The EMC Directive 
2014/30/EU  
The Low Voltage 
Directive 
2014/35/EU

The unit must remain switched on at all times to maintain ventilation within
the dwelling. Turning the unit off will cause long term damage to the unit
and building fabric.

This appliance is not intended for use by persons (including children) with
reduced physical, sensory or mental capabilities, or lack of experience and
knowledge, unless they have been given supervision or instruction 
concerning the use of the appliance by a person for their safety. Children
should be supervised so that they do not play with the appliance.

Installation and Maintenance

MRXBOX95-WH1-1Z (Standard Unit)
MRXBOX95-WH1-1Z-OH (Opposite hand Unit)
MRXBOX95AB-WH1-1Z  (Standard Unit)
MRXBOX95AB-WH1-1Z-OH (Opposite hand Unit)

Mechanical Ventilation Units with Heat Recovery for Wall Mounting

1

27. 11. 17. Leaflet Number 671721

Figure 1. Airflow through unit (Standard unit).

Figure 2. Airflow through OH unit (Opposite hand unit).

Intake air 
from outside

Extract air 
from house

Supply air 
to house

Exhaust air 
from house
to outside

Extract air 
from house

Intake air 
from outside

Exhaust air 
from house
to outside

Supply air 
to house

Spigot fixing plate

Transportation fixings

1.0 Introduction

The WH1-1Z wall mounted range of units are designed to offer

 

improved sound levels and an aesthetically pleasing installation by

 

housing a Mechanical Ventilation with Heat Recovery unit (MVHR)

 

and attenuator inside an acoustically lined enclosure.

The MVHR unit is fitted with two independent fans. Each fan has full

 

speed control for background and boost ventilation rates. To recover

 

heat from the extract air the heat exchanger block is utilised. The heat

 

exchanger can recover up to 95% of the normally wasted heat.

If the MVHR unit has integral automatic 

HX 

bypass 

(AB models only) 

The bypass damper shall open automatically via 

a wax actuator allowing the air to bypass the heat exchanger to 
deliver fresh filtered air during the warmer months.

2.0 Installation

Installation must be carried out by competent personnel in accordance
with the appropriate authority and conforming to all statutory 
governing regulations. All mains wiring must be in accordance with the
current I.E.E. Regulations, or the appropriate standards. Ensure that the
mains supply (Voltage, Frequency and Phase) complies with the rating
label. 

Please allow a minimum of 430mm in front of the enclosure for
MRXBOX95-WH1 models and 360mm for MRXBOX95AB-WH1 units.

The fan must be installed indoors, on a suitable wall away from direct
sources of frost, heat, water spray or moisture generation. 
For a vibration-free result the unit must be mounted to a non-
reverberant wall.

2.1 Transportation fixings

To prevent damage during transportation the product is shipped
with securing fixings, these can be found front and centre of the
enclosure top panel (fig.3).  These must be removed before use, fail-
ure to do so will result in excessive vibration and noise.  The screws
removed can be discarded and replaced with rubber caps provided.

Figure 3. Securing fixings.

2.2 Wall Mounting the MVHR Unit

The unit is designed for wall mounting only on a solid wall, a gypsum
block/plasterboard wall will not suffice, examples of suitable 
installation are shown overleaf. The wall brackets supplied should be
secured to the wall using suitable fixings (supplied by others) as per
the dimensions given in fig.4, the head of the chosen fixing should
protrude no more than 8mm from the wall bracket. The enclosure
assembly can then be lifted using suitable equipment and moved into
position so it is sitting directly on the wall brackets (ensuring the rear
panel of the enclosure is not in contact with the wall bracket fixings).
The enclosure can be secured to the wall brackets using the 4x M8 
fixings supplied. 

No part of enclosure should be in contact with the building structure,
the only components that should be in contact are the wall mounting
brackets.

Figure 4. Dimensions for fitting wall brackets.

Note: Care must be taken to ensure the unit is installed true in all 3 
dimensions. Failure to do so may result in overflow from the internal 
condensation drip tray.

25

25

704 crs

9.1 dia.

30

94

94

33

Nuaire: A Trading Division of Polypipe Limited  

Western Industrial Estate

 

Caerphilly  United Kingdom  CF83 1NA  

T: 029 2088 5911  F: 029 2088 7033  E: [email protected]  W: www.nuaire.co.uk

Содержание Ecosmart MRXBOX95-WH1-1Z

Страница 1: ...opriate authority and conforming to all statutory governing regulations All mains wiring must be in accordance with the current I E E Regulations or the appropriate standards Ensure that the mains supply Voltage Frequency and Phase complies with the rating label Please allow a minimum of 430mm in front of the enclosure for MRXBOX95 WH1 models and 360mm for MRXBOX95AB WH1 units The fan must be inst...

Страница 2: ...nd the cover plate slid along the length to bond against the base panel of the enclosure preventing noise breakout fig 7 Figure 7 1 The condensate must be discharged under a water level in a U trap drainpipe or an alternative drain method which acts as an airlock 2 If using a U trap please ensure the U trap has been filled to a suitable level of water to avoid any air locks 3 If the condensation p...

Страница 3: ...et duct and the air outlet duct from the unit these ducts should be insulated Ducting must be installed in such a way that resistance to airflow is minimised Bends should be kept to a minimum A minimum distance of 300mm between the appliance and any bends in ductwork is recommended Ideally 150mm diameter or 220 x 90mm rectangular ducting should be used Refer to dwelling design drawing figure 10a a...

Страница 4: ...sanitary accommodation should be omitted from the step 2 calculation Step 3 The required airflow rates are as follows n the maximum whole dwelling extract ventilation rate e g boost should be at least the greater of step 1 and step 2 Note that the maximum individual room extract rate should be at least those given in table 1 for minimum high rate n the minimum air supply rate should be at least th...

Страница 5: ...pply duct Air supply to lounge via Air Valve in ceilings Extract air from kitchen bathroom via Air Valve in ceilings Air supply to bedrooms via Air Valve in ceilings Top of ceiling void Top of ceiling void Air supply to bedrooms via Air Valve in ceilings Insulated extract duct Insulated extract duct Minimum distance as specified in building regulations MVHR DRAIN Condensate drain uninsulated drain...

Страница 6: ...ion to Remote Fail Indicator Ref MRXBOX95 RFI Optional 3 2 Figure 11a Note Wiring is for reference purposes only as the connections in fig 11a are factory fitted The unit is pre wired with a 2 metre fly lead Disconnection from the supply mains must be incorporated within the fixed wiring in accordance with the wiring regulations and shall have a minimum contact separation of 3mm Disconnection from...

Страница 7: ...l covering the control has an adhesive panel which should be removed post commissioning to prevent tampering 8 Speed 1 is limited to never exceed the speed 2 when commissioning the speed 2 should always be set first 6 1 Speed 3 The unit has to ability to override both speed 1 and speed 2 to operate the fan to maximum airflow See wiring diagram for details of operating this facility 6 2 Humidity ad...

Страница 8: ...arranty The 5 year warranty starts from the day of delivery and includes parts and labour for the first year and parts only for the remaining 4 years This warranty is void if the equipment is modified without authorisation is incorrectly applied misused disassembled or not installed commissioned and maintained in accordance with the details contained in this manual and general good practice The pr...