Introduction
DGX A100 System
DU-09821-001_v06
| 4
1.1.3
Power Specifications
The DGX A100 system contains six power supplies with balanced distribution of the power
load.
Table 1-4.
Power Specifications
Input
Specification for Each Power Supply
200-240 volts AC
6.5 kW max.
3000 W @ 200-240 V, 16 A, 50-60 Hz
1.1.3.1
Support for N+N Redundancy
The DGX A100 includes six power supply units (PSU) configured for 3+3 redundancy. If three
PSUs fail, the system will continue to operate at full power with the remaining three PSUs.
Note
: If only two PSUs are working, the GPUs will not be available, but the server will still boot.
This is to allow you to gather debug or system logs.
If only one PSU is working, troubleshoot the cause for the loss of power from the other PSUs and
correct. If faulty PSUs need to be replaced, shut the system down and install working PSUs.
1.1.3.2
DGX A100 Locking Power Cord Specification
The DGX A100 is shipped with a set of six (6) locking power cords that have been qualified for
use with the DGX A100 to ensure regulatory compliance. Two locking power cord types are
approved - switch-locking for the PSU side and twist-locking for the PSU side.
WARNING: To avoid electric shock or fire, only use the NVIDIA-provided power cords to connect
power to the DGX A100. For more details, see
Electrical Precautions
Table 1-5.
Power Cord Specifications
Power Cord Feature
Specification
Electrical
250VAC, 16A
Plug Standard
C19/C20
Dimension
1200mm length
Compliance
Cord: UL62, IEC60227
Connector/Plug: IEC60320-1
Содержание DGX A100
Страница 1: ...DU 09821 001_v06 May 2022 DGX A100 System User Guide ...
Страница 74: ...Using the BMC DGX A100 System DU 09821 001_v06 69 7 Select Server CA Configuration 8 Select Enroll Cert ...
Страница 76: ...Using the BMC DGX A100 System DU 09821 001_v06 71 ...
Страница 107: ...Redfish APIs Support DGX A100 System DU 09821 001_v06 102 Korea RoHS Material Content Declaration ...
Страница 108: ...Redfish APIs Support DGX A100 System DU 09821 001_v06 103 ...