NP620 Pressure Transmitter 

 

NOVUS AUTOMATION 

2/3 

ELECTRICAL CONNECTIONS 

 

Fig. 2 – Electrical Connections 

Recommendations for installation 

 

Sensor signals conductors must go through the plant system 

separate from power leads (loop).  If  possible,  in grounded 

conduits. 

 

The instruments must be powered from the instrumentation power 

supply circuit. 

 

It is mandatory  the use of RC FILTERS (electrical noise 

suppressors) in contactor coils, solenoids, etc. 

 

To improve the stability, immunity and safety of the measurement, 

it is recommended to use the system grounding. 

CONFIGURATION 

When the transmitter is used with the factory setting, no further 

action is required and the transmitter is ready to be installed. 
When a new configuration is required, you should use the 

Transmitter Configuration Kit. This kit includes the TxConfig-II 

software, distributed free on the Novus website, and the TxConfig-

USB-DIN43650 interface, which can be purchased in our distribution 

and reseller network. 
To install the TxConfig-II  software, run the setup file 

TxConfigIISetup.exe

 and follow the instructions of the installer. 

The  TxConfig  interface must be connected to the transmitter 

according to Fig. 3. The interface itself provides the electrical power 

necessary for transmitter operation during configuration. 

 

Fig. 3 – Connection of the TxConfig-USB 

SOFTWARE CONFIGURATION 

 

Fig. 4 – TxConfig II software main screen 

When you run the TxConfig-II  software, it will recognize 

automatically the transmitter and will  display the following 

information: 
1.

 

General Information
This field shows information that identifying the transmitter. This 

information should be sent to the manufacturer in an eventual 

request for technical assistance. 

2.

 

Unit
Setting the pressure unit assumed for the measuring range 

setting fields. 

3.

 

Measuring Range
Setting the measurement range assumed by the transmitter. 
Lower Limit: Target pressure value for 4 mA current. 
Upper Limit
: Target pressure value for 20 mA current. 
Minimum Range 
Do not set a lower band (span) that the Minimum Range 

indicated below in this same field. 

4.

 

Sensor Failure:  Sets the current output behaviour when the 

transmitter experiences a fault: 
Minimum: Output current goes to < 4 mA. 
Maximum: Output current goes to > 20 mA. 

5.

 

Zero Correction:  It corrects small deviations presented in the 

transmitter output, when there is no applied pressure. 

6.

 

Send Configuration:  It applies the new setup. Once sent, the 

setup will be immediately adopted by the transmitter. 

7.

 

Read Configuration: Reads the current setup in the transmitter 

connected. The screen now presents the current setup that may 

be changed by the user. 

 

 