5.Operation
Group 8 control system settings
5-51
ID
Contents
17
Positioning Methods
[EDGEPOS]
Control power a reactivation after setting.
Setting range
Unit
Standard value
00 to 01
-
00:Pulse_Interval
■
Select the Encoder pulse positioning.
◆
Positioning accuracy is improved by selecting Edge positioning when the encoder
resolution is coarse. However, this may cause the driving sound of the mechanical
system to increase as this edge is always the center of vibration.
◆
Select standard value for usual operation.
Selection
Contents
00
Pulse_Interval
Specify Pulse Interval
01
Pulse_Edge
Specify Pulse Edge
18
In-Position Signal/ Position Deviation Monitor
[PDEVMON]
Setting range
Unit
Standard value
00 to 01
-
00:After_Filter
■
Select in-position signal (INP) and Position deviation monitor output before and after passing
through the Position Command Filter.
◆
For 00 After_Filter, use the Position deviation value of the Position controller.
◆
For 01 Before_Filter, use the Position deviation value based on Position command
before FF vibration suppressor control.
◆
With system parameter ID0A Position Control Selection at 01 Model 1 Model Following
Control, or 02 Model 2 Model Following Vibration Suppress Control, 01: Before_Filter
always operates no matter the selection.
Selection
Contents
00
After_Filter
Compare Position command value with Feedback value after
passing through the filter.
01
Before_Filter
Compare Position command value with Feedback value before
passing through the filter.
Pulse interval positioning
Phase A
Phase B
Edge positioning
+
-
Position
control
00: After_Filter
FF vibration
suppressor
control
Position loop
encoder
Position
command
smoothing
Electronic
gear
+
-
01: Before_Filter
Position
command
filter
Model