The  temperature  control  should  only  be  installed  by  qualified

technicians  in  accordance  with  the  respective  national  electrical  codes.

The safety and protection against incidental contact is to be ensured

through  proper  installation.

The  technical  specifications  (voltage  and  current)  as  stated  on  the

product must not be exceeded!

L’installation du régulateur de température ne doit être réalisée que par un

personnel  qualifié  dans  le  respect  des  règlements  locaux  en  vigueur  concernant

l’alimentation  électrique.

Le montage doit garantir le respect des normes de sécurité et la protection contre

les  contacts  accidentels.

Les  caractéristiques  techniques  (tension  et  courant)  indiquées  sur  la  plaque

signalétique  doivent  être  impérativement  respectées  !

La  instalación  del  regulador  de  temperatura  se  realizará  solamente  por  personal

calificado,  bajo  el  cumplimiento  de  las  directivas  locales  de  alimentación  de  corriente.

Mediante el montaje se deben asegurar las medidas de protección y la protección

contra  contactos.

Las  indicaciones  técnicas  (tensión  y  corriente)  en  la  placa  de  características  no

deben  ser  superadas!

WARNING AVERTISSEMENT ADVERTENCIA

ENGLISH

Versions

:

a.  Normally closed contact  

(switching contact opens at  

rising temperature)

b.  Normally open contact (switching contact closes at rising temperature)

c.  Combination (combination of a) and b))

Applications:

The temperature controls are used to regulate heating equipment, cooling equipment, filter fans and 

heat exchangers. In addition, they can also be used as switching contacts for signal devices used as 

low− or high temperature alarms.
Installation guidelines:

The temperature controls are designed to measure the temperature in enclosures. When used in 

heating applications, they should be installed in the upper area of the enclosure as far away as 

possible from heaters or other heat−generating components. When used in cooling appl ications, they 

should be installed at the bottom of the enclosure as far away as possible from the cooling device.

Clip−mounting onto 35 mm DIN rails according to EN50022 is standard.The ventilation openings of 

the temperature control should not be covered at any time.Operating temperature range: -45 °C to 

80 °C (-49 °F to 176 °F)

Important: as operating conditions vary widely, safe operation of the temperature control is to be 

checked in the final application.
Setting recommendations:

The hysteresis (switching difference) of the temperature control should be taken into account: 

a), b) and c): 7 K± 4 K (Kelvin) In order to determine the actual set point of the normally closed contact, 

the maximum rated hysteresis should be added to the required minimum operating temperature:

Example for a):  

required minimum temperature in enclosure: 

5 C (41 F) 

Hysteresis of temperature control: 

+ 11 K (= 7 K ± 4 K) 

Set point on adjustment knob: 

16 C (61 F)