Technical Specifications

 

Description

Value

 

Rated power supply voltage, V

 12 - 24

The error of measuring DC voltage in the range of 0-10 V, min

1%

The error of measuring DC in the range of 0-20 mA, min

1%

Temperature measurement range (NTC 10 KB), °C

-25…+125

Temperature measurement error (NTC 10 KB) from -25 to +70 °C

±1

Temperature measurement error (NTC 10 KB) from +70 to +125 °C

±2

Temperature measurement range (PTC 1000), °C

-50…+120

Temperature measurement error (PTC 1000), °C

±1

 

Temperature measurement range (PT 1000), °C

-50…+250

 Temperature measurement error (PT 1000), °C

±

1

 Max. pulses frequency in “Pulse Counter/Logic Input” mode, Hz

200

 Max. voltage given on an «IO1» input, V

12

 Max. voltage given on an «IO2» input, V

5

 

Readiness time, max, s

0.4

 

Max. switched current with active load, A

8

 

Quantity and type of relay contact (switching contact)

1

 

Communication Interface

RS (

EIA

/TIA)

-485

 

ModBus data exchange protocol

RTU / ASCII

 Rated operating condition

continuous

 

Climatic design version

 

NC

 3.1

 

Protection rating of the device

IP

2

0

 

Permissible contamination level

                             

II

 

Maximal power consumption, W, not more

1

 

Electric shock protection class

II

 

Wire cross-section for connection, mm²

0.5 - 1.0

 

Tightening torque of screws, N*m

0.4

 

Weight, max., kg

0.07

 

Overall dimensions, mm

90х

18x

64

 

The device meets the requirements of the following

:

 EN 60947-1;  

EN

 60947-6-2;

  EN 55011

;  

IEC 

61000-4-2

 

Installation is on standard 35 mm DIN-rail

Position in space - arbitrary

 Housing material is self-extinguishing plastic 

Harmful substances in amounts exceeding maximum permissible concentrations are not available

Table

 2 

 – 

Settings for OB-215

Description

Range

Factory 

setting

Type

W/R

Ad

d

res

s

(DEC)

Digital signals measurement:

0 – 

pulse counter;

1 – 

logic input/pulse relay.

Analog signals measurement:

2 – 

voltage measurement;

3 – 

current measurement.

Temperature measurement:

4 – NTC (10KB) 

sensor

;

5 – PTC1000

 sensor

;

6 – PT 1000

 sensor 

.

Interface transformation mode:

7 – RS-485 – UART (TTL);
8 – 

digital sensor 

(1-Wire, I2C)*.

0…

8

1

UINT

W/R

100

Connected digital sensor

0 – DS18B20 (1-Wire);
1 – DHT11 (1-Wire);
2 – DHT21/AM2301 (1-Wire);
3 – DHT22 (1-Wire);
4 – BMP180 (I2C)

.

0…4

0

UINT

W/R

1

01

Temperature correction

-99…99

0

INT

W/R

102

Relay control:

0 – control is disabled;
1  –  relay  contacts  are  opened  at  a  value  above  the  upper 

threshold, they are closed at a value below

 

the lower threshold;

2  –  relay  contacts  are  closed  at  a  value  above  the  upper 

threshold, they are opened at a value below the lower

 

threshold.

0…2

0

UINT

W/R

103

Upper threshold

-50

0

...250

0

250

UINT

W/R

104

Lower threshold

-50

0

...250

0

0

0

 

UINT

W/R

105

Pulse counter mode:

0 – counter on the leading edge of the pulse;
1 – counter on the trailing edge of the pulse;
2 – counter on both edges of the pulse.

0…2

0

UINT

W/R

106

Switch debouncing delay

**

1…250

100

UINT

W/R

107

Number of pulses per counting unit 

***

1…65534

8000

UINT

W/R

108

RS-485

:

        

0 – ModBus RTU;

                     

1 – ModBus ASCII.

0…1

0

UINT

W/R

1

0

9

ModBus

 

UID

1…127

1

UINT

W/R

110

Rate of exchange

:

       

0 – 1200; 1 – 2400; 2 – 4800; 3 – 9600; 4 – 14400; 5 – 19200.

0…5

3

UINT

W/R

111

Parity check and stop bits:

0 – 

no, 2 stop bits;

 

1 – 

even, 1 stop bit;

 

2 – 

odd, 1 stop bit.

