 0155 LSW Unsigned 32 bit integer Range 0 4 296x10E 5 cu m Resolution 1x10E 4 cu m Black Water Tank Instance 3 Registers 0x009C 0156 Fluid Level Signed 16 bit integ...

Страница 29: ...0 004 0x00A6 0x00A7 0166 0167 Tank Capacity 0166 MSW 0167 LSW Unsigned 32 bit integer Range 0 4 296x10E 5 cu m Resolution 1x10E 4 cu m Black Water Tank Instance 7 Registers 0x00A8 0168 Fluid Level Sig...

Страница 30: ...ge Line to Line Voltage AC RMS Unsigned 16 bit integer Range 0 64255 Volts Resolution 1 Volt 0x00AD 0173 Average Line to Neutral Voltage Unsigned 16 bit Integer Range 0 64255 Volts Resolution 1 Volt 0...

Страница 31: ...e Line to Line Voltage AC RMS Unsigned 16 bit integer Range 0 64255 Volts Resolution 1 Volt 0x00B2 0178 Average Line to Neutral Voltage Unsigned 16 bit Integer Range 0 64255 Volts Resolution 1 Volt 0x...

Страница 32: ...ne to Line Voltage AC RMS Unsigned 16 bit integer Range 0 64255 Volts Resolution 1 Volt 0x00B7 0183 Average Line to Neutral Voltage Unsigned 16 bit Integer Range 0 64255 Volts Resolution 1 Volt 0x00B8...

Страница 33: ...ne to Line Voltage AC RMS Unsigned 16 bit integer Range 0 64255 Volts Resolution 1 Volt 0x00BC 0188 Average Line to Neutral Voltage Unsigned 16 bit Integer Range 0 64255 Volts Resolution 1 Volt 0x00BD...

Страница 34: ...ne to Line Voltage AC RMS Unsigned 16 bit integer Range 0 64255 Volts Resolution 1 Volt 0x00C1 0193 Average Line to Neutral Voltage Unsigned 16 bit Integer Range 0 64255 Volts Resolution 1 Volt 0x00C2...

Страница 35: ...igned 16 bit integer Range 0 64255 Volts Resolution 1 Volt 0x00C6 0198 Average Line to Neutral Voltage Unsigned 16 bit Integer Range 0 64255 Volts Resolution 1 Volt 0x00C7 0199 Frequency Unsigned 16 b...

Страница 36: ...Amps Resolution 1x10E 1 Amps 0x0164 0356 Battery Case Temp Unsigned 16 bit integer Range 0 655 32 K Resolution 1x10E 2 K Battery Bank Instance 2 Registers 0x0165 0357 Battery Voltage Signed 16 bit int...

Страница 37: ...Range 3 276 4 Amps Resolution 1x10E 1 Amps 0x0170 0368 Battery Case Temp Unsigned 16 bit integer Range 0 655 32 K Resolution 1x10E 2 K Battery Bank Instance 6 Registers 0x0171 0369 Battery Voltage Sig...

Страница 38: ...xxx Data not available xxxx xx00 xxxx xxxx Charger Off Disabled xxxx xx01 xxxx xxxx Charger On Enabled xxxx xx10 xxxx xxxx Error xxxx xx11 xxxx xxxx Unknown Unavailable xxxx 00xx xxxx xxxx Eq Pend Off...

Страница 39: ...xxxx 0000 Not Charging xxxx xxxx xxxx 0001 Bulk xxxx xxxx xxxx 0010 Absorption xxxx xxxx xxxx 0011 Overcharge xxxx xxxx xxxx 0100 Equalise xxxx xxxx xxxx 0101 Float xxxx xxxx xxxx 0110 No Float xxxx x...

Страница 40: ...xxx Data not available xxxx xx00 xxxx xxxx Charger Off Disabled xxxx xx01 xxxx xxxx Charger On Enabled xxxx xx10 xxxx xxxx Error xxxx xx11 xxxx xxxx Unknown Unavailable xxxx 00xx xxxx xxxx Eq Pend Off...

Страница 41: ...xxxx 0000 Not Charging xxxx xxxx xxxx 0001 Bulk xxxx xxxx xxxx 0010 Absorption xxxx xxxx xxxx 0011 Overcharge xxxx xxxx xxxx 0100 Equalise xxxx xxxx xxxx 0101 Float xxxx xxxx xxxx 0110 No Float xxxx x...

Страница 42: ...xxx Data not available xxxx xx00 xxxx xxxx Charger Off Disabled xxxx xx01 xxxx xxxx Charger On Enabled xxxx xx10 xxxx xxxx Error xxxx xx11 xxxx xxxx Unknown Unavailable xxxx 00xx xxxx xxxx Eq Pend Off...

Страница 43: ...xxxx 0000 Not Charging xxxx xxxx xxxx 0001 Bulk xxxx xxxx xxxx 0010 Absorption xxxx xxxx xxxx 0011 Overcharge xxxx xxxx xxxx 0100 Equalise xxxx xxxx xxxx 0101 Float xxxx xxxx xxxx 0110 No Float xxxx x...

Страница 44: ...xxx Data not available xxxx xx00 xxxx xxxx Charger Off Disabled xxxx xx01 xxxx xxxx Charger On Enabled xxxx xx10 xxxx xxxx Error xxxx xx11 xxxx xxxx Unknown Unavailable xxxx 00xx xxxx xxxx Eq Pend Off...

Страница 45: ...xxxx 0000 Not Charging xxxx xxxx xxxx 0001 Bulk xxxx xxxx xxxx 0010 Absorption xxxx xxxx xxxx 0011 Overcharge xxxx xxxx xxxx 0100 Equalise xxxx xxxx xxxx 0101 Float xxxx xxxx xxxx 0110 No Float xxxx x...

Страница 46: ...ith the following values which vary whether the switch is being read or set When controlling or reading the switchves using the Holding Registers then these values MUST be used by the Modbus Master de...

Страница 47: ...e above 0x0191 0401 Switches 17 24 16 bit field SSxx xxxx xxxx xxxx Switch 17 bits xxSS xxxx xxxx xxxx Switch 18 bits xxxx SSxx xxxx xxxx Switch 19 bits xxxx xxSS xxxx xxxx Switch 20 bits xxxx xxxx SS...

Страница 48: ...able above 0x0196 0406 Switches 25 28 16 bit field xxxx xxxx SSxx xxxx Switch 25 bits xxxx xxxx xxSS xxxx Switch 26 bits xxxx xxxx xxxx SSxx Switch 27 bits xxxx xxxx xxxx xxSS Switch 28 bits Values as...

Страница 49: ...xxxx Switch 2 bits xxxx SSxx xxxx xxxx Switch 3 bits xxxx xxSS xxxx xxxx Switch 4 bits xxxx xxxx SSxx xxxx Switch 5 bits xxxx xxxx xxSS xxxx Switch 6 bits xxxx xxxx xxxx SSxx Switch 7 bits xxxx xxxx x...

Страница 50: ...16 bit field SSxx xxxx xxxx xxxx Switch 9 bits xxSS xxxx xxxx xxxx Switch 10 bits xxxx SSxx xxxx xxxx Switch 11 bits xxxx xxSS xxxx xxxx Switch 12 bits xxxx xxxx SSxx xxxx Switch 13 bits xxxx xxxx xxS...

Страница 51: ...per bit value table above 0x01A5 0421 Switches 17 24 16 bit field SSxx xxxx xxxx xxxx Switch 17 bits xxSS xxxx xxxx xxxx Switch 18 bits xxxx SSxx xxxx xxxx Switch 19 bits xxxx xxSS xxxx xxxx Switch 20...

Страница 52: ...able above 0x01AA 0426 Switches 25 28 16 bit field xxxx xxxx SSxx xxxx Switch 25 bits xxxx xxxx xxSS xxxx Switch 26 bits xxxx xxxx xxxx SSxx Switch 27 bits xxxx xxxx xxxx xxSS Switch 28 bits Values as...

Страница 53: ...xSS xxxx xxxx Switch 20 bits xxxx xxxx SSxx xxxx Switch 21 bits xxxx xxxx xxSS xxxx Switch 22 bits xxxx xxxx xxxx SSxx Switch 23 bits xxxx xxxx xxxx xxSS Switch 24 bits Values as per bit value table a...

Страница 54: ...osure or seals Ensure that the unit is mounted securely and cannot be moved relative to the mounting surface If the unit is loose tighten the mounting screws Check the security of the cables connected...

Страница 55: ...SPECIFICATION 9 Parameter Comment NMEA2000 Level B Maritime Nav and RadioComm Equipment IEC60945 CE and FCC Electromagnetic Compatibility Source Max No PGN No PGN Name Engines 3 127488 Engine Paramete...

Страница 56: ...t 160gm Parameter Value IEC 60954 Classification Protected Degree of Protection IP40 Operating Temperature 25 C to 50 C Storage Temperature 40 C to 70 C Relative Humidity 93 RH 40 per IEC60945 8 2 Vib...

Страница 57: ...ive New Milton Hampshire BH25 6RH United Kingdom Tel 44 0 1425 610022 Fax 44 0 1425 614794 Email sales osukl com Web www osukl com Copyright 2017 Oceanic Systems UK Ltd All rights reserved Our policy...

Страница 58: ...DAMAGES DAMAGES FOR LOSS OF USE LOSS OF ANTICIPATED PROFITS OR SAVINGS OR ANY OTHER LOSS INCURRED BECAUSE OF INTERRUPTION OF SERVICE IN NO EVENT SHALL OCEANIC SYSTEMS AGGREGATE LIABILITY EXCEED THE PU...

Страница 59: ...58 of 59...

Страница 60: ...59 of 59 OCEANIC SYSTEMS PRODUCT MAP 10...