DESCRIPTION

The nVent RAYCHEM FTC-P Power Connection and End Seal Kit is 

for use with XL-Trace, RaySol and IceStop heating cables. Materials 

for one power connection and one end seal are included in this kit. 

These installation instructions should be used in conjunction with 

the XL-Trace, RaySol and IceStop System Installation and Operation 

Manuals. For technical support contact your nVent representative  

or call nVent at 800-545-6258.

TOOLS REQUIRED

• Screw driver 

• Pen

•  Needle-nose pliers 

•  Diagonal cutters

•  Utility knife 

•  Heat gun or propane torch

ADDITIONAL MATERIALS REQUIRED  

(NOT PROVIDED IN THIS KIT)

•  UL Listed or CSA Certified junction box suitable for the location, 

with a clearance hole or threaded hub for 1⁄2-inch NPT. For 

RaySol applications, the power connection and end seal may be 

terminated in the same box.

This component is an electrical device that must be 

installed correctly to ensure proper operation and to 

prevent shock or fire. Read these important warnings 

and carefully follow all the installation instructions.
•  To minimize the danger of fire from sustained 

electrical arcing if the heating cable is damaged 

or improperly installed, and to comply with the 

requirements of nVent, agency certifications, 

and national electrical codes, ground-fault 

equipment protection must be used. Arcing may 

not be stopped by conventional circuit breakers.

•  Bus wires will short if they contact each other. 

Keep bus wires separated.

•  Keep components and heating cable ends dry 

before and during installation.

•  The black heating cable core is conductive  

and can short. It must be properly insulated 

and kept dry.

•  Component approvals and performance are 

based on the use of nVent– specified parts 

only. Do not use substitute parts or vinyl 

electrical tape.

•  Leave these instructions with end user for 

reference and future use.

HEALTH HAZARD: 

Overheating heat-

shrinkable tubes will produce fumes that may 

cause irritation. Use adequate ventilation and 

avoid charring or burning. Consult MSDS RAY3122 

for further information.
CHEMTREC 24-hour emergency telephone:  

(800) 424-9300
Non-emergency health and safety information:  

(800) 545-6258.

WARNING:

CAUTION:

APPROVALS

FTC-P

XL-Trace, RaySol, and IceStop Power Connection Kit with  

End Seal Installation Instructions

With XL-Trace and IceStop heating cables only

For Class I, Div. 2, Groups A, B, C, D

hazardous locations-GM-1XT and GM-2XT only

718K Pipe Heating Cable or 877Z De-Icing and 

Snow- Melting Equipment or 

9J86 Radiant Heating Cable

For 12XL2-CT,

-CR only

Certified with XL-Trace, IceStop 

and RaySol heating cables

-WS

-WS