0…2

0

UINT

W/R

112

Rate of exchange 

UART(TTL)->RS-485:

    

0 – 1200; 1 – 2400; 2 – 4800; 3 – 9600; 4 – 14400; 5 – 19200.

0…5

3

UINT

W/R

113

Stop bits for 

UART(TTL)->RS-485:

 

 0 – 1 

stop bit

;  1 – 1

.

stop bits

;  2 – 2 

stop bits

.

0…2

0

UINT W/R

114

Parity check for 

UART(TTL)->RS-485

:   

 0 – 

None

; 1 – 

Even

;  2 – 

Odd

.

0…2

0

UINT

W/R

115

ModBus password protection 

****

:     

 0 – 

disabled

; 1 – 

enabled

.

0…1

0

UINT

W/R

116

ModBus password value

A-Z,a-z,

0-9

admin

STRING W/R 1

17-124

Note:

The sensor to be connected is selected at address 101.

 ** 

The delay used in switch debouncing in the Logic Input / Pulse Relay mode; the dimension is in millisecond.

*** 

Only used if the pulses counter is on. The column "Value" indicates the number of pulses at the input, after 

registration of which, the counter is incremented by one. Recording to memory is performed with a periodicity of 
1 minute.

***

If ModBus Password Protection is enabled (address 116, value "1"), then to access the recording functions, 

you must write the correct password value to addresses 51-59.

Table 1 – 

Basic Technical Specifications

Table 

3

 – 

Output Contact Specifications

Operation 

mode

Max. current at 

 

U~250 V [A]

Max. switching power 

at 

 U~250 V [VA]

Max. continuous permissible 

AC / DC voltage

 [V]

Max. current at 

 

U

con

 =

30 V DC [A]

cos

 φ=1

2000 

250/30

 

0.6

Digital I/O module OB-215 hereinafter referred to as the "device" can be used as 

the following:

− remote DC voltage meter (0 – 10 V);
− remote DC meter (0 – 20 mA);
− remote temperature meter with the ability to connect sensors NTC (10 KB), 
PTC 1000, PT 1000 or digital temperature sensor D18B20;
− temperature regulator for cooling and heating plants;
− pulse counter with saving the result in memory;
− pulse relay with switching current up to 8 A;
− interface converter for RS-485 – UART (TTL).
OB-215 provides:
− equipment control using relay output with switching capacity up to 1.84 kVA;
− tracking the state (closed/open) of the contact at the dry contact input.
RS-485 interface provides control of the connected devices and reading of the 

sensors readings via the ModBus protocol.

Parameter setting is set by the user from the Control Panel using the ModBus 

RTU/ASCII protocol or any other program that allows working with the ModBus RTU / 
ASCII protocol.  

The  status  of  the  relay  output,  the  presence  of  the  power  supply  and  the  data 

exchange are displayed using indicators located on the front panel (Fig. 1, it. 1, 2, 3).

The overall dimensions and layout of the device are shown in Fig. 1.

Note:

Temperature sensors are included in the delivery scope as agreed upon. 

 

1  – 

indicator  of  data  exchange  via  RS-485  interface  (it  is  on  when  data  is  being 

exchanged);

2 – indicator of the status of the relay output (it is on with closed relay contacts);
3 – indicator       is on when there is supply voltage;
4 – terminals for connecting RS-485 communication;
5 – device power supply terminals;
6 – terminal for reloading (resetting) the device;
7 – terminals for connecting sensors;
8 – output terminals of relay contacts (8 A).

Figure

 1

5

6

7

8

1

2

3

+

-

+A              -B

NO 

  

  C      NC 

  

IO1 

   

IO2

4

R

18

Operation Conditions

The device is intended for operation in the following conditions:
− Ambient temperature: from minus 35 to +45 

°С

;

− Atmospheric pressure: from 84 to 106.7 kPa;
− Relative humidity (at temperature of +25 

°С): 30 … 80

 %.

The device 

is not intended

 for operation in the following conditions:

− Significant vibration and shocks;
− High humidity;
− Aggressive environment with content in the air of acids, alkalis, etc., as well as 

severe contaminations (grease, oil, dust, etc.).

Quality Management System of the device designing and production complies with the requirements of 

ISO 9001:2015, IDT

Dear Customer,

Novatek-Electro

 Ltd. Company thanks you for purchasing our products. 

You will be able to use properly the device after carefully studying the Operating Manual.

Keep the Operating Manual throughout the service life of the device.

Designation

Operating Manual

 

DIGITAL I/O MODULE

OB

-215

1