ID50 Series Panel - Installation, Commissioning & Configuration Manual
Configuration
Mode
65
997-263, Issue 4
September 2002
5.7.1 Output Type
Nine (9) CBE Output Rule types are available. This menu
allows the type to be selected. The current attributes of
the selected Rule are displayed and can be edited. To
change the Rule type, from the CBE Output Rules menu
proceed as follows:
1
Press the
1
button on the numeric keypad to select
the Type option from the menu. The LCD displays the
Type menu:
2
Using the
2
/
8
buttons, step through the CBE
Output Rule types until the required type is displayed
on the upper line, i.e. FIRE, EXTSYSTEM, DAY
MODE, RESET, FTR, PLANT, PRE-ALARM, FAULT,
INPUTS.
3
Press the
5
button to confirm selection. The LCD
displays only the appropriate editable settings for the
selected rule, for example:
To change any of the settings on the CBE Output Rules
refer to
Sections 5.7.2 Filter-by-type, 5.7.3 Evacuation,
5.7.4 Silence, 5.7.5 Interrupt Delay, 5.7.6 Class Change,
5.7.7 Two Zone, 5.7.8 Zones,
5.7.9 Device Inputs
and
5.7.10 Soak Timer
.
CBE 01 [FIRE
][ANY] 1--------------------16
1 : Change[EvSlln
] YYYYNNYYNDDNCCNN
CBE Rule:01
1:Type
2:Filter
3:Evac
4:Silence
5:Interrupt
×
: More
CBE Rule:01
Current Type = [FIRE ]
×
: Change Rule Type
3
: Accept < : Cancel
5
or
8
2
xn
1