ID50 Series Panel - Installation, Commissioning & Configuration Manual
Configuration
Mode
67
997-263, Issue 4
September 2002
5.7.3 Evacuation
The Evacuation option has two states, Yes (Y) and No
(N). This option is available with the Fire, Pre-Alarm and
Device Inputs rules. To change the Evacuation setting:
1
Press the
3
button (using the numeric keypad) to
select the Evacuation option from the menu below.
2
Press the
6
button to select the required setting.
Refer to
Section 5.7, Control-By-Event Output
Rules
for further information.
3
Confirm the selection by pressing the
5
button. To
cancel the selection, press
4
button. In either case
the menu below is re-displayed.
5.7.4Silence
The Silence option has two states, Yes (Y) and No (N).
This option is available with the Fire, Pre-Alarm and
Device Inputs rules. To change the Silence setting from
the CBE Output Rules menu:
1
Using the numeric keypad, press
4
to select the
Silence option from the menu below.
2
Press the
6
button to select the required setting.
Refer to
Section 5.7, Control-By-Event Output
Rules
for further information.
3
Confirm the selection by pressing
5
. To cancel the
selection, press
4
button. In either case the menu
below is re-displayed.
CBE Rule:01
1:Type
2:Filter
3:Evac
4:Silence
5:Interrupt
×
: More
CBE Rule:01
Evacuate = [Y]
>:Change
3
:Accept
< : Cancel
CBE Rule:01
Evacuate = [N]
>:Change
3
:Accept
< : Cancel
CBE Rule:01
1:Type
2:Filter
3:Evac
4:Silence
5:Interrupt
×
: More
CBE Rule:01
1:Type
2:Filter
3:Evac
4:Silence
5:Interrupt
×
: More
CBE Rule:01
Silence = [N]
>:Change
3
:Accept
< : Cancel
CBE Rule:01
Silence = [Y]
>:Change
3
:Accept
< : Cancel
CBE Rule:01
1:Type
2:Filter
3:Evac
4:Silence
5:Interrupt
×
: More
6
3
5
6
5
4