Specifications
Digital Inputs DC
Inputs per Module
12 (including 4 HSC inputs)
Faixa de tensão de entrada
12 VDC / 24 VDC
Absolute Max. Voltage
35 VDC Max.
Input Impedance
10 k
Input Current
Positive Logic
Negative Logic
Lower / Upper Threshold
0.3 / 0.8 mA
-2.1 / -1.6 mA
Min / Max Upper Threshold
3 VDC / 8 VDC
OFF to ON Response
1 ms
ON to OFF Response
1 ms
HSC Max. Switching Rate
10 kHz Totalizer/Pulse, Edges
5 kHz Frequency/Pulse, Width
2.5 kHz Quadrature
Relay Outputs
Outputs per Module
6 relay SPST-NO
Max. Output Current per Relay
3 A at 250 VAC, resistive
Max. Total Output Current
5 A continuous
Max. Output Voltage
275 VAC , 30 VDC
Max. Switched Power
1250 VA, 150 W
Contact Isolation to XL6 ground
1000 VAC
Max. Voltage Drop at Rated
Current
0.5 V
Expected Life
(See Derating section for chart.)
No load: 5,000,000
Rated load: 100,000
Max. Switching Rate
300 CPM at no load / 20 CPM at rated load
Type
Mechanical Contact
Response Time
One update per ladder scan plus 10 ms
Analog Inputs, Medium Resolution
Number of Channels
4
Input Ranges
0 - 10 VDC / 0 – 20 mA / 4 – 20 mA
Safe input voltage range
-0.5 V to +12 V
Input Impedance
(Clamped @ -0.5 V to 12 VDC)
Current Mode:
100
Voltage Mode:
500 k
Nominal Resolution
10 Bits
% AI full scale
32,000 counts
Max. Over-Current
35 mA
Conversion Speed
All channels converted once per ladder
scan
Max. Error at 25
C
(excluding zero)
*can be made tighter (~0.25%) by
adjusting the digital filter = 3.
4-20 mA 1.00%
0-20 mA 1.00%
0-10 VDC 1.50%*
Additional error for temperatures
other than 25
C
TBD
Filtering
160 Hz hash (noise) filter
1-128 scan digital running average filter
General Specifications
Required Power (Steady State)
500 mA @ 24 VDC
Required Power (Inrush)
30 A for 1 ms @ 24 VDC
Primary Power Range
10 ~ 30 VDC
Relative Humidity
5 to 95% Non-condensing
Clock Accuracy
+/- 1.53 Minutes/Month at 25
C
Operating Temperature
-10
C to +60
C
Terminal Type
Screw Type, 5 mm Removable
Display Size / Type
5.7” / QVGA TFT
Display Screen Dimension
320 x 240
Display Life
Min 4000 hours (50 % brightness, 25 °C
Colors
32768
Serial Ports
2 serial ports – RS232 & RS485
USB
USB networking port for communications
with PC
2
Panel Cut-Out and Installation
Refer to the XL6 User Manual for panel box information and a handy checklist of
requirements.
Notes:
The tolerance to meet NEMA standards is
0.005” (0.1 mm).
Max. panel thickness: 5 mm.
Caution: Do not force the ocs into the panel cutout. An incorrectly sized panel cutout
can damage the touch screen.
3
Ports / Connectors / Cables
To Remove Back Cover unscrew 4 screws located on the back of the unit.
I/O Jumpers: (Not Shown):
I/O Jumpers (
JP
) are located internally. To access,
remove back cover of unit.
Wiring Connectors (J1 / J2)
and
I/O Jumpers (JP1 / JP2
are described in the
Wiring
and Jumpers
section of this document.
Memory Slot:
Uses
Removable Memory
for data logging, screen captures, program
loading and recipes.
Novus
Part No.: HE-MC1
Serial Communications: MJ1
: (RS-232 / RS-485) Use for
Cscape programming and
Application-Defined Communications.
MJ2:
(RS-232 / RS-485) Use for Application-
Defined Communications.
Ethernet: Used for Cscape Programming and application-Defined communications.
Power Connector and Can Connector