High Temperature 400°C for 2 hr

Single In-line Fans 50 / 60 Hz 
Installation and Maintenance

IMPORTANT

Please ensure that there is adequate clearance for the removal 

of the motor/fan assembly for maintenance purposes.

IMPORTANT

AV mounts isolate the fan only. Silencers/backdraught 

dampers and other "significant mass" accessories should form 

part of the fixed ductwork after the flexible connection.

1.0 INTRODUCTION

The Squif range of fans are designed for in-duct applications. 
Manufactured from galvanised steel, they are suitable for in or outdoor 
installation and can be installed in a horizontal or vertical attitude.

For full unit description, dimensional, weight and performance details 
refer to Nuaire catalogue.

The units are designed for: 

S1 DUTY - Day to day operation and in the 

event of fire a one off emergency use.

2.0 HANDLING

Handle the unit with care. Note the weight from the rating plate, lift 
using slings attached to the four lifting eyes as (see fig. 1).

Care must be taken when handling a unit/attenuator assembly fitted 
with flexible connectors as the connectors can be distorted or damaged.

Figure 1. 

 

3.0 INSTALLATION AND GENERAL ADVICE

Installation must be carried out by competent personnel, in accordance 
with good industry practice, the appropriate authority and in 
conformance with all statutory and governing regulations e.g. lEE, 
CIBSE, HVCA, BSI and EN standards etc.

Before commencing installation check that all material, including 
mounting feet and optional ancillaries are available to complete the 
work. Every unit is tested and serialised at works and a test certificate 
produced, the details are also recorded on the fan side rating plate 
which should also be referred to before handling and installation. Any 
damage or deviations should be immediately reported to the seller/
supplier/agent quoting the order and rating plate details.

Rotate the fan impeller by hand to ensure free and smooth rotation and 
that no handling or transit damage has occurred, observe the direction 
of flow/direction of rotation arrow and ensure that:

All optional accessories such as support brackets, attenuators, 
guards, flexible connectors etc. are assembled to the fan. 

Support brackets are fitted appropriate for the installed attitude - 
vertical or horizontal.

When offering the fan to the ducted system that both inlet and 
outlet connections are perfectly aligned.

It is advisable to fit flexible connectors on either side of the fan unless 
there is an open-ended inlet or discharge and the fan should be 
supported on Anti-Vibration mounts. The AV's should be levelled off to 
maximise isolation and the flexible connectors correctly aligned with 
the fan at the correct tension.

3.1 Mechanical Installation

Fans are suitable for both internal and external installation and whilst 
they can be installed in either the recommended vertical (installation 
type A) or alternative horizontal (installation type B) attitude, the 
standard brackets provided are suitable only for the more conventional 
vertical (A) mounting position.

Where silencers are to be fitted to the unit (for all sizes except 
SQF41), installation type A should be used to ensure silencer 
splitters are vertically orientated (Figure 2). SQF41 silencers are 
square and can be rotated to ensure vertical orientation in either 
installation type.

For horizontal (B) mounting (Figure 3), observe the centre of gravity 
(approximately 100 - 150mm left of flange) and fit an angle bracket 
or unistrut steel bar (not supplied) to brace the unit. Fit AV mounts 
equidistant of CG line and at a safe distance so as to level unit.

Bracket 

A

Note: Installation A silencer 

splitters are vertical 

Bracket 

Approx
CG line 

AV’s equidistant of CG

Note: Installation B silencer 

splitters are horizontal (except SQF41) 

B

Figure 2. End view of recommended vertically mounted unit 
installation (bracket supplied).

Figure 3. End view of non-recommended horizontally mounted unit 
installation (bracket by others).

Содержание Squif SQF Series

Страница 1: ...seller supplier agent quoting the order and rating plate details Rotate the fan impeller by hand to ensure free and smooth rotation and that no handling or transit damage has occurred observe the direction of flow direction of rotation arrow and ensure that All optional accessories such as support brackets attenuators guards flexible connectors etc are assembled to the fan Support brackets are fit...

Страница 2: ... 380V 3 phase 60Hz supply 400V 3 phase 50Hz supply 460V 3 phase 60Hz supply L1 L2 Low Speed High Speed L3 L1 L2 L3 Motor Terminal Box Note High Speed Supply 2U 2V 2W Link 1U 1V 1W Low Speed Supply 1U 1V 1W 1U 1V 1W 400V 3 phase 50Hz supply C1 C2 C3 L1 L2 L3 A1 A2 A2 A2 A1 A1 1 3 5 1 3 5 1 3 5 2 4 6 2 4 6 2 4 6 2U 2V 2W E For low speeds connect Contactor C1 For High speed connect Contactor C2 and C...

Страница 3: ...ce visits must be performed on the installation AT LEAST EVERY 6 MONTHS incorporating the following checks i Checking the insulation resistance R 100 MOhms 500V DC If the drain holes are blocked open them to eliminate any accumulated condensation If R 100 MOhms dry the stator in an oven and check the insulation resistance If the fault persists replace the stator The stator must be replaced 5 years...

Страница 4: ...heck that the impeller rotates freely and the inlet cone and impeller are concentric with a running clearance ITEM TICK Check that safety grilles are secure and free of obstruction Inspect all bolts fixings and electrical terminals for security Check motor for undue wear signs of overheating and apply winding insulation and continuity tests Remove all dust and dirt from impellers be especially car...

Страница 5: ...nal limits for the equipment are adhered to e g operational air temperature air borne contaminants and unit orientation 4 2 Where installation accessories are supplied with the specified equipment eg wall mounting brackets They are to be used to support the equipment only Other system components must have separate provision for support 4 3 Flanges and connection spigots are provided for the purpos...