ES-PIR2 Sensor

Installation Guide

10m sensor connection
wire (supplied).

Clearance aperture for wire
should be approx 20mm dia
to allow passage of plug end.
Allow approx 75mm of wire 
through for fitting to the 
backplate.

Wire can be located behind
a wall panel or fixed to wall 
surface.

Wall

To fan connector 
box terminal 
marked NET

Cable from bottom 
half of unit mounted 
on the wall.

Plug end mounted into the
PCB socket inside the front
half of the unit.

Feed the cable through the 
hole in the bottom half of the 
unit and mark the fixing hole 
locations on the wall. 
Fix this half of the unit to the 
wall using the fasteners 
provided.

Figure 1.

Figure 2.

Figure 3.

Figure 4.

Figure 5.

Line up the slots 
in the 2 halves,
push together
and rotate to
lock them 
together.

11

. 0

5.

 17. Leaflet Number 671416

IMPORTANT! Please refer to the 

installation instructions of the fan to

check the compatibility of this sensor.

Parts check list:

ES-PIR2 Passive Infra red detector

1 off 10 metre length of plugged

SELV cable

ES-PIR2 Occupancy
Sensor

Designed to be compatible with the

Ecosmart system, this PIR unit is supplied

with a pre-plugged, 10 metre length of 

communications cable. Note: longer lengths

are available if required.

The sensor operates with Safe Extra Low

Voltage (SELV) with power supplied from

the fan unit via the communications cable.

The ES-PIR sensor will activate the system

when movement is detected. An adjustable

1-60 minute timer is incorporated to provide

a run on facility.

Installed Environment

0 - 40

0

C up to 90%RH non-condensing.

Fault indication

The LED will change from green to red if

any fan connected in that zone has failed.

Multiple Sensors

Multiple sensors can be connected to the

network. Please refer to the actual fan

installation instructions for exact 

quantities.

Installing the Sensor

The unit must be installed away from any

direct source of heat (e.g. radiators) and

areas where it would be subjected to steam

or water spray.

The mounting surface must be vibration

free.

The unit is supplied complete with 10 metres

of connecting cable with plugs attached.

Fasteners for wall fixing are included in the

package. 

a) Fix one end of the 10m cable to the fans

customer connection box (connection

sockets marked NET).

b) Select a suitable location for the sensor

and arrange the cable in position. Leave

approx. 75mm of the cable free at the

mounting point to ease the connection 

of the plug. (Fig. 1).

c) Hold the base of the unit with one hand

and the top half with the other. Twist the

upper half anti-clockwise to open the unit.

(Fig. 2).

d) Feed the cable through the hole of the

lower half of the unit and mark the

locations of the fixing holes on the wall.

There is a raised line inside the base of the

unit to aid alignment to the horizontal or

vertical. (see Fig.3).

e) Fix the base of the unit to the wall using

the fasteners provided, or other suitable

fasteners.

f) Plug the cable into the socket of the PCB.

(Fig.4).

g) Align the slots of the upper and lower

halves of the unit and twist the upper half

clockwise to lock the 2 halves together.

(see Fig. 5).

Data cable installation

A 4-core SELV data cable is used to 

connect devices. 

Do not run data cable in the same conduit

as the mains cables and ensure there is a

50mm separation between the data cable

and other cables. The maximum cable run

between any two devices is 300m when it

is installed in accordance with the 

instructions.

Please note that the total data cable length

used in any system must be less than

1000m. Keep the number of cable joints to 

a minimum to ensure the best data 

transmission efficiency between devices.

Adjusting the run on timer
ES-PIR2 Run on timer 
(1-60 minutes)

Use a small screwdriver through the hole 

in the casing to reach the adjustment

potentiometer. Gently turn the screwdriver

either clockwise or anti-clockwise to

increase or decrease the set point.

Alternatively, open the unit to gain easy

access to the potentiometer.

When adjustments are made to the sensor,

the LED light on the sensor front will flash

on and off to show the set point. First,

green flashes will indicate the set point in