Version 5.2_2022 (January 26, 2022)
38
11.11.
Table of alarm messages
The alarm messages table is as follows:
Alarm ID
Type
Description
0
Manual reset
Error in the amount of data written to memory
1
Manual reset
Error writing to memory
2
Automatic reset
Alarm message from supply temperature probe
3
Automatic reset
Alarm message from the supply coil temperature probe
4
Automatic reset
Alarm message from the return coil temperature probe
5
Automatic reset
Alarm message from the air intake temperature probe
6
Automatic reset
Dirty filter alarm message
7
Automatic reset
Offline EBM 1
8
Manual reset
Phase fault EBM 1
9
Manual reset
Motor blocked EBM 1
10
Manual reset
Undervoltage power supply EBM 1
11
Manual reset
Overvoltage power supply EBM 1
12
Manual reset
Overvoltage DC connection EBM 1
13
Manual reset
Undervoltage DC connection EBM 1
14
Manual reset
Motor overheating EBM 1
15
Manual reset
Internal circuit overheating EBM 1
16
Manual reset
Overheating of outgoing phase EBM 1
17
Manual reset
Hall sensor fault EBM 1
18
Manual reset
Communication fault EBM 1
19
Manual reset
General fault EBM 1
20
Automatic reset
High temperature outgoing phase EBM 1
21
Automatic reset
High temperature internal circuit EBM 1
22
Automatic reset
High temperature motor EBM 1
23
Automatic reset
Low voltage DC connection EBM 1
24
Automatic reset
Output limit power supply EBM 1
25
Automatic reset
Current limit power supply EBM 1
26
Automatic reset
Braking mode EBM 1
27
Automatic reset
Cable break EBM 1
28
Automatic reset
Ice protection EBM 1
29
Automatic reset
Heating: motor stop EBM 1
30
Automatic reset
Speed below limit EBM 1
31
Automatic reset
DC voltage high EBM 1
32
Automatic reset
Supply voltage high EBM 1
33
Automatic reset
Line resistance high EBM 1
34
Automatic reset
Offline EBM 2
35
Manual reset
Phase fault EBM 2
36
Manual reset
Motor blocked EBM 2
37
Manual reset
Undervoltage power supply EBM 2
38
Manual reset
Overvoltage power supply EBM 2
39
Manual reset
Overvoltage DC connection EBM 2
40
Manual reset
Undervoltage DC connection EBM 2
41
Manual reset
Overheating motor EBM 2
42
Manual reset
Internal circuit overheating EBM2
43
Manual reset
Overheating of outgoing phase EBM 2
44
Manual reset
Hall sensor fault EBM 2
45
Manual reset
Communication fault EBM 2
46
Manual reset
General fault EBM 2
47
Automatic reset
High temperature outgoing phase EBM 2
48
Automatic reset
High temperature internal circuit EBM 2
49
Automatic reset
High temperature motor EBM 2
50
Automatic reset
Low voltage DC connection EBM 2
51
Automatic reset
Output limit power supply EBM 2
52
Automatic reset
Current limit power supply EBM 2
53
Automatic reset
Braking mode EBM 2
54
Automatic reset
EBM 2 cable break
55
Automatic reset
Ice protection EBM 2
56
Automatic reset
Heating: motor stop EBM 2
57
Automatic reset
Speed below limit EBM 2