ESCO-CO2D

Ecosmart Connect Duct Mounted CO

2

 Sensor

 

Installation Manual

1.0 SAFETY INFORMATION

• 

The provision of the electrical supply and the connection of the unit to the mains must be 
carried out by a qualified electrician.

1.1 Hazard Symbols

 

GENERAL WARNING 

 

 

Signifies a general warning regarding hazard specified by supplementary information.

 

REFER TO INSTRUCTION MANUAL

 

 

 

Read and understand the installation and maintenance manual before installing,    

 

 

operating or maintaining this product.

1.2 Important Information

This manual contains important information on the safe and 
appropriate assembly, transport, commissioning, operation, 
maintenance, disassembly and simple troubleshooting of the product.

While the product has been manufactured according to the accepted 
rules of current technology, there is still a danger of personal injury or 
damage to equipment if the following general safety instructions and 
the warnings contained in these instructions are not complied with.

Read these instructions completely and thoroughly before 
working with the product.

Keep these instructions in a location where they are accessible 
to all users at all times.

Always include the operating instructions when you pass the 
product on to third parties.

1.3 Personal Protective Equipment

The following minimum Personal Protective Equipment (PPE) is 
recommended when interacting with Nuaire product:

Protective Steel Toed Shoes - 

when handling heavy objects.

 

Full Finger Gloves (Marigold PU800 or equivalent) - 

when 

handling sheet metal components. 

Semi Fingerless Gloves (Marigold PU3000 3DO or equivalent) 

- when conducting light work on the unit requiring tactile 
dexterity. 

Safety Glasses

 - when conducting any cleaning/cutting operation 

or exchanging filters. 

Reusable Half Mask Respirators 

- when replacing filters which 

have been in contact with normal room or environmental air.

Nuaire would always recommend a site specific risk assessment by a 
competent person to determine if any additional PPE is required. 

2.0 INTRODUCTION

Nuaire’s Ecosmart Connect Controls offer a compact, duct mounted 
carbon dioxide (CO

2

) sensor for measuring and transmitting CO

2

 levels, 

ranging from 0 to 2,000 parts per million (ppm). Nuaire’s CO

2

 sensors 

are easy to install and to operate.

The silicon-based sensor delivers high accuracy and long-term 
measurement stability (±100 ppm) over a five-year period without 
calibration. The diffusion-aspirated, single-beam, dual-wavelength 
sensor structure is remarkably simple. It consists of an infrared (IR) 
source, a sample cell, an IR detector, and a tuneable interference filter 
that enables measurements at two wavelengths. This innovative design 
provides precise reference readings that eliminate the typically broad 
deviation expected from a traditional CO

2

 sensor.

The ESCO-CO2D duct mounted CO

2

 sensor is intended to  

provide an input to equipment under normal operating conditions.

Where failure or malfunction of the sensor could lead to personal injury or 
property damage to the controlled equipment or other  
property, additional precautions must be designed into the control system. 
Incorporate and maintain other devices, such as supervisory or alarm 
systems or safety or limit controls, intended to warn of, or protect against 
failure or malfunction of the sensor.

2.1 MECHANICAL INSTALLATION
2.2 Parts Included

The duct mount CO

2

 sensor is shipped assembled. It consists of three 

main parts: base and Printed Circuit Board (PCB), cover, and mounting 
flange with four screws (for probe depth adjustment). A conduit 
adaptor is also included.

2.3 Mounting Location

When selecting a location for the sensor, note the following:

 The sensor is designed for duct mounting in any position.

 The probe is best mounted in the return air stream.

 The device should penetrate the duct by a minimum of 76mm to 
ensure the sensing part of the element is fully in the air  stream.

 The sensor should be placed in an area free of condensation.