TFTN 085-199 Installation and Operation Manual
89
16.3.2.6 Restore/Backup
The factory settings are stored in memory in the PCB and can be restored at any time
using the “Reset PCB to Factory
Defaults Settings” option.
After 30 minutes of the boiler first being powered on, the PCB settings are automatically backed
up to the display memory for future use (i.e., in the event the PCB is replaced). The operator can at any time select to back
up the PCB settings to, or restore the PCB settings from, the display memory, or an external memory (USB Flash Drive)
connected to the USB port of the display. See Figure 16-13 and Table 16-12 for details.
Figure 16-13 Restore/Backup Menus
Table 16-12 Restore/Backup
Option
Parameter
Description
Reset PCB to Factory
Default Settings
24.19.0
Resets the PCB setting to the values originally set on the PCB at the factory. Note:
if it is a replacement PCB the settings will be reset to the default settings of a
replacement PCB.
Backup PCB Settings
NA
Select to back up the PCB settings to the Display Memory, or to an external
memory device (USB Flash Drive).