Overall Limitations

NOTI•FIRE•NET™  PN 50257:E  7/5/01

9

Table 3 Twisted Pair Cable Lengths per Cable Segment (2 of 3)

Table 4 Twisted Pair Cable Lengths per Cable Segment (3 of 3)

Fiber Optic Circuits

The attenuation of cabling between two nodes/repeaters (fiber optic circuits are point-to-point) 
must not exceed a 8 dB limit.   If the distance required for a circuit segment is greater than 
permitted, a Repeater module (RPT-F) must be inserted into the circuit at intervals less than, or 
equal to, the 8 dB attenuation length restriction.

Attenuation Determination:

Find the rated dB loss per foot within the cable manufacturer's specifications.  Determine the 
total attenuation between the two nodes/repeaters due to the cable.

Loss = (loss/ft.) x (length in feet) 

Establish the dB loss for each connector and splice.  Sum all the losses. 

SIGNAL 82802-06-14, 18 AWG, 1 
Pair Unshielded

Mid-Cap., FPLP, PVC, NEC 
Article 760, UL 1424

High:

1-1200

1-100

Low:

1000-2800

N/A

SIGNAL 98181-06-04, 18 AWG, 1 
Pair Unshielded

Mid-Cap., FPL, PVC, NEC 
Article 760, UL 1424

High:

1-1200

1-100

Low:

1000-2800

N/A

SIGNAL 962034619, 24 AWG, 
3 Pair Unshielded

CLZ/CMR

High:

1-1400

1-100

Low:

1200-2000

N/A

SIGNAL 962044619, 24 AWG, 
4 Pair Unshielded

CLZ/CMR

High:

1-1400

1-100

Low:

1200-2000

N/A

SIGNAL 962064619, 24 AWG, 
6 Pair Unshielded

CLZ/CMR

High:

1-1400

1-100

Low:

1200-2000

N/A

SIGNAL 962624619, 24 AWG, 
4 Pair Unshielded

CMR/MRP

High:

1-1400

1-100

Low:

1200-2000

N/A

SIGNAL9669544623, 24 AWG, 4 
Pair Unshielded

CMP/MPP

High:

1-1400

1-100

Low:

1200-2000

N/A

WEST PENN WIRE D999, 
12 AWG, 1 Pair Shielded

FPL, PVC, NEC, Article 760, UL 
1424 and 1581

High:

1-800

1-100

Low:

800-1400

N/A

Cable Manufacturer, Part 
Number, and Number of Gauges/
Conductors

Manufacturer's Specifications

Data Threshold: 
All Nodes And/Or 
Repeaters On A 
Cable Segment

Permissible Single Twisted Pair Range 
(In Feet) For Each Cable Segment

Point-To-Point

Bus Configuration

2 Nodes/Repeaters

3 to 7 Nodes/Repeaters

Cable Manufacturer,
Part Number,
and Number of 
Gauges/Conductors

Manufacturer's 
Specifications

Data Threshold: 
All Nodes And/Or 
Repeaters On A 
Cable Segment

Permissible Single 
Twisted Pair Range (In Feet) 
For Each Cable Segment

Point-To-Point

Bus
Configuration

2 Nodes/Repeaters

3 to 7 Nodes/Repeaters

WEST PENN WIRE 991, 
14 AWG, 1 Pair Shielded

FPLR, UL 1424 and UL 1666 High:

1-800

1-100

Low:

600-1000

N/A

WEST PENN WIRE D995, 14 
AWG, 1 Pair Shielded

FPL, PVC, NEC, Article 760, 
UL 1424 and 1581

High:

1-800

1-100

Low:

800-1400

N/A

WEST PENN WIRE AQ225,
16 AWG, 1 Pair Unshielded

FPL or PLTC
Direct Burial Water Blocked

High:

1-1400

1-100

Low:

1200-2800

N/A

WEST PENN WIRE AQ294,
16 AWG, 1 Pair Shielded

FPL or PLTC
Direct Burial Water
Blocked

High:

1-1000

1-100

Low:

1000-1600

N/A

WEST PENN WIRE D980,
18 AWG, 1 Pair Unshielded

FPL, PVC, NEC Article 760, 
UL 1424 and 1581

High:

1-1200

1-100

Low:

1000-3000

N/A

WEST PENN WIRE D975,
18 AWG, 1 Pair Shielded

FPL, PVC, NEC Article 760, 
UL 1424 and 1581

High:

1-800

1-100

Low:

800-1400

N/A

NOTE:  In the event of a panel failure at a wire node, the data is not regenerated locally.  The node may be manually bypassed using the NBB-1 
Assembly.  In this case, the total length of wire becomes the sum of both lengths of wire between operating nodes.  If the total length exceeds the 
maximum allowable length for a given threshold, the network may lose communication.  Separately powered repeater(s) may be employed at each 
node in a point-to-point connection to ensure data regeneration.

