ID50 Series Panel - Installation, Commissioning & Configuration Manual
Configuration
Mode
70
997-263, Issue 4
September 2002
5.7.8 Zones
The Zones option determines the output response when
a zone detects an alarm. Each zone can be configured
as Yes (Y), No (N), Pulse (P), Coincidence (C) or Delay
(D) - see
Section 5.7
for definitions of these parameters.
If Day Mode is enabled (
Section 5.5.17, Day mode
activity
) delays do NOT occur unless manually activated.
Manual activation can occur at any time of day - it does
not have to be during the set Day Mode period. Delays
are automatically de-activated with the end of the day
mode period.
To change the CBE Rules: Zone Setting from the CBE
Rules: Output menu, follow the described procedure
below:
1
From the menu options below, press the
9
button
to select the Zones option.
2
The LCD displays the pattern number and zone range
(either 1 to 16 for fire alarms or 17 to 32 for plant
alarms) on line 1. Line 2 of the LCD displays the
selected zones number, the full description of its
current status and the zones flashing editable status.
To select a zone, press the
6
button until the
appropriate zone number appears on line 2 in the
left-hand corner. The display cycles from 16 to 1 and
32 to 17.
3
To change a zones status, press the
2
/
8
buttons
until the required state is displayed.
4
Confirm the changes by pressing the
5
button.
Press
4
to cancel any changes.
CBE Rule:01
6:Class Change
7:Two Zone
9:Zones
×
: More
CBE Rule 01 Zones
1--------------------16
[Zone 01]
[Yes
]
Y
YYYNYYYNDDNCCNN
CBE Rule 01 Zones
1--------------------16
[Zone 06]
[No
] YYYYN
N
YYNDDNCCNN
CBE Rule 01 Zones
1--------------------16
[Zone 06]
[No
] YYYYN
N
YYNDDNCCNN
CBE Rule 01 Zones
1--------------------16
[Zone 06]
[Yes
] YYYYN
Y
YYNDDNCCNN
CBE Rule 01 Zones
1--------------------16
[Zone 06]
[Pulse
] YYYYN
P
YYNDDNCCNN
6
2
8
x5
9
Содержание ID50 SERIES
Страница 1: ...ID50 60 installation commissioning configuration manual 997 263 Issue 4 September 2002...
Страница 2: ......