Date: 2021/04/07
Page
: 18 of 47
3.4.2 Requirements for the water quality
ATTENTION
Risk of corrosion!
If aluminum is used in the external water circuit, there is a risk of corrosion.
To avoid electrochemical corrosion, the compatibility of the materials used in the
cooling module with those of the external cooling circuit must be observed.
The type and dosage of a suitable anticorrosive or antifreeze agent depends on the
structural environment and the external recooling system and must be determined
individually by the plant planner.
The following materials are used in the cooling module:
Aluminum
Brass
Copper
Stainless steel
To ensure trouble-free operation of the cooling module, the following water quality
requirements must be met.
(see also VDI 3803 / ASHRAE: Liquid cooling guidelines for Datacom equipment centers,
second edition).
Electrical conductivity:
25 mS/m - 100 mS/m at 25 °C /77 °F
Hydrogen concentration:
7,5 - 8,5 (ph-value) at 20 °C /68 °F
Chloride:
< 50 mg/l / 50 ppm
Total Hardness:
> 3 °dH < 8 °dH
Colony-forming units:
< 1000 CFU/ml
Appearance:
clear
Colour:
colourless
Содержание 10130-325
Страница 1: ...1 nVent SCHROFF Cooling Cabinet LHX User Manual Release 1 0 07 04 2021 Doc No 61130 210...
Страница 27: ...Date 2021 04 07 Page 27 of 47...
Страница 28: ...Date 2021 04 07 Page 28 of 47 Screen Upgrade...
Страница 31: ...Date 2021 04 07 Page 31 of 47 4 2 2 Display menu...
Страница 44: ...Date 2021 04 07 Page 44 of 47 23130 662 Water hoses duct for rear panel...
Страница 46: ...Date 2021 04 07 Page 46 of 47 8 5 Air flow Air flow LHX 5 kW Air flow LHX 10 kW...
Страница 47: ...Date 2021 04 07 Page 47 of 47 8 7 Noise Level Noise level LHX 5 kW Noise level LHX 10 kW...