Power Controller – PCW / PCWE 

INSTRUCTION MANUAL – V1.0x F 

PRESENTATION 

The NOVUS power controller is a type of electronic equipment with 

functions to control and limit the electric power delivered to a generic 

electric load. These functions are executed with modern techniques, 

in order to provide significant gains for the process, all with durability, 

precision, efficiency and economy. 
It also executes the important function of protecting the connected 

load and the system as a whole, since it has ultra-fast fuses included 

in all its versions. 
There are two types of controller models: PCW and PCWE. The 

PCWE model has a feature that limits the electric power delivered to 

the load (Load Limit), the only difference between the two models. 

SPECIFICATIONS 

General Specifications 

Load Voltage (MAIN POWER): .......................180~440 Vac; 50/60 Hz 
Command Signal (INPUT): ...................................... 0-20 mA, 4-20 mA 
 ................................................................ 0-5 V, 1-5 V, 0-10 V e 2-10 V 
 .............................................................................. 10 k (Potentiometer) 
Type of control: ................................................. PWM and phase angle 
Control feed (AUX. POWER):.................................... 220 Vac (PCWE) 
 .............................................................................. 220/380 Vac (PCW) 
Alarm .......................................................... relay SPST; 3 A / 250 Vac 
Dielectric rigidity between parts ................................................  2500 V 
Operating Temperature: ...................................................  -10 to 60 ºC 
Plastic Cabinet ....................................................... ABS+PC / UL-94V0 

Monophase Models 

MODEL 

PCW-1P-100 

PCWE-1P-200 

Load Current 

100 A 

200 A 

Protection 

Fuse 100 A 

Fuse 200 A 

Surge Current (10 ms) 

1600 A 

5400 A 

Dimensions 

Figure 1 

Figure 4 

Fan 

12 Vdc 

Three Phase Models – Two controlled phases 

MODEL 

PCW-2P-60  PCW-2P-100  PCW-2P-150  PCWE-2P-200 

Load Current 

60 A 

100 A 

150 A 

200 A 

Protections 

Fuse 60 A 

Fuse 100 A  Fuse 150 A 

Fuse 200 A 

Surge Current 

(10 ms) 

1200 A 

1600 A 

2250 A 

5400 A 

Dimensions 

Figure 1 

Figure 2 

Figure 3 

Figure 5 

Fan 

12 Vdc 

220 Vac 

Three Phase Models – Three controlled phases 

MODEL 

PCW-3P-60  PCWE-3P-100  PCWE-3P-160  PCWE-3P-200 

Load Current 

60 A 

100 A 

160 A 

200 A 

Protection  Fuse 60 A 

Fuse 100 A 

Fuse 160 A 

Fuse 200 A 

Surge Current 

(10 ms) 

1200 A 

1600 A 

2250 A 

5400 A 

Dimensions 

Figure 2 

Figure 5 

Fan 

12 Vdc 

220 Vac 

INSTALLATION 

The controller is made to be attached vertically, for instance, in the 

rear of a control panel. It needs an open area for an appropriate air 

circulation and the environment should meet the typical requirements 

for electronic equipment. 

DIMENSIONS 

 

Figure 1 

 

 

Figure 2 

 

Содержание PCW-3P-60

Страница 1: ...CWE 220 380 Vac PCW Alarm relay SPST 3 A 250 Vac Dielectric rigidity between parts 2500 V Operating Temperature 10 to 60 ºC Plastic Cabinet ABS PC UL 94V0 Monophase Models MODEL PCW 1P 100 PCWE 1P 200 Load Current 100 A 200 A Protection Fuse 100 A Fuse 200 A Surge Current 10 ms 1600 A 5400 A Dimensions Figure 1 Figure 4 Fan 12 Vdc Three Phase Models Two controlled phases MODEL PCW 2P 60 PCW 2P 100...

Страница 2: ...l signal should be applied in terminals 1 2 and 3 of the controller s connector bar MANUAL CONTROL Feature that allows the user to manually establish the percentage value of the power delivered to the load The options for a manual control are Via keypad adjustment Available when following a recommendation such as Manual percentage value of the power delivered to the load See Mode of Operation late...

Страница 3: ... Fuse rupture The alarm activates a relay that can be configured to operate in NA or NF mode The Aln 0 configuration parameter defines the relay s operation mode SOFT START FUNCTION STR 0 Allows for a slow and gradual power increase delivered to the load The increase speed of the delivered power is determined by a time interval that can be adjusted by the user in seconds During this time interval ...

Страница 4: ...load i Recommends load current value n Recommends manual percentage value of the power delivered to the load 1nt 0 Selection of the Control Signal 1nt 0 4 20 mA 1nt 1 0 20 mA 1nt 2 1 5 V 1nt 3 2 10 V 1nt 4 0 5 V 1nt 5 0 10 V 1nt 6 10 k Power meter on 0 Type of control on 0 Square Wave control type on 1 Phase Angle Control Str 0 Soft Start Kick Start Function Str 0 Adopts the Soft start function St...

Отзывы: