UBZ-304

                                                                                                   

NOVATEK-ELECTRO

 

Reset of energy meters (total, active and reactive) is performed when setting the parameter "Energy RESET" to 

"On"  (setting  to  "1"  when  using  RS-232/RS-485  interface).  After  reset  of  energy  meters,  the  parameter  "Energy 
RESET" will automatically switch to "Off" ("0" 

 when reading the parameter via RS-232/RS-485 interface). 

 

5.3 UBZ OPERATION 

In describing the operation of UBZ it is assumed that this protection is enabled and all the required sensors are 

connected.   

5.3.1 UBZ operation before load relay on 
5.3.1.1

 UBZ operation after energizing (first start-up) 

After  energizing  the  indicator  displays  the  device  name,  the  version  number  of  software,  the  name  of  the 

manufacturer and the operation performed (Fig.5.11).  

 

 

 

N o t e

 

 the software version number may vary. 

 

Figure 5.11

 

 UBZ indicator view after energizing 

 

After  1-2  seconds  the  indicator  will  display  the  values  of  the  measured  parameters.  What  parameters  will  be 

displayed on the indicator it depends on the value of the parameter 

“Indicat <Start”:

 

  line voltages at 

“Ind

i

cat <Start”=”LineU”;

 

  the  motor  operating  time,  the  insulation  resistance  of  the  motor  and  mains  frequency  at 

“Indicat  <Start”= 

“InsFr”.

 

Before the load relay enabling UBZ checks the following: 

  the level of stator winding insulation relative to the motor housing (when insulation resistance is less than  

500 ± 20 kOhm at “Insulation  Mr” =

 

”5” (1000 ±

 50 kOhm at 

“Insulation  Mr” =

 

”10”) 

the load is not enabled); 

  the quality of the mains voltage: full phase, symmetry, the current line voltage value;  

  correct phase sequence, the lack of their 

“coincidence”.

 

If any of disabling factors, the load relay is not activated, and the display of mnemonics shows the corresponding 

message about the fault (Table 5.13) and the led 

FAULT

 lights up. 

In  the  absence  of  disabling  factors,  enabling  the  load  relay  is  determined  by  the  value  of  parameter 

“Start>Power” (

UBZ operation after energizing): 

1)  when 

“Start>Power” = “StOff”

, the load relay will not be enabled.

  

To enable the load relay in this case, you should simultaneously press UP and DOWN buttons. 

2)  when 

“Start>Power” = “St>AR” 

the load relay will be enabled after ARS time. 

3)  when 

“Start>Power” = “St>2s” 

the load relay will be enabled within 2 seconds after energizing. 

Simultaneously with the load relay enabling the green led "

Power relay

" lights up.  

After you activate the relay and up to the moment of the motor starting (motor start is determined by the excess 

of  the  load  current  of  120%  level  of  rated  current),  control  and  taking  action  on  voltage  quality  is  maintained.  If 
within no-current pause the disabling factors are appeared, the load relay is deactivated. 

UBZ  operation  when  enabled  remote  control  of  the  motor  via  RS-232/RS-

485  interface  (parameter  “MotorOp 

RS-

2/5”) is co

nsidered in it. 5.4.9. 

5.3.1.2 

UBZ operation after shutdown owing to the fault 

UBZ operation in this case is similar to the work when first starting, but enabling the load relay does not depend 

on the value of the parameter 

“Start>Power”.

 

If after the faul

t ARS is disabled (“AR”="Off"), then with disabled motor start on the front panel (it is determined 

by the value of the parameter "MotorOp UBZ") the automatic enabling the motor is impossible up to UBZ turning off. 

The action of the parameter “AR” value is

 applied to all types of faults except voltage faults. To disable ARS in case 

of voltage faults you should use the parameters 

“Umax protec”, “Umin protec”, “Uimbal protec”. 

 

 

 

5.3.2  UBZ operation  after  load  relay  enabling  and  motor  is  on

  (currents  occurrence more  than  10%  of  the 

motor rated current) 

UBZ provides monitoring for voltage and currents. The load relay is disabled when any protection tripping from 

Table 5.13 with the exception of: 

  voltage protection; 

  overcurrent protection with 

“Imax<>T” =”Ind” (

in this case, the warning is there, but the load relay is not disabled). 

The indicator can display phase currents of motor or group of three (two) parameters selected by the user (Table 3.5).    
The group of parameters selected by the user can be displayed constantly 

(“Indicat mode” =” Conti”) 

or for 15 s, and then 

indication of motor currents returns 

(“I

n

dicat mode “ = ”>15s”).

 

 

 

5.3.3 Functional relay operation 

The functions performed by the functional relay are determined by the parameter 

“Relay F mode”.

 

Содержание UBZ-304

Страница 1: ...TRO LTD thanks you for purchasing our products You will be able to use properly the product after carefully studying the Operating Manual Keep the Operating Manual throughout the service life of the p...

Страница 2: ...onnection 21 5 1 2 Selection of Current Transformers CT 21 5 1 3 General 21 5 1 4 Unit Installation 22 5 1 5 UBZ 304 connect 23 5 2 UBZ Control 24 5 2 1 Modes of UBZ control and status 24 5 2 2 Measur...

Страница 3: ...dure 37 7 TRANSPORTATION AND STORAGE 38 8 SERVICE LIFE SHELF LIFE AND MANUFACTURER WARRANTY 38 9 ACCEPTANCE CERTIFICATE 38 10 CLAIMS DATA Appendix 39 CURRENT PROTECTION WITH DEPENDENT TIME DELAY Appen...

Страница 4: ...OUNTING WORKS AND MAINTENANCE WITHOUT DISCONNECTING THE PRODUCT FROM THE MAINS TO OPEN AND REPAIR THE PRODUCT INDEPENDENTLY TO OPERATE THE PRODUCT WITH MECHANICAL DAMAGES OF THE CASE IT IS NOT ALLOWED...

Страница 5: ...gn version UBZ provides continuous monitoring of mains voltage parameters current values of the phase line currents of three phase electrical equipment for 415V 50Hz and checking the resistance values...

Страница 6: ...ltages and currents calibration factors is added Version 9 control algorithms by the engine on analog inputs are added 1 3 CONTROLS AND OVERALL DIMENSIONS Overall dimensions of UBZ are given in Fig 1...

Страница 7: ...n the parameters setting mode 11 Button DOWN is scrolling of displayed parameters in the parameter view mode and scrolling of the menu in the parameters setting mode 12 Button RES MEM SEL is the param...

Страница 8: ...oad VA not more 5 0 Weight not more kg 0 34 Overall dimensions Fig 1 1 H B L mm 110 96 88 3 Position in space free Housing material self extinguishing plastic Table 3 3 Characteristics of built in rel...

Страница 9: ...ll drop lower than 1 2 In Maximum phase current achieved during this period is the maximum starting current 3 I t 3 I t 0 1 600 2 10 Start i Overload i Start time 42 43 44 Voltage Effective values of...

Страница 10: ...d with MW MVA MVAr 5 If the temperature value exceeds specified limits then the indicator displays the alarm code in accordance with table 5 13 If the temperature sensor is disabled by software then t...

Страница 11: ...sable 2 On AR protection is on ARS is enabled 161 Negative sequence current protection Actuation setting I2 rev tresh 5 20 10 It is set as percentage of rated current 162 Tripping delay s I2 rev delay...

Страница 12: ...otec 0 2 2 0 Off protection is off 1 OnnAR protection is on ARS after tripping is disable 2 On AR protection is on ARS is enabled 179 Maximum line voltage V Umax tresh 330 450 415 180 Tripping delay f...

Страница 13: ...t 0 2 0 0 Off protection is off 1 OnnAR protection is on ARS after tripping is disable 2 On AR protection is on ARS is enabled 194 Motor control and ARS ARS time after protection operation at minimum...

Страница 14: ...abled 1 Pt100 of Pt100 type 2 Ni100 of Ni100 type 3 Ni120 of Ni120 type 204 Motor trip temperature Temp S2 Off M 0 220 180 205 Warning temperature Temp S2 Alarm 0 220 170 206 Temperature correction of...

Страница 15: ...tional relay is enabled Timer value s Relay F time 0 300 30 See it 2 it 3 of the parameter Relay F mode address 214 215 Star delta mode Switching time s Delay RP RF 0 1 2 0 4 The time between the load...

Страница 16: ...Version 9 The parameter value depends on software version 230 Indicator illumination1 Indicator L 0 2 1 0 Off illumination is off 1 On15s illumination is on for 15 s after pressing any buttons 2 On i...

Страница 17: ...current factor to negative sequence voltage factor for thermal overload undercurrent protection in phases delayed starting rotor blocking overheating of windings for minimum line voltage for maximum...

Страница 18: ...are assumed ARS after tripping will not occur regardless of the value of I2 rev protec parameter The coefficient of negative voltage current sequence is characteristic of unbalance of three phase vol...

Страница 19: ...n you should enter the response time in case of double overload T2 the parameter of Thermal delay Current time characteristic with different values of T2 is given in Fig 3 4 For the standard recommend...

Страница 20: ...751 and DIN 43760 3 4 9 Voltage protection In UBZ voltage protection before enabling the load it is necessary to check the corresponding set points and depending on their value the load relay enabling...

Страница 21: ...upplier or manufacturer Carefully study the Operating Manual pay special attention to the connection diagram to power the product If you have any questions regarding the installation of the product pl...

Страница 22: ...5 91 5 mm 0 5mm tolerance the distance between UBZ panels top bottom and side and the relevant surfaces of the panel should be at least 10 mm if it is assumed to have operational use of communication...

Страница 23: ...insulation 23 to one of output contacts of MS If the motor housing is not grounded or network with isolated neutral is used or neutral wire is not connected to UBZ terminal it is necessary to connect...

Страница 24: ...0 are closed when relay is off the contacts 16 17 and 20 21 are closed 5 2 UBZ CONTROL 5 2 1 Modes of UBZ control and status UBZ has five control modes Keyboard blocking MNS User level Advanced user l...

Страница 25: ...g the keyboard no button is pressed within 15 s and setting of blocking has not been disabled by the user the keyboard is blocked again 5 2 4 Mode of Minimum number of settings MNS Mode of MNS is desi...

Страница 26: ...play instead of the inscription OFF MMSP the inscription MMSP should remain The value of the parameter in the user mode can be changed if the fourth line of the indicator has only the inscription MMSP...

Страница 27: ...s are restored advanced user password 123 This method does not recover the following settings the unit operating time Time UBZ operating time of the motor Time motor clock correction Correct Time Afte...

Страница 28: ...simultaneously press UP and DOWN buttons 2 when Start Power St AR the load relay will be enabled after ARS time 3 when Start Power St 2s the load relay will be enabled within 2 seconds after energizin...

Страница 29: ...er 0 1 2 3 4 5 6 7 ASCII code 30 Hex 31 Hex 32 Hex 33 Hex 34 Hex 35 Hex 36 Hex 37 Hex Character 8 9 A B C D E F ASCII code 38 Hex 39 Hex 41 Hex 42 Hex 43 Hex 44 Hex 45 Hex 46 Hex In RTU mode 8 bit dat...

Страница 30: ...t changed but the format of the transmission data and control of data is based on the Table 5 4 Table 5 4 Data packet in ASCII mode Name Description STX Start character 3A Hex ADR1 UBZ communication a...

Страница 31: ...operation day Time UBZ 217 Motor operating time day Time motor 218 Access code of user Users code 219 Access code of advanced user Password 220 Restoration of factory settings Default Factor 221 The u...

Страница 32: ...mitting device In case of mismatching the generated and received Cyclic Redundant Check the error message will be generated The field of Cyclic Redundant Check has two bytes CRC in the message is tran...

Страница 33: ...l relay operation 00 alarm relay 01 time relay 10 star delta Bit 6 0 MNS mode is disabled 1 MNS mode is enabled Bit 7 0 clock battery is normal 1 the clock battery should be replaced Bit 8 0 normal op...

Страница 34: ...and The master should repeat the message later when the slave is freed 07h NEGATIVE ACKNOWLEDGE UBZ cannot perform the program function received in request 5 4 9 Remote control of the motor using RS 2...

Страница 35: ...the command UBZ RESTART the delay of at least 100 ms should be provided ATTENTION WHEN THE MOTOR IS ENABLED THE FULFILLMENT OF COMMAND UBZ RESTART RESTART IS DISABLED 5 4 12 UBZ factory settings using...

Страница 36: ...alance 314 14 901 14 Minimum insulation resistance of motor winding Insul Res Insulation resistance 315 15 901 15 Mains minimum frequency F min Frequency 316 16 902 0 Mains maximum frequency F max Fre...

Страница 37: ...fault code Stop nAR The restart of the motor is possible only after de energizing and re energizing of UBZ unit St motor start and shutdown is permitted the load relay is disabled with issuance of co...

Страница 38: ...he unit operation is 5 years from the date of sale During the warranty period the Manufacturer is responsible for free repair of the unit if the Consumer has complied with the requirements of this Ope...

Страница 39: ...39 NOVATEK ELECTRO UBZ 304 Appendix CURRENT PROTECTION WITH DEPENDENT TIME DELAY mandatory...

Страница 40: ...40 UBZ 304 NOVATEK ELECTRO...

Страница 41: ...g over and the motor insulation control When UBZ is in the star delta mode it is allowed performing the motor control in the following ways the motor disabling enabling using the external automatic st...

Отзывы: