background image

36

NFS2-640/E Installation Manual —

 P/N 52741:P2  7/10/14

Installation

Connecting the Power Cables

Connect external field wires to the power supply terminals TB10 RESET(+) and (–) to provide up 
to 1.25 A of current for powering four-wire smoke detectors. See Figure 3.16 above. TB2 (on CPS-
24), TB10 and all 4 NACS share a maximum of 3.0 A in standby and 6.0 A in alarm.

24 VDC Non-resettable Power Circuit  

The power supply provides one 24 VDC filtered, 

power-limited, non-resettable power output, capable of up to 1.25 A. Use this circuit to power 
devices that require low-noise 24 VDC power (such as annunciator model ACM-24AT or the 
transmitter module TM-4).

Connect external field wires to power supply terminals TB10 NO)and(–) to provide up 
to 1.25 A of non-resettable current for powering external devices such as annunciators. See 
Figure 3.16 above. TB2 (on CPS-24), TB10 and all 4 NACS share a maximum of 3.0 A in standby 
and 6.0 A in alarm. 

3.7.6  Accessories DC Power Output Connections

Terminal TB2 supplies one (1) non-resettable, power-limited 24 VDC circuit and one non-
resettable, power-limited 5 VDC circuit available to power external devices. Applications that 
require a 5V connection to the Accessories Output, such as an UZC-256, must be within 10 feet 
(3.658 meters) of the power supply. The distance from the power supply to the accessory requiring 
power must not extend past the length of the supplied cable, P/N 75657 (supplied with UZC-256), 
which is 10 feet long. Do not splice or otherwise extend P/N 75657. Refer to section B.2, "Wire 
Requirements" of 
this manual for all applications requiring a 24V connection. Connect wiring with 
all power sources off.

• 24 VDC (nominal) @ 0.5 A max
• 5 VDC (nominal) @ 0.15 A max

Figure 3.17  Connecting to the Accessories Output TB2 on CPS-24/E

!

CAUTION:

During system reset, power remains at terminals TB10 NO)and(–).

A

M

P

S

24_TB

2

access.wmf

24V

 - Blue Wire

COM

 - Black Wire

5V

 - Red Wire

COM

 - Black Wire

Содержание NFS2-640/E

Страница 1: ...P2 P N 52741 P2 ECN 13 838 Document 52741 7 10 14 Rev Fire Alarm Control Panel NFS2 640 E Installation Manual...

Страница 2: ...adequate warning of a fire Smoke detectors cannot be expected to provide adequate warn ing of fires caused by arson children playing with matches especially in bedrooms smoking in bed and violent exp...

Страница 3: ...Failure to do so can damage circuits Remove all electronic assemblies prior to any drilling filing reaming or punching of the enclosure When possible make all cable entries from the sides or rear Bef...

Страница 4: ...priate version for a specific application Documentation Feedback Your feedback helps us keep our documentation up to date and accurate If you have any comments or suggestions about our online Help or...

Страница 5: ...ay Unit 25 3 5 2 Using NCA 2 as Primary Display 26 3 6 Mounting Option Boards 27 3 6 1 Option Boards in the NFS2 640 E Chassis 27 3 6 2 Option Boards in CHS 4L 28 3 6 3 Option Boards on BMP 1 in Dress...

Страница 6: ...leasing Device to the Control Panel 56 4 7 4 Connecting a Releasing Device to the FCM 1 Module 57 4 7 5 Connecting Releasing Devices to the FCM 1 REL Control Module 59 4 7 6 Connecting an NBG 12LRA Ag...

Страница 7: ...Inspection Testing and Maintenance for Fire Alarm Systems NFPA 72 Notification Appliances for Fire Alarm Systems Underwriters Laboratories UL 38 Manually Actuated Signaling Boxes UL 217 Smoke Detector...

Страница 8: ...s well as documents for selected other compatible devices The document series chart DOC NOT provides the current document revision A copy of this document is included in every shipment Compatible Conv...

Страница 9: ...nunciator Manual 51482 System Components Document Number Annunciator Control System Manual 15842 FDU 80Remote Annunciator Manual 51264 LCD 80 Liquid Crystal Display Remote Annunciator 15037 LCD2 80 Li...

Страница 10: ...ment I56 1804 FSA 8000 Intelligent Aspiration Sensing Technology Document I56 3903 FWSG Wireless Manual LS10036 000NF E If you are installing the panel in the same cabinet as digital audio equipment h...

Страница 11: ...f detectors and modules Integral power supply with battery charger Four standard Notification Appliance Circuits NAC Class A or B Alarm Trouble Supervisory and Security relays Support for 32 annunciat...

Страница 12: ...operation or CPU2 640E 240V operation is the control panel itself and the heart of the system it ships with a grounding cable battery interconnect cables and document kit It includes power supply CPS...

Страница 13: ...ntegral battery charger This can be used for many functions including Powering the NFS2 640 E Powering a variety of UL listed 24 VDC notification appliances from four built in NAC outputs Providing up...

Страница 14: ...r Connection Figures 3 25 3 26 TB12 EIA 232 PC Terminal Connection CRT Figure 3 27 J1 Network Service Connection NUP power limited supervised J2 USB A VeriFire Tools Connection J3 USB B VeriFire Tools...

Страница 15: ...ignals Silenced LED LED4 System Trouble LED LED8 Fire Alarm LED LED1 Power on LED AC or battery System Switches for No Keyboard Operation SW5 Acknowledge SW6 Silence SW7 Reset CPU2640 KAPS 2 wmf CPU2...

Страница 16: ...ing Out Equipment in Cabinet and Chassis A size backbox one row 24 00 in 60 96 cm wide 20 00 in 50 8 cm tall 5 218 in 13 254 cm deep Uses optional trim ring TR A4 Optional trim ring TR A4 Opening 24 0...

Страница 17: ...t Panel Interface DS AMP Digital Amplifier DS BDA Backup Amplifier DS DB Digital Distribution Board DS XF70V Step up Transformer DVC AO Digital Voice Command Audio Output DVC EM Digital Voice Command...

Страница 18: ...ciator Dress Panel BMP 1 Blank Module Plate BP2 4 Battery Dress Plate CA 1 Audio Chassis CA 2 Audio Chassis CAB 4 Series Doors Black unless R is added to the P N Add B to the P N for blank door DR A4...

Страница 19: ...nd Local codes for fire alarm systems Do not draw wiring into the bottom 9 inches 22 86 cm of the cabinet except when using a separate battery cabinet this space is for internal battery installation R...

Страница 20: ...ttery charger Auxiliary power manuals 6 Connect AC wiring place batteries into backbox without connecting them and run cable to optional power supplies DC power outputs NACs and relays CAUTION Do not...

Страница 21: ...B 3 CAB 4 Series Cabinet Installation Document 3 4 Laying Out Equipment in Cabinet and Chassis The NFS2 640 E allows for flexible system design Backboxes are available to hold up to four rows of equip...

Страница 22: ...nt such as annunciators may be mounted on a dress panel directly in front of the control panel The BMP 1 Blank Module Plate covers unused positions in a dress panel also providing an additional mounti...

Страница 23: ...ed wiring as discussed in Section 3 11 UL Power limited Wiring Requirements Slot 2 CPU CPS 24 and primary display Slot 3 Mounting location for LEM 320 or other option board Slot 4 Mounting location fo...

Страница 24: ...with annunciator Dress panels DP DISP2 ADP2 640 ADP 4B Option board BMP 1 attaches to dress panel option module attaches to BMP 1 Screws provided with option module See Figure 3 7 Dress panel ADP 4B...

Страница 25: ...Mounting Perform the following steps when installing the NFS2 640 E 1 Screw chassis to the backbox 2 If installing KDM R2 as primary display Attach ribbon cable from keypad to J7 connector on control...

Страница 26: ...tand offs as shown in Figure 3 5 Mounting KDM R2 3 5 2 Using NCA 2 as Primary Display The NFS2 640 E can be set up to use the NCA 2 as the primary display In this system design mount NCA 2 to the NFS2...

Страница 27: ...oards in slots 3 and 4 of the NFS2 640 E chassis See Figure 3 2 Figure 3 6 and Figure 3 7 For standoff lengths see Table 3 2 NOTE This is the only NCA 2 application that does not require an NCM or HS...

Страница 28: ...on the option board 3 Attach the option board using screws provided with the board or if installing a second option board with stand offs provided with the second board 2 640_assembly_5a 2 wmf Attach...

Страница 29: ...nting an Option Board in a Chassis CHS 4L Shown Two option boards in CHS 4L NOTE See the BMP 1 Product Installation Drawing for details if considering mounting the module behind blank module plate in...

Страница 30: ...U2 640 2 Align the LEM with the four 1 inch standoffs and the stacker connector as shown in Figure 3 12 firmly seat the stacker connector 3 Attach LEM to standoffs using screws or another set of stand...

Страница 31: ...ion Document and the HS NCM Installation Document Do not connect two NCM HS NCMs via NUP ports aka NUP to NUP 3 When installing the NCM Connect Channel A and or Channel B as described in the NCM Insta...

Страница 32: ...port all Network Control by Event each node DVC CPU 2 and NCA 2 requires a network address NCM port in network applications DVC EM Digital Voice Command extended memory wire version standard DVC EMF D...

Страница 33: ...Auxiliary power source 24 VDC power 0 5 A and 5 VDC power 0 15 A from TB2 on the CPS 24 E See Appendix B 1 Electrical Specifications for details and overall installation guidelines NUP DAL Optional S...

Страница 34: ...contains a checklist for checking the system with AC power applied TB1 AC Power Connection Hot Neutral Ground Earth Figure 3 14 CPS 24 E AC Power Connections CAUTION While checking AC power make sure...

Страница 35: ...er Circuit Four Wire Smoke Detectors The power supply provides a single 24 VDC filtered power limited resettable power circuit for devices that require resettable power such as four wire smoke detecto...

Страница 36: ...B10 and all 4 NACS share a maximum of 3 0 A in standby and 6 0 A in alarm 3 7 6 Accessories DC Power Output Connections Terminal TB2 supplies one 1 non resettable power limited 24 VDC circuit and one...

Страница 37: ...appliances only refer to the Device Compatibility Document nfs640 nacout cdr Style Y Class B Connection Style Z Class A Connection Unused Circuits UL listed ELR 2 2K 1 2 W supplied Figure 3 18 Notifi...

Страница 38: ...For multiple Stat X devices installed in series the REL 2 2K is installed on the last device on the releasing circuit as shown A REL 2 2K is required for ULC applications Stat X devices are not to be...

Страница 39: ...the corresponding switch was enabled The alarm will activate during microcontroller failure regardless of the settings of switches SW1 SW4 SW1 NAC 1 SW2 NAC 2 SW3 NAC 3 SW4 NAC 4 So for example if SW1...

Страница 40: ...wiring is routed away from power limited wiring 320 2 640 PWRLMTWIR ISO2 wmf Figure 3 23 Typical Wiring for UL Power limited Wiring Requirements Shown with relays as connected to power limited module...

Страница 41: ...e specific connections can vary by the type of device being connected refer to the product installation manual for details Figure 3 24 EIA 485 Connections 3 13 Installing Remote Printers and or CRT 3...

Страница 42: ...is UL listed for Fire Protective Signaling You may use your building emergency power supply so long as it meets the power continuity requirements of NFPA 72 Refer to NFPA 72 for further details Connec...

Страница 43: ...protocol Baud Rate 9600 Parity Even Data bits 7 2 Set the printer DIP switches SP1 and SP2 according to settings in Table 3 7 Option Setting Option Setting Font LPI ESC Character Bidirectional Copy H...

Страница 44: ...s discussed in Table 3 27 Setting CRT 2 Parameters The CRT 2 communicates with the control panel through a protocol defined by thirteen groups of parameters To access a parameter group press the corre...

Страница 45: ...rmal Overscan Borders Off F4 Kybd Spl Funct key Language U S Keyclick Off Key Lock Caps Char Set Mode ASCII Key Repeat Off Keyboard Present Yes Key Mode ASCII Margin Bell Off F5 Keys Prior key Enter K...

Страница 46: ...information refer to the SLC Wiring Manual Wiring Maximum wiring distance of an SLC using 12 AWG 3 31 mm2 wire is 12 500 feet 3810 meters total twisted pair for Style 4 Style 6 and Style 7 circuits Ca...

Страница 47: ...via a standard USB B cable 2 For PCs without USB Ports connect the PC s serial port to the Control Panel Network Service Connection J1 NUP NOTE To meet the ten second response time required by UL 864...

Страница 48: ...to install UDACT UDACT 2 with the control panel for use as a NFPA Central or Remote Station Fire Alarm System Protected Premises Unit Section 4 5 NFPA 72 Proprietary Fire Alarm Systems How to set up a...

Страница 49: ...al or UDACT 2 Instruction Manual Device to be Supervised Non resettable 24 VDC Power from a listed source SLC from FACP FCM 1 N C Supervision Relay Contact Part of EOLR 1 Not required for FlashScan ty...

Страница 50: ...und To supervised phone lines Ferrite cores P N 29090 FACP Cabinet EIA 485 ACS Mode 24 VDC Nonresettable power Supervised and power limited EIA 485 and power wiring CPU2 640 udact wmf Figure 4 2 Typic...

Страница 51: ...FAIL PRI SEC OPTION SELECT SWITCH 1 2 3 4 OFF ON ON LED21 TONE DETECT RECON PULSE1 LED6 LED7 LED101 LED100 LED4 LED2 LED3 LED5 LED1 LED8 STATA STATB RCDA RCDB A HI B HI EF B TERM B SW101 SW102 SW103 O...

Страница 52: ...ogram one or more monitor modules listed for security applications with the SECURITY Type Code and wire as shown in Figure 4 6 Activating this type of module lights the SECURITY LED and displays a sec...

Страница 53: ...underneath the edge of KDM R2 4 6 3 Receiving Unit For applications requiring transmission of security alarm information to a central receiving unit the control panel may be connected via the UDACT or...

Страница 54: ...Refer to the Device Compatibility Document for compatible NAC devices All monitor modules used for security application must be installed in the NFS2 640 E cabinet with STS 1 Security Tamper Switch F...

Страница 55: ...disable functions in the panel as lockout WARNING Do not enable the BACKUP option switch for any of the four Notification Appliance Circuits NACs if they are used for releasing functions Standard Cove...

Страница 56: ...are supervised against opens and shorts 4 For applications not requiring power limited circuits a If the application does not require supervising the releasing device against shorts in line superviso...

Страница 57: ...A of current Make sure to keep total system current within the limits of the power supply You can power the module from the power supply of the Control Panel or any UL ULC listed 24 VDC regulated pow...

Страница 58: ...CKT c Limited energy cable cannot be used to wire a non power limited releasing device circuit d Maintain a 0 25 inch 6 35 mm spacing between the non power limited releasing circuit device wiring and...

Страница 59: ...C power Compatible UL listed 24 VDC releasing device One 1 device maximum Module polarities are shown in alarm condition All wiring shown is supervised and power limited Figure 4 13 NPFA Style Y Class...

Страница 60: ...the FCM 1 Module on page 57 If using the FCM 1 REL see Circuit Requirements for Section 4 7 5 Connecting Releasing Devices to the FCM 1 REL Control Module on page 59 SLC loop to FACP or LEM 320 FCM 1...

