Nu-Flame SYNERGY ELLESSE Скачать руководство пользователя страница 29

29 

 

21 - FAULT FINDING GUIDE, SYMPTOMS AND POSSIBLE CAUSES 

Important : 

In instances where it is indicating that the main control system needs changing, (specifically either of  the 

Thermatronic Control Systems), you should investigate returning the whole Burner Control Assembly  to Nu-Flame for rectification as 
this could be the least cost option. 

a. 

Prior to any Servicing ensure that you have carried out the procedures in Section 20.1 General (Servicing). 

b. 

Check the supply pressure at the isolation elbow. 

c.  Important 

: With either of the Thermatronic Systems always change the batteries before carrying out any Fault Finding.

 

d.

  Check the supply pressure at the isolation elbow. 

 

21.1 - RESETTING THE ELECTRONIC CONTROL (Applies to Thermatronic RF System Only) 

Full Reset - 

If a new handset is obtained the control system will need to learn the handset’s unique code via a Full Reset. 

 Also, if the fire is not working and the Basic Reset (described on page 7) has not worked a Full Reset can be carried out: 
 

a.   

Open the outer door by pulling at the left side to release it from the magnetic catches and open the outer door, locate the  

      electronic Receiver Box.   

b. 

Locate the Reset Hole on the side of the Receiver and using a pen press and hold in the Reset button until you hear two beeps. 

c. 

The first beep is short and the second beep is long. After the second beep release the Reset Button. 

d. 

Now on the Handset, within the next 20 seconds press and hold the Small Flame Button until you hear two additional short beeps 

      confirming the code is set in the Receiver.  

e. 

If you hear one long beep the Code as not been set so repeat the procedure. 

f. 

If the Handset still does not work check the wiring and or replace the Receiver and Handset .

 

 
21.2 - NO SPARK IGNITION 

a.

   Replace the batteries in the receiver and handset see Section 3.4 and check the Control. 

b.

   Check there is no vermiculite shorting out the electrode or blocking gas from the pilot. 

c.

   Check the condition of the Ignition lead and ensure it is connected to both the ignition electrode and receiver. Replace if required. 

d.

   Check that gas is flowing from the pilot during the ignition sequence. Clean or Replace as required. 

e.

   Listen to the control to hear if the pilot gas solenoid is opening.  

f.

   Change the receiver and the handset at the same time and/or gas control. Refer to Diagram for Cable connections in section 22.  

Important : 

In instances where it is indicating that either of the main control systems need changing, you should investigate  

   returning the whole Burner Control Assembly to Nu-Flame for rectification as this could be the least cost option. 
 

21.3 - PILOT GOES OUT AFTER FIRST LIGHTING 

a.

   Check there is no vermiculite blocking the flame to the thermocouple. 

b.

   Check the thermocouple is tightly connected to the control. 

c.

   Change the pilot assembly as a new thermocouple may be required. 

d.

   Change the receiver and the handset at the same time and/or the gas control. 

   Refer to Diagram for Cable connections on in section 22. 

e.

   Also see Section 21.2 & 21.4 

 

21.4 - PILOT LIGHTS BUT MAIN BURNER DOES NOT LIGHT 

a.

   Check there is no vermiculite blocking the flame from the pilot to the main burner. 

b.

   Check if the main control knob on the control is turning to the high setting and listen to hear if the solenoid valve is opening. 

 

Change the receiver, infrared sensor and the handset at the same time and/or the gas control. Refer to Diagram for Cable  

 

connections in section 31.  Check c. (below) before replacing any parts. 

c.

   Check if the main injector is blocked. Clean or Replace.   

d.

   Both of the Thermatronic Controls have a pressure point to allow the Burner Pressure to be checked.  

      It is at the left side of the Control and is the rear Pressure Test Point. Ensure the Screw is gas tight after the test. 

Important : 

In instances where it is indicating that either of the main control systems need changing, you should investigate  

   returning the whole Burner Control Assembly  to Nu-Flame for rectification as this could be the least cost option. 
 

21.5 - PILOT FLAME SHORTENS, OR GOES OUT WHEN MAIN BURNER IS SELECTED 

a.

   Monitor the supply pressure at the isolation elbow as the main burner lights. If pressure drops, check gas pipe sizing, quality of pipe 

bending. Check for debris in the gas supply and or gas filter if fitted. 

b.

   Check that another appliance is not affecting the gas supply pressure.    

 

21.6 - POOR FLAME PICTURE 

a. 

Check the supply pressure is correct at the isolation elbow. If the pressure is low, check gas pipe sizing, quality of pipe bending. 
Check for debris in the gas supply and or gas filter if fitted. 

b. 

Both of the Thermatronic Controls have a pressure point to allow the Burner Pressure to be checked.  

      It is at the left side of the Control and is the rear Pressure Test Point. Ensure the Screw is gas tight after the test. 

c. 

Check that another appliance is not affecting the gas supply pressure.  

d. 

Check there is not a flue/ventilation problem – carry out a spillage test. 

f. 

Check fuel bed layout as detailed in Section 17. 

   ABOUT THE FLAME PICTURE: THE SYNERGY RANGE HAS A UNIQUE BURNER SYSTEM WHERE THE FLAME SIZES 
                                    AND COLOURS WILL CHANGE LIKE A REAL FIRE AND WILL VARY FROM FIRE TO FIRE. 
 

IT IS PERFECTLY NORMAL FOR THE FIRE TO MAKE POPPING & BURBLING NOISES WHEN LIT. 

 
 
 
 

 

Содержание SYNERGY ELLESSE

Страница 1: ...FIRE IS HEAVY AND ASSISTANCE SHOULD BE SOUGHT WHEN LIFTING ALL INSTRUCTIONS MUST BE LEFT WITH THE USER FOR SAFE KEEPING MANUFACTURED by Nu Flame Limited Unit 4 Kimpton Trade Business Centre Minden Ro...

Страница 2: ...12 Hole in the Wall Installations for Steel Glass Trim Styles 12 With Appropriate Sealing Frame 13 Hole in the Wall Installations for Echo Trim Style 14 14 Hole in the Wall Installations with Marble...

Страница 3: ...rone to being chipped or scratching 1 2 Removal of Components a Fires Ordered with Steel or Glass Trims i The Outer Door will have to be removed and stored carefully to allow access for removal of the...

Страница 4: ...he Fire can be installed into a suitably designed fire surround with a 150 C Rating v Take care with some Micro Marble Materials claiming a 150 C Rating as they may give off odours blister or discolou...

Страница 5: ...nked by arrow Please note that you can have the flame height anywhere between maximum and preset low For fine adjustment simply tap the large and small flame buttons d Switching Off Press the red off...

Страница 6: ...esent room temperature the fire will go straight to the Standby Setting until the temperature drops below the Set Temperature at which point the main burner will relight Note The Room Temperature is s...

Страница 7: ...ELDERLY OR INFIRM OR PETS ARE LEFT IN ATTENDANCE 3 5 RESETTING THE MERTIK MAXITROL LOGIC CIRCUITS IF THE HANDSET DOES NOT WORK APPLIES TO BOTH CONTROL SYSTEMS Must only be done when the fire is Cool B...

Страница 8: ...of the door Follow instructions in section b above e The logs must not be cleaned or moved f The outer surfaces of the fire can be cleaned with a damp lint free cloth do not use abrasive cleaners IMPO...

Страница 9: ...FORE PROCEEDING WITH THE INSTALLATION READ THESE INSTRUCTIONS CAREFULLY THESE INSTRUCTIONS SHOULD BE LEFT WITH THE USER FOR SAFE KEEPING AND FUTURE SERVICING PRIOR TO INSTALLATION ENSURE THAT THE GAS...

Страница 10: ...Height mm Synergy Ellesse Echo Trim with Metal Door 1140mm 540mm Synergy Ellesse Echo Trim with Glass Door 1140mm 540mm Synergy Ellesse Steel Trim No Sealing Frame 1135mm 560mm Synergy Ellesse Steel...

Страница 11: ...PPLIANCE SEEK EXPERT ADVICE 10 VENTILATION a No additional purpose provided ventilation is normally required for the fire when installed in the UK however this must be confirmed by the Spillage Test s...

Страница 12: ...rials d No combustible materials must present in the builders opening e The base of the builders opening must be flat level and square to the wall f The builders opening should have provision for a ga...

Страница 13: ...rs opening d If the silicone sealing strip is not compressed and there are gaps they must be filled with a suitable sealant fireclay or high temperature silicone Wall staining may occur if the seals a...

Страница 14: ...placed too close e No combustible material e g curtains must be closer than 500mm to the builders opening The wall between the sealing frame and any shelf would become hot Therefore we do not recomme...

Страница 15: ...with a suitable sealant fireclay or high temperature silicone j Refit the burner mounting plate assembly by first putting the Receiver through the opening then tilt the assembly and slide it into the...

Страница 16: ...ng structural check may be required c The builders opening must be constructed from Non combustible materials d No combustible materials must present in the builders opening e The base of the builders...

Страница 17: ...ay in position to make a seal against the top edge of the slip at the base of the builders opening and the front face of the slips where they locate against the rear of the Fire outer frame While slid...

Страница 18: ...any rendering building work is allowed to thoroughly dry out before Installation IMPORTANT Dry lined walls ensure that any air gaps between the back of the plasterboard and wall are sealed around the...

Страница 19: ...slightly and slide it home ensuring that the sealing strips on the underside of the front riser channel and the rear of the Fire outer frame stay in position to make a seal against the base of the fi...

Страница 20: ...y Breast will occur e The Wall Mounted Television must be mounted on a suitable bracket or angled bracket that meets the Television Manufacturer s requirements and spaces the Television at least 35mm...

Страница 21: ...osition for a Wall Mounted Television Must meet the Installation Requirements of these Instructions e The Nu Flame Television Glass Heat Shield is only suitable for the Nu Flame Synergy Range of Gas F...

Страница 22: ...the Fire s Installation Instructions and the Fire Surround meets the Minimum Dimensions as detailed in the Diagrams Below b You Must take account of the Television Manufacturer s Installation requirem...

Страница 23: ...fuel tray g Place the large rear log No 1 to the rear of the fire on the fuel tray ensuring that the cut out in the log sits behind the pilot shield and that it is central about the burner h Place lo...

Страница 24: ...n the log support at the front k Place log No 5 next to log No 6 locating it on the peg and the cut out in the rear log l Place the last log No 4 so that it locates on the central peg and rests in the...

Страница 25: ...Emberglow material is a consumable material and as a limited life You can buy replacements through your local Nu Flame Ltd Stockist or Installer q For Synergy Perspective Glass Wall Mounted Installati...

Страница 26: ...m or adjacent rooms running at high The fire should continue to clear its combustion products Also operate any other flued appliance in the same or neighbouring rooms and ensure they continue to funct...

Страница 27: ...ii Now secure the upper Hinge Pin with the fixing screw provided as shown the door should then be closed and held shut by the magnet catches Very Important The Hinge Pin Screw Must be fitted to ensur...

Страница 28: ...SES WHEN LIT 20 SERVICING 20 1 GENERAL Note Servicing must be carried out by a registered installer a The fire does not have to be removed for Servicing b Check the operation and ignition of the fire...

Страница 29: ...Burner Control Assembly to Nu Flame for rectification as this could be the least cost option 21 3 PILOT GOES OUT AFTER FIRST LIGHTING a Check there is no vermiculite blocking the flame to the thermoco...

Страница 30: ...ork d Change the Handset and or Receiver and or Burner Control System Important In instances where it is indicating that either of the main control systems need changing you should investigate returni...

Страница 31: ...5 4 The fire must be Installed serviced by a properly qualified in accordance with Local National Codes Installation Engineer and in accordance with these Installation Instructions Supplier Nu Flame L...

Страница 32: ...fire must be Installed serviced by a properly qualified in accordance with Local National Codes Installation Engineer and in accordance with these Installation Instructions Supplier Nu Flame Limited...

Страница 33: ...33 23 DIAGRAM OF INFRARED CONTROL SYSTEM...

Страница 34: ...elivery to us We will not be liable for any such breakages or losses Under no circumstances should any attempt be made to repair the burner on site without our express knowledge and approval during th...

Отзывы: