NOVUS AUTOMATION 

1/4

 

 

 

 

DigiRail-2R

 

Digital Outputs Module 

COMMUNICATION MANUAL 

INTRODUCTION 

The 

DigiRail-2R

  is provided with RS485 two wire serial communications, operating as slave in the Modbus RTU 

protocol. The entire equipment configuration, as well as activating of  the output relays, is performed through serial 
communication. 

This manual provides the information necessary for performing the output activation without using the software 

DigiConfig

. In order to assure the correct configuration of DigiRail, always use the DigiConfig software. After being 

configured, the data of its inputs and/or outputs can be accessed by any other software having Modbus RTU 
communication capacity. 

For further details regarding the implementation of a network of devices please refer to the document 

Basic Concepts of 

RS485 and RS422

, available the website 

www.novusautomation.com

, for download.

 

MODBUS ADDRESS ASSIGNMENT SYSTEMATICS 

The 

DigiRail

  equipment  does  not have keys for determination of  the Modbus communication address. This must be 

determined by using the communication in the Modbus protocol itself.  This will require that the address of the device to 
be configured is known, this being possible by two different means: 

  If the equipment is a new one, it will show the configuration as set by the factory: Address=247, Baud rate=1200, 

Parity Even, 1 Stop Bit. 

  If the equipment has already been used and you do not know its address and/or other communication parameters, 

press the RCom button on your front panel. It will enter the diagnostics mode during 1 minute, assuming the following 
communication parameters: Address=246, Baud rate=1200, parity even, 1 stop bit. 

The 

DigiConfig

 software configurator is provided with a function of searching the network for temporary devices, exactly 

the devices in the previous conditions. Once having been localized, the address and the other communication 
parameters of the device can be changed according to the necessity of the application. 

The communication parameters in the two previous conditions are not very common in Modbus networks, and they may 
probably cause no conflicts with other equipment of the network. Obviously only one 

DigiRail

 in the network can be in 

each of the previous conditions so that the communication with the configurator 

DigiConfig

  is possible. If several new 

DigiRail

  are to be included in a network, they must be inserted individually. Only after changing the communication 

parameters for the definitive values, the next new 

DigiRail

  can be inserted. In an already existing network, only one 

DigiRail

 at a time can be set in diagnostics mode in order to be detected by the 

DigiConfig

It is important to emphasize that the 

DigiConfig

 software acts as a master in the Modbus network. Its utilization requires 

that the original master of the network (SCADA software, for instance) be disconnected during its use. For further details 
please refer to the on-line Help of the 

DigiConfig

MODBUS COMMANDS 

The Modbus RTU commands (functions) listed below are implemented. For further information with respect to each one 
of these commands and the Modbus protocol in general, please access the website: 

http://www.modbus.org

 

 

READ COILS – 01H 

This command can be used for reading the current state of one or two digital outputs, according to the table below. 

Address 

Description 

State of digital output 1 (0=off; 1=on) 

State of digital output 2 (0=off; 1=on) 

The specified 

addresses

 correspond to the low level physical addresses, where zero (0) corresponds to the address of 

PLC 00001. 

The response of this command will inform the state of each requested input with one bit only. Thus the state of the first 
requested input comes at bit 0 (less significant bit), the state of the second at bit 1 and so on.

 

Содержание DigiRail-2R

Страница 1: ... exactly the devices in the previous conditions Once having been localized the address and the other communication parameters of the device can be changed according to the necessity of the application The communication parameters in the two previous conditions are not very common in Modbus networks and they may probably cause no conflicts with other equipment of the network Obviously only one Digi...

Страница 2: ... R W indicates if the parameter is for writing and reading R W or for reading R only Address Description SuperView Mnemonic Minimum Maximum R W 0 Series number word high 0 65535 R 1 Series number word low 0 65535 R 2 Baud rate 0 7 R W 3 Modbus Address 1 247 R W 4 Parity 0 2 R W 5 Firmware version 0 999 R 6 Diagnostic state timer in tenths of seconds 0 600 R W 7 State of the digital outputs where b...

Страница 3: ...al output 2 characters 5 and 6 0 65535 R W 47 Tag of digital output 2 characters 7 and 8 0 65535 R W 48 Tag of digital output 2 characters 9 and 10 0 65535 R W 49 61 Reserved 0 0 R 62 DigiRail model 0 4 R 63 84 Reserved 0 0 R DETAILS OF SOME REGISTERS REGISTER 2 BAUD RATE Code of speed used in Modbus communication Code Baud rate 0 1 200 1 2 400 2 4 800 3 9 600 4 19 200 5 38 400 6 57 600 7 115 200 ...

Страница 4: ... received REGISTERS 20 TO 23 TIME FOR DEACTIVATING THE RELAY WHEN ACTIVATION TEMPORIZED Time in hundredths of seconds which remains for the relay be deactivated after an activation command REGISTERS 34 TO 48 TAGS DigiRail features some identification tags where characters can be written in order to help identifying the device and its outputs Identification tag of the device 10 characters Identific...

Отзывы: