NuAire FLATMASTER Скачать руководство пользователя страница 1

1

nuaire.co.uk 

029 2085 8400

28. 10. 19. Leaflet Number  671566

The EMC Directive

 

2014/30/EU

The Low Voltage 
Directive

2014/35/EU

FLATMASTER

Low Energy Positive Input Ventilation Unit

 

Installation and Maintenance

IMPORTANT

Whilst the installation of the Flatmaster unit may be achieved by 

a suitable craftsman, the provision of the electrical supply and the 

connection of the unit to the mains must be carried out by a qualified 

electrician.

1.0 INTRODUCTION

The Nuaire Drimaster/Flatmaster range has been curing severe 
condensation problems for over 20 years in some of the worst affected 
properties throughout the world. Its successful operation depends 
entirely upon the unit being installed strictly in accordance with these 
instructions. We would, therefore, respectfully suggest that you read 
through this guide in its entirety before commencing installation 
and then go through this guide step by step to ensure a satisfactory 
completion.

2.0 INSTALLATION

IMPORTANT

Where the systems are installed in flats, ensure all regulatory  

provisions are adhered to. Where the systems are installed in flats 

where these regulatory provisions do not apply, good installation 

practice should be observed. 

For more information please refer to the Building Regulations,  

Approved Document B (Fire safety) – Volume 1: Dwelling houses 

(2006 Edition)

The unit is designed to take fresh air from outside, clean the air, and 
discharge it into the central hallway via a system of ducting supplied by 
the installer.

The dwelling supply grille is usually installed at high level in a central 
location within the hallway, although discharging the air down the 
length of the hallway (away from the front door) should also prove 
acceptable. Unit performance may be enhanced if an existing heat 
source can warm the discharged air e.g. by locating the discharge grille 
above a radiator.

Before commencing installation decide the best position for the unit 
and where the fresh air is to come from and be discharged to. The unit 
can be installed in many different configurations and is supplied with 
enough interchangeable spigots to enable it to be used with either 
round (100mm) or rectangular ducting (121mm x 60mm).

The unit can be turned through 180° to any angle if required.

Rear entry

‘Blank off’ plate

‘Blank off’ plate

Spigot insert

Alternative
inlet position

Figure 1. Typical installations show unit with top discharge.

2.1 Spigot inserts

The unit is designed to be used with rigid ducting only. Ensure that 
when the ducting is fitted it is secured in place using wall brackets and 
screws on the duct as close to the spigots as possible to prevent the 
spigot inserts (fig. 1) or rigid ducting from being removed or accidently 
knocked off. If it is necessary to fit flexible ducting then the spigot 
inserts should be glued in place, using super glue Loctite 454 Gel, at the 
clip points 1, 2, 3 & 4 for all spigot inserts (see fig. 2).

Outlet

Inlet

1

4

2

3

1

4

2

3

1

4

2

3

Clip & glue points

Alternative inlet position

‘Blank off’ plate

Figure 2. Fitting spigot inserts. 

2.2 Fixing the unit to the wall

The unit has three mounting feet. Mark through these feet when 
the unit is in the correct position. Drill and plug wall with suitable 
fixings. Remove PCB cover and feed the electrical supply cable 
through the grommet hole (standard 1mm three core lighting cable is 
recommended) in the rear of the unit screw unit to wall (see fig. 3).

Installers must ensure the grommet provided or other suitable 
insulated grommet/bushing is used for cable entry.

Supply 
cable 
position

Supply 
cable 
(optional 
position)

AIRFLOW

Right Hand Discharge (when viewed from front)

Figure 3. Supply cable must be secured by passing RH or LH of unit 
to clamp cable to the wall (Rear view of unit shown).

Отзывы: