          INSTALLATION GUIDE FOR THE  

 

   

ENVIROMUX-AV-LC-E7 

 
 
 
 
 
 
 

INTRODUCTION 

The NTI ENVIROMUX-AV-LC Air Velocity Sensor monitors air flow rate when connected to an ENVIROMUX-16D, ENVIROMUX-
5D or ENVIROMUX-2D Enterprise Environment Monitoring System (SYSTEM).  When connected to a SYSTEM via the 7 foot   
cable provided, the air flow rate can be monitored and the SYSTEM can be configured to alert users as to variations in that 
movement. 
 

Features:  

 

¾

 

Reliable sensor for measurement of air velocity. 

¾

 

Flow range: 0-82 ft/s (0-25 m/s). 

¾

 

Accuracy: ±1.6 ft/s (±0.5 m/s) from 0 to 49 ft/s @21°C (0 to 15 m/s). 

¾

 

Includes mounting hardware. 

¾

 

Operating temperature: 32 to 158°F (0 to 70°C). 

¾

 

Probe dimensions: 6.3x0.6 inches (160x15 mm). 

¾

 

Probe material: PA 2200. 

¾

 

Cable length of 7 feet, but can be extended to 1000 feet (use NTI# RJ45-FF - included) 

¾

 

Powered by ENVIROMUX-2D/5D/16D. 

¾

 

Compatible with ENVIROMUX-2D/5D/16D.  

o

 

ENVIROMUX-2D: only compatible with Rev C units (features two power inputs). 

¾

 

Regulatory approvals: CE, RoHS. 

¾

 

Compatible with ENVIROMUX-FSC Fiber Converter/Extender.  

o

 

Use to extend sensor up to 1.2 miles (2 km) from the ENVIROMUX unit.  

 
 
 

INSTALLATION 

 

 

ENVIROMUX-AV-LC can be mounted using the mounting adapter provided.    When mounting the adapter, be sure to align the 
mounting screws in line with the air flow.   The key should be positioned towards the source of the airflow.       
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

Note: The ENVIROMUX-xD must be 
running firmware version 2.10 or later 
in order to use the ENVIROMUX-AV-
LC with it.   Refer to the  
ENVIROMUX-xD manual for firmware 
upgrade instructions as needed.  