Liquid Crystal Display

LCD-160

Manual

  

Содержание LCD-160

Страница 1: ...A P N 51850 A ECN 03 419 Document 51850 09 26 2003 Rev Liquid Crystal Display LCD 160 Manual...

Страница 2: ...ate warning of fires caused by arson children playing with matches especially in bedrooms smoking in bed and violent explosions caused by escaping gas improper storage of flammable materials etc Heat...

Страница 3: ...l electronic assemblies prior to any drilling filing reaming or punching of the enclosure When possible make all cable entries from the sides or rear Before making modifi cations verify that they will...

Страница 4: ...information Product name and version number if applicable Printed manual or online Help Topic Title for online Help Page number for printed manual Brief description of content you think should be imp...

Страница 5: ...l Hardware 15 Section 5 Mounting 16 Mount the Cabinet or Backbox 16 Mount the LCD 160 16 In an CAB 4 Series backbox 16 In an ABS 2D 4D or ABF 2B 4B backbox 16 Section 6 Wiring 17 Overview 17 The RDP B...

Страница 6: ...hic Screen 32 Programming Screens 33 Setting the Programming Switch 33 Panel Program Menu 34 LCD Display 35 Programming Confirmation Dialog 36 Operating Screens 37 Event Counts Display 37 More Informa...

Страница 7: ...ipment damage irreversible loss of programming data or personal injury Table 1 1 Typographic Conventions in this Manual When you see Specifies Example text in all caps and bold text In body text text...

Страница 8: ...or the Installation of Fire Alarm Systems Applicable Local and State Building Codes Requirements of the Local Authority Having Jurisdiction The Canadian Electrical Code Part 1 2 1 Related Documentatio...

Страница 9: ...ort diagnostics Software upgrades and foreign languages character sets via serial port from a panel or other device via the Remote Data Port RDP interface Upgrades do not require the replacement of an...

Страница 10: ...rd layout is illustrated in Figure 1 J1 Key Switch LED 13 Transmit LED 12 Receive SW17 LED14 MicroFail LED11 Status TB2 Power TB1 RDP Port See Figure 11 See Figure 8 See Figure 13 See Figures 9 and 21...

Страница 11: ...ough 10 indicate system status and are visible to the user See Status LED Indicators on page 25 for information on LED indicators 1 10 Table 3 1 Diagnostic LED Indicators Reference LED Name Color Desc...

Страница 12: ...12 LCD 160 P N 51850 A 09 26 2003 System Overview Features and Specifications...

Страница 13: ...7 Mount the dress panel to the backbox 8 Make all electrical connections RDP bus shielding if necessary Figures 7 8 Power circuit Figure 11 9 Attach doors to backboxes Section 5 2 10 Power up system...

Страница 14: ...semi flush enclosure for mounting one to four rows of equipment plus batteries up to two 25AH batteries There are four different sizes available The separately ordered doors can be mounted on the lef...

Страница 15: ...y to threaded studs on the dress panel An LCD 160 mounted on an ADP 4B fits in front of most CAB 4 series chassis as long as the top layer of the chassis is displayless or unoccupied Figure 3 ADP 4B s...

Страница 16: ...on page 19 and Power Supply Connections on page 21 3 If using a semi flush mount backbox attach the door Align the door with the dress plate and slide the door down onto the pins on the dress plate Wh...

Страница 17: ...different knockouts Install tie wraps and adhesive squares to secure the wiring WARNING Remove all power sources to equipment while connecting electrical components Leave the external main power break...

Страница 18: ...e the RDP bus as shown in Connecting the RDP Bus on page 19 These requirements must be followed There is a maximum of 4000 feet at 12 AWG to 18 AWG between the panel and the last device on the RDP bus...

Страница 19: ...vides RDP circuit diagrams for the LCD 160 See RDP Bus Wiring Specifications on page 18 for circuit requirements End of Line Resistor for RDP Devices If the LCD 160 is the last device on the RDP bus t...

Страница 20: ...earth ground such as a cold water pipe Connect the LCD 160 s Earth Ground located on the RDP interface to a mounting screw on the backbox or cabinet See Figures 8 and 10 Figure 9 SW17 ELR Disabled LC...

Страница 21: ...n have ground fault detection enabled The power run to the LCD 160 need not contain a Power Supervision Relay because loss of power is inherently supervised through communication loss loss of RDP comm...

Страница 22: ...etection disabled Common Reference LCD 160 Remote Power Supply A caba3 wmf Fire Alarm Control Panel Two wire RDP bus Power Loop When more than one power supply is used on an RDP bus a common reference...

Страница 23: ...well as other information Enter or change fields and issue commands on the display by using both the fixed function and soft keys on the keypad 7 2 The Keypad The keypad consists of two types of keys...

Страница 24: ...to the appropriate FACP manual for further information about this function SYSTEM RESET Press this key to send a system reset command to the panel The exact action to take on a reset command is contr...

Страница 25: ...dged Security Blue Illuminates when at least one security event exists It will flash if any of these events are unacknowledged Supervisory Yellow Illuminates when at least one supervisory event exists...

Страница 26: ...40 characters long Line one is a custom message Line two is a standard message showing the System Normal status Line five indicates the current time and date Event Reporting Format When there is an o...

Страница 27: ...been acknowledged or cleared Event Format nottrouble or pre alarm Event Format trouble Line 1 DisplaysPREALARM the sensitivity reading and whether it has been acknowledged or cleared PREALARM 120 OF...

Страница 28: ...Event Display Example The event counts section shows the counts for outstanding events The date in line eight gives the current time The soft keys may be used to deal with the event their functions ar...

Страница 29: ...CC all remote displays with Local Control ON will automatically participate Refer to the FACP programming manual for more information When an LCD 160 is not the DCC pressing Signal Silence System Rese...

Страница 30: ...ntrol to the requesting device NO Press this key to deny control to the requesting device FIRE ALARM ELEVATOR LOBBY EAST WING FIFTH FLOOR Z005 SMOKE PHOTO 11 57 45A WED JUN 26 2003 N112L03D052 RELEASE...

Страница 31: ...individually event acknowledge or as a group block acknowledge Event Acknowledge Event acknowledge acknowledges off normal events one at a time you must press the acknowledge key once for each event t...

Страница 32: ...Program screen This option will not be visible if any unacknowledged fire alarms exist or if the programming switch is disabled See pages 33 34 GRAPHIC SCREEN Press this key to display the Graphic Sc...

Страница 33: ...arm present Setting the Programming Switch The LCD 160 s programming switch must be enabled to program the LCD 160 Set dip switch 1 on SW17 to permit programming on the LCD 160 SW17 is located on the...

Страница 34: ...bled Refer to Setting the Programming Switch on page 33 SOFT KEYS ADDRESS CHANGE Press this key to increase the LCD 160 s address on the RDP bus The address will cycle from 1 to 32 PIEZO Press this ke...

Страница 35: ...by 4 BACKLIGHT Pressing this key toggle the status of the backlight between ON OFF and ON EXCEPT AC FAIL DEFAULT Press this key to revert all screen preferences to their factory settings ACCEPT Press...

Страница 36: ...atabase and reminds them not to power off the system during the update SOFT KEYS YES Press this key to write the changes you made in the Panel Program Menu and the LCD Display screen to the database N...

Страница 37: ...ge 26 Lines six and seven display current counts of off normal events in six categories The counts include both acknowledged and unacknowledged events During an off normal event line eight will displa...

Страница 38: ...event information on the More Information screen PROGRAM Press this key to go to the Panel Program Menu This option will not be visible if any unacknowledged fire alarms exist or if the programming sw...

Страница 39: ...eding the prealarm level by 45 Line 12 ALARM 6 1 66 Six is the preprogrammed alarm level value for this detector its value is 1 66 indicating the percent per foot obscuration value assigned to level 6...

Страница 40: ...e address es of any detector s linked with the detector that is in alarm for Co operative Multi alarm Sensing This field does not display for Acclimate detectors Line 15 The line displays the current...

Страница 41: ...g one of the Scroll Display fixed function keys will cause the first event of that type e g alarm trouble etc to display at the top and subsequent events of that type to display in sequence below it I...

Страница 42: ...n event list This option will change to MAIN MENU when the FIRST EVENT key is pressed ACKNOWLEDGED FIRE ALARM ELEVATOR LOBBY EAST WING FIFTH FLOOR Z005 SMOKE PHOTO 11 57 45A WED JUN 26 2003 N112L03D05...

Страница 43: ...e screen as they are completed Failure of a test may prevent the LCD 160 from performing its functions Holding the DRILL key during the power up will reset all settings including address information t...

Страница 44: ...may use the TROUBLE scroll display key to list individual troubles Download Application Screen This screen is displayed during application downloads Downloading is initiated at the FACP The progress...

Страница 45: ...der Screen Download Strings Screen This screen is displayed during strings downloads Downloading strings is initiated at the FACP The progress meter shows the progress of the current download Figure 3...

Страница 46: ...cation code Usually this screen results from a power interrupt during a critical period of application download The Trouble LED will flash and the piezo if enabled will sound while this screen is in e...

Страница 47: ...l Ratings Input Voltage 24 VDC must be non resettable Data Communications Port RDP interface power limited Table 9 1 LCD 160 Current Draw Non Fire Alarm Status A Power LED is on backlight is off Numbe...

Страница 48: ...48 LCD 160 P N 51850 A 09 26 2003 Screen Displays Service Screens...

Страница 49: ...t Scroll Display key 24 Display and Control Center 24 29 30 Display intensity 35 Download screens 44 45 DP DISP 15 Dress Panels 15 16 Drill and Power up screen 43 fixed function key 24 E Earth Ground...

Страница 50: ...LED indicator 11 Remote Data Port see RDP S Scroll Back 42 SCROLL DISPLAY keys 24 Security events 31 event format 27 LED indicator 25 SCROLL DISPLAY key 24 Self Test Screen see Power Up Screen Servic...

Страница 51: ...nville Road Northford Connecticut 06472 1653 This writing constitutes the only warranty made by NOTIFIER with respect to its products NOTIFIER does not represent that its products will prevent any los...

Страница 52: ...World Headquarters 12 Clintonville Road Northford CT 06472 1653 USA 203 484 7161 fax 203 484 7118 www notifier com NOTIFIER is a company...