Heat-Tracing Remote Monitoring Module for the nVent RAYCHEM NGC Control System 
Installation Instructions

DESCRIPTION

The nVent RAYCHEM remote monitoring module (catalog no. 

RMM2) is part of the RAYCHEM NGC Control System. The 

RMM2 takes inputs from up to 8 RTDs that measure pipe, vessel, 

or ambient temperatures in a heat-tracing system. Multiple 

RMM2 units communicate with a RAYCHEM NGC controller 

using a single RS-485 bus (a shielded, twisted pair).
Refer to the specific RAYCHEM NGC controller Installation and 

Operation manual for additional information. For technical 

support call nVent at (800) 545-6258.

MONITORING SYSTEM COMPONENTS AND ACCESSORIES

RMM2

RMM2 module without enclosure (for use with user-

supplied enclosures.)

RMM2-4X

Reinforced polyester Type 4X enclosure with  RMM2, 

grounding hardware and four plugs. For Ordinary and 

Division 2 hazardous locations.

Additional Materials Required

User supplied 

enclosure

Agency-approved enclosure fitted with an aluminum 

DIN 35 rail and grounding hardware. For Ordinary and 

Division 2 hazardous locations only.

RTDs

For measuring temperatures. Make RTD selection 

based on temperature range of heat-tracing 

application. Up to eight three-wire RTDs may be used.

Extension wire

MONI-RTD-WIRE Shielded cable with three 22 AWG wires;  

PVC insulation; for use as RTD lead wire. 1000 ft reel.

MONI-RS485-

WIRE 

Shielded cable with twisted pair of 22 AWG wires;  

PVC insulation; for use as RS-485 bus. 1000 ft reel.

Conduit drain

JB-DRAIN-PLUG-

3/4IN

PN 278621 (recommended for Division 2 locations)

TOOLS REQUIRED

•  3 mm slotted screwdriver

•  Needle nose pliers

•  3/8 hex key (for RMM2-4X only) •  Wire stripper/cutter

APPROVALS

Type NM 

Nonhazardous locations

LISTED

80BJ ENERGY MANAGEMENT

EQUIPMENT SUBASSEMBLY AND

GENERAL SIGNALING 

EQUIPMENT SUBASSEMBLY

Hazardous locations

LISTED

9Z63 TEMPERATURE 

INDICATING EQUIPMENT 

FOR USE IN HAZARDOUS 

LOCATIONS

RMM2-4X (RMM2 with Type 4X Enclosure)

Class I, Division 2, Groups A, B, C, D

Class II, Division 2, Groups F, G

KIT CONTENTS

Item Qty  Description

RMM2 module

Spare fuses - 200 mA 250 V

C 2 Jumpers (Use 2 jumpers for 115 V or 1 jumper for 230 V)

Product label (for user supplied enclosures only)

 

Enclosure - not shown (for RMM2-4X only)

(RMM2-4X shown)

WARNING:

This component is an electrical device that 

must be installed correctly to ensure proper 

operation and to prevent shock or fire. Read 

these important warnings and carefully follow 

all of the installation instructions.

•   Component approvals and performance are 

based on the use of nVent -specified parts 

only. Do not use substitute parts.

•   Keep components dry before and during 

installation.

•  

NOTE:

 Leave these instructions with the end 

user for reference and future use.

A

B

C

D

Содержание Raychem RMM2

Страница 1: ...le with three 22 AWG wires PVC insulation for use as RTD lead wire 1000 ft reel MONI RS485 WIRE Shielded cable with twisted pair of 22 AWG wires PVC insulation for use as RS 485 bus 1000 ft reel Condu...

Страница 2: ...with provision for daisy chaining 5 Shorting block to select RS 485 termination mode for last RMM2 module in network 6 LEDs which indicate communications activity 7 Rotary switch 16 position to assign...

Страница 3: ...M2 The RMM2 is an electronic device that could be damaged by filings or other debris The RMM2 4X comes supplied with six 3 4 inch conduit entries for installation of power wiring RS 485 cables and RTD...

Страница 4: ...ers to the appropriate terminals 3 to select input voltage The RMM2 comes supplied jumpered for 230 volts The RMM2 has terminals for 8 three wire 100 platinum RTDs do not use other types of RTDs Selec...

Страница 5: ...ller to the last RMM2 in the system Note The RS 485 bus operates at 5V and equipment connected to it could be damaged by exposure to higher voltages Take precautions to avoid exposing the RS 485 wirin...

Страница 6: ...e communications XMT and RCV LEDs 6 are flashing Confirm that the RMM2 network does not have any duplicate RS 485 addresses Check the fuse If the resistance is greater than 10 replace 16 Use the NGC c...

Страница 7: ...nVent com 7 E INITIALIZE OR UPDATE THE NGC SYSTEM NETWORK AND ASSIGN SETTINGS FOR EACH RTD RMM2 terminal no P ID or Drawing Identification Description or location 1 2 3 4 5 6 7 8...

Страница 8: ...ght to change specifications without notice Raychem IM H56848 RMM2 EN 1805 nVent com North America Tel 1 800 545 6258 Fax 1 800 527 5703 thermal info nvent com Europe Middle East Africa Tel 32 16 213...

Отзывы: