ID50 Series Panel - Installation, Commissioning & Configuration Manual
Configuration
Mode
41
997-263, Issue 4
September 2002
5.5.7 Device Blinking
The Device Blinking option configures the LEDs of
sensors and modules on the SLC Loop to blink or not
when polled. To configure this option:
1
From the Commissioning menu, press the
1
button
on the numeric keypad to enter the Setup menu.
2
Press the
2
/
8
buttons to step through the Setup
menus until the LCD shows the Device Blinking menu.
3
Press the
6
button to select the required setting,
either ON or OFF.
4
Press
4
to return to the Commissioning menu.
[Setup]
Device Blinking = ON
> : Change
×
: More
< : Exit
[Setup]
Device Blinking = OFF
> : Change
×
: More
< : Exit
1
or
8
2
6
[Setup] Language =
English
> : Change
×
: More
< : Exit
5.5.6 Hold Switch Operation
AUX modules, configured as one of four Hold Switch
categories, can be used to affect the Extinguishing
System Delay timer function. The four categories are:
AHJ - While this input is active, the Extinguishing System
Delay timer is reset to the configured value and paused.
NYC - While this input is active, the Extinguishing
System Delay timer is reset to the configured value
plus 90 secs and paused.
ULI - While active, the Extinguishing System Delay
timer continues to count down but pauses at 10 secs
before release.
IRI - Hold switch activity is ignored if two or more
zones associated with CBE rules with a category of
Extinguishing System are in alarm. Otherwise
operation is the same as type ULI.
Note:
Only one of the above Hold Switch input types may
be used per panel.
1
From the Commissioning menu, press the
1
button
on the numeric keypad to enter the Setup menu.
2
Press the
2
/
8
buttons to step through the Setup
menus until the LCD shows the Hold Switch Operation
menu.
3
Press the
6
button to select alternative settings of
NYC, ULI or IRI, as required. Changing the setting
saves the change automatically.
Note:
The default selection is AHJ.
[Setup] Language =
English
> : Change
×
: More
< : Exit
[Setup]
Hold Switch Operation =
AHJ
> : Change
×
: More
< : Exit