Страница 61: ...NFS2 640 E Installation Manual P N 52741 P2 7 10 14 61 Releasing Applications Applications...

Страница 62: ...the fire department and the central alarm receiving station if transmitting alarm conditions b notify facility personnel of the test so that alarm sounding devices are disregarded during the test peri...

Страница 63: ...ion A discharged battery typically reaches the voltage of 27 6 VDC within 48 hours the charge rate depends on the battery size 2 0A for 18 26AH 5 0A 5 7A for 26AH 200AH Batteries should be replaced in...

Страница 64: ...of external devices continuously during non fire alarm conditions Use column 1 in Table A 2 to calculate the Non Fire Alarm Load on the power supply regulator when applying primary power The main pow...

Страница 65: ...each set of devices in calculation columns 1 2 and 3 Calculation Column 1 Primary Non Fire Alarm Current in amps Add the contents of calculation column 1 to get the current drawn from the power supply...

Страница 66: ...ing non fire conditions x 0 0054 x 0 0054 AFM 16AT AFM 32A ACM 16AT ACM 32A AEM 16AT AEM 32A x 0 040 x 0 040 x 0 002 x 0 056 x 0 056 x 0 018 x 0 040 x 0 040 x 0 002 AFM 16A ACM 8R refer to manual LDM...

Страница 67: ...in amps Total Current Type Alarm Current from Table A 2 col 2 APS 6R Actual load current may be used in place of maximum rated supply current To calculate actual load current sum the current draws for...

Страница 68: ...tems require 24 hours of standby power followed by 5 minutes in alarm 2 NFPA 72 Auxiliary and Remote Station Systems require 24 hours of standby power followed by 5 minutes in alarm 3 Batteries instal...

Страница 69: ...the acceptable battery charger range Write the amp hours requirements on the Protected Premises label The maximum battery size that can be mounted inside a CAB 4 series backbox is 26AH Battery Size Vo...

Страница 70: ...Description Specifications CPS 24 E Main Power Supply An internal battery charger for 18 AH to 200 AH Normal Charge 27 6 VDC 0 24 VDC Charging Current 2 0 A or 5 7 A Software selectable CHG 120 Batte...

Страница 71: ...tification appliances Operating Power AC Branch Circuit The control panel requires connection to a separate dedicated AC branch circuit Follow these guidelines when connecting the AC branch circuit La...

Страница 72: ...tery charger is current limited and can recharge sealed lead acid type batteries The battery charger shuts off when the control panel is in alarm B 2 Wire Requirements Each type of circuit within the...

Страница 73: ...18 AWG 0 82 mm2 minimum 20 feet 6 1 m without modem 16 AWG 1 31 mm2 IDC Initiating Device Circuit FMM 1 FMM 101 FDM 1XP10 M XP6 MA power limited 12 18 AWG 3 31 to 0 82 mm2 Maximum circuit resistance i...

Страница 74: ...re information The NCA 2 or Network Control Station NCS may be employed as a Display and Control Center In the event that communication fails between the panels and the Control Center the panels will...

Страница 75: ...ower Supply CPU CPU 640 120V operation 12 CPU 640E 240V operation 12 Drawing 13 14 15 Overview 13 CRTs 46 CRT PRN Combination 46 CRT 2 Configuration 44 CRT 2 Function Keys and Parameters 45 Installati...

Страница 76: ...Combination 46 Proprietary Security Alarm Applications Wiring 54 Protected Premises Unit 49 R Related Documentation 8 Relays see Form C Relays 38 Releasing Circuits Connections 37 Releasing Applicatio...

Страница 77: ...NFS2 640 E Installation Manual P N 52741 P2 7 10 14 77 Index W W...

Страница 78: ...World Headquarters 12 Clintonville Road Northford CT 06472 1610 USA 203 484 7161 fax 203 484 7118 www notifier com...

Отзывы: