The Basicmaster and Minimaster user
controls are compatible with our range
of frequency inverter speed controls 
and designed for simple and easy 
management of inverter and fan.

Parts check list:

BASICMASTER

Manual control

1 off 10 metre length of 
plugged SELV cable

MINIMASTER/10

7 Day Timeclock control

1 off 10 metre length of 
plugged SELV cable

BASICMASTER

Offers a facility to manually vary 

fan speed, via a rotary dial, between 

the minimum and maximum speeds 

set within the inverter parameters.

Two faced-mounted system system 

status lights record power (green) 

and fan status (green/red).

MINIMASTER-10

Manually vary speed via the key pad

within the minimum and maximum 

speeds set at the inverter.

Programme the seven day timer via 

the key pad (21 on/off programmes).

Manually override the timer via the 

key pad.

Manually set ‘holiday mode’ without 

disruption to timer settings.

Handling

Always handle the controls carefully to

avoid damage and distortion.

Installation

The installation must be carried out 

by  competent personel in accordance

with the appropriate authority and 

conforming to all statutory and govern-

ing regulations i.e. IEE, CIBSE, CCHSE,

HVCA etc.

The unit is suitable for indoor use only.

Mount on a secure, vibration free vertical

surface away from any direct source of

heat and areas where it would be 

subjected to waterspray. The maximum

permissible ambient temperature is 40

o

C.

a) Remove the backing plate/mounting

cradle shown dotted in figure 1. Offer the

cradle to the selected mounting position,

mark and fix.

b) Draw approx. 75mm of data cable

through the cradle and plug in to the rear

socket of the control, paying particular

attention to plug/socket colour code for

correct orientation

c) Finally clip the control into the cradle.     

The matched frequency inverter will have

been pre programmed to suit the user

control prior to delivery. 

Install the inverter in accordance with 

the instructions provided with it.

Connect the other end of the data cable

to the inverter, remove the plug from the

data cable and terminate, following the

instructions provided with the inverter.

Data cable installation

A 4-core 10 metre length of SELV data

cable is used to connect devices. Longer

lengths are avavailable if required. 

Do not run data cable in the same conduit

as the mains cables and ensure there is a

50mm separation between the data cable

and other cables. The maximum cable run

between any two devices is 100m when it

is installed in accordance with the

instructions.

II

I

I

I

I

I

I

I I I

Power

Ventilation Control

Status

A

B

C

Figure 2.

Leaflet Number 671198 May 2003

NuAire Limited

Western Industrial Estate Caerphilly  United Kingdom CF83 1NA

Telephone:  029 2088 5911   Facsimile: 029 2088 7033

Email: [email protected]   www.nuaire.co.uk

BASICMASTER

and 

MINIMASTER/10

Extra Low Voltage User Controls 
(for use with frequency inverters)

The EMC Directive 
89/336/EEC   
With modification 
92/31/EEC  
The Low Voltage 
directive 73/23/EEC

97 mm fixing ctrs

147 Cover open

54

Cable entry

Cable 
entry

Drill 2 holes in wall 
surface for 6mm dia.
wallplugs (supplied).

163 mm overall

Cover

Figure 1. 

Drill pattern and fixing details.

Unit dimensions and weights

A

B

C

Weight

Basicmaster 163

40

75

0.25 Kg

Minimaster

163

23

75

0.17 Kg