Technical Manuals Online! - http://www.tech-man.com

firealarmresources.com

Содержание NOTI-FIRE-NET

Страница 1: ...Document 50257 E 7 5 01 Rev E PN 50257 E ECN 01 146 NOTI FIRE NET Manual Technical Manuals Online http www tech man com firealarmresources com...

Страница 2: ...proper storage of flammable materials etc Heat detectors do not sense particles of combustion and alarm only when heat on their sensors increases at a prede termined rate or reaches a predetermined le...

Страница 3: ...ct AC power and batteries prior to removing or in serting circuit boards Failure to do so can damage circuits Remove all electronic assemblies prior to any drilling filing reaming or punching of the e...

Страница 4: ...ons 13 Configuration Definitions 13 Characteristic Impedance In a Point to Point Configuration 14 Characteristic Impedance In a Bus Configuration 15 Terminating Point To Point and Bus Configurations 1...

Страница 5: ...ons port The network has the ability to send acknowledge signal silence drill and reset commands to the AFP 200 or AFP 300 AFP 400 AFP 200 or AFP 300 AFP 400 zones may be used to activate other networ...

Страница 6: ...s onto the NRT NET card to complete the network interface Each NRT or NCS requires a network node address The Repeaters RPT boost data signals between network nodes extending communication distances T...

Страница 7: ...a fiber optic segment The following paragraphs detail each procedure Twisted Pair Circuits The length of cable for each segment in the system must fall within the range specified in Table 2 If the dis...

Страница 8: ...100 Low 1200 2000 N A BRAND REX 93782 01 16 AWG 1 Pair Shielded Contact Manufacturer High 1 1400 1 100 Low 1200 2000 N A Genesis GJ 854020514 14 AWG 1 Pair Shielded FPLP NEC Article 760 High 1 400 1 1...

Страница 9: ...t Number and Number of Gauges Conductors Manufacturer s Specifications Data Threshold All Nodes And Or Repeaters On A Cable Segment Permissible Single Twisted Pair Range In Feet For Each Cable Segment...

Страница 10: ...ave to travel from one end of the network to the other end refer to Figure 2 The length is influenced by the total number of MIB NAM 232 RPT devices and medium along the circuit path Refer to Figure 3...

Страница 11: ...A B C or D When employing the SIB NET a MIB W MIB WF or MIB F is required The SIB 2048A may also be used as a NOTI FIRE NET interface with the NAM 232 Initiating Devices Initiating device requirement...

Страница 12: ...to the right of the break However the fragment to the right of the break can receive information from the fragment to the left of the break Figure 5 Fiber Optic Style 4 System Break Note A wire to wi...

Страница 13: ...optic cable or mixed media wire and fiber Figure 6 Style 7 Configurations Configuration Definitions The following configurations are defined Point To Point Configuration A point to point wiring config...

Страница 14: ...r network with more than two nodes Terminating resistors are only needed for the first and last nodes of the bus configuration all other terminating resistors must be removed In a bus configuration mo...

Страница 15: ...upport point to point connections to the remaining buildings in the system Figure 9 Combination Wiring Terminating Point To Point and Bus Configurations Both point to point and bus configurations requ...

Страница 16: ...R70 These point to point circuit segments are terminated at each node repeater A bus circuit spans multiple nodes repeaters with a terminating resistor at each end of the circuit segment A point to po...

Страница 17: ...rations for point to point and bus wire configurations In the examples that follow the MIB WF or NAM 232W may be used in place of the MIB W Point To Point Configuration In a point to point configurati...

Страница 18: ...s through switch SW3 is ON allowing the left node to provide ground fault detection for the two point to point wire connections on the left and right of the repeater The Port A switch on the right MIB...

Страница 19: ...etection along the bus The primary difference is that one node can provide ground fault detection for multiple nodes along the bus refer to EXAMPLE 1 and 2 Note Refer to the Network Adaptor Module NAM...

Страница 20: ...ft separate ground fault detection circuits must be fed through The node second from the right continues to provide ground fault detection up to the RPT W Port B and must be an AFP 200 AFP 300 AFP 400...

Страница 21: ...ng with the supplied tie wrap at each end of the cylinder 4 If used repeat for the remaining twisted pair s on a MIB W second port Figure 19 Installation of the Ferrite Cylinder on the NRT NCS Install...

Страница 22: ...22 NOTI FIRE NET PN 50257 E 7 5 01 Notes Technical Manuals Online http www tech man com firealarmresources com...

Страница 23: ...ting constitutes the only warranty made by NOTIFIER with respect to its products NOTIFIER does not represent that its products will prevent any loss by fire or otherwise or that its products will in a...

Страница 24: ...World Headquarters 12 Clintonville Road Northford CT 06472 1653 USA 203 484 7161 Fax 203 484 7118 www notifier com Technical Manuals Online http www tech man com firealarmresources com...

Отзывы: