3 Operation Theory
PCS-9611 Feeder Relay
3-67
Date: 2014-04-08
6
25.t_ClsCB
The circuit breaker closing time setting of the
closing synchronism check function
0.02~1.00s
0.001s
7
25M.U_Diff
The voltage difference setting of the manual
closing synchronism check function
2~120V
0.001V
8
25M.f_Diff
The frequency difference setting of the manual
closing synchronism check function
0~2Hz
0.001Hz
9
25M.df/dt
The frequency rate-of-change setting of the
manual closing synchronism check function
0~3Hz/s
0.001
Hz/s
10
25M.phi_Diff
The phase angle difference setting of the manual
closing synchronism check function
0~60°
1°
11
25M.t_Wait
The waiting time setting of the manual closing
synchronism check function
0.01~30s
0.001s
12
25M.Opt_DdChk
The setting for selecting the dead check mode of
the manual closing function
1~7
1
13
25M.En_SynChk
The logic setting of the synchronism check
function of the manual closing function
0~1
1
14
25M.En_DdChk
The logic setting of the dead check function of the
manual closing function
0~1
1
3.19 Mechanical Protection
3.19.1 Mechanical Protection Theory
This relay can provide up to 4 programmable binary inputs for mechanical protection. If a binary
input which is used as a mechanical protection input is energized, this relay will issue an operation
signal after a predefined time delay.
The following figure shows the logic diagram of the No.1 mechanical protection. Other mechanical
protections have the same functional logic with the No.1 mechanical protection.
[MR1.Op]
&
[MR1.Blk]
[MR1.Input]
[MR1.En]
[MR1.En1]
[MR1.St]
t
MR1
0
Figure 3.19-1 Logic diagram of the No.1 mechanical protection
Where:
[MR1.Input] is the mechanical protection input signal which can be from a binary input;
“t
MR1
” is the setting [MR1.t_Op], the time setting of the No.1 mechanical protection;
[MR1.En] is the logic setting of the No.1 mechanical protection;
[MR1.En1] is the binary signal for enabling the No.1 mechanical protection;
[MR1.Blk] is the binary signal for blocking the No.1 mechanical protection.
Содержание PCS-9611
Страница 1: ...PCS 9611 Feeder Relay Instruction Manual NR Electric Co Ltd...
Страница 2: ......
Страница 10: ...1 Introduction PCS 9611 Feeder Relay 1 b Date 2014 04 08...
Страница 30: ...2 Technical Data PCS 9611 Feeder Relay 2 14 Date 2014 04 08...
Страница 36: ...3 Operation Theory PCS 9611 Feeder Relay 3 f Date 2014 04 08...
Страница 108: ...4 Supervision PCS 9611 Feeder Relay 4 b Date 2014 04 08...
Страница 116: ...5 Management Function PCS 9611 Feeder Relay 5 b Date 2014 04 08...
Страница 120: ...5 Management Function PCS 9611 Feeder Relay 5 4 Date 2014 04 08...
Страница 218: ...9 Configurable Function PCS 9611 Feeder Relay 9 b Date 2014 04 08...
Страница 232: ...9 Configurable Function PCS 9611 Feeder Relay 9 14 Date 2014 04 08...
Страница 262: ...11 Installation PCS 9611 Feeder Relay 11 b Date 2014 04 08...
Страница 272: ...12 Commissioning PCS 9611 Feeder Relay 12 b Date 2014 04 08...
Страница 292: ...13 Maintenance PCS 9611 Feeder Relay 13 b Date 2014 04 08...
Страница 296: ...14 Decommissioning and Disposal PCS 9611 Feeder Relay 14 b Date 2014 04 08...
Страница 298: ...14 Decommissioning and Disposal PCS 9611 Feeder Relay 14 2 Date 2014 04 08...
Страница 300: ...15 Manual Version History PCS 9611 Feeder Relay 15 2 Date 2014 04 08...