ID50 Series Panel - Installation, Commissioning & Configuration Manual
Commissioning
31
997-263, Issue 4
September 2002
Status: NORMAL
Sat 05/01/2002
00:00
4.5 Powering the Panel
To power up an ID50 Series panel:
1
Ensure all wiring is terminated correctly and all PCBs
are fitted correctly.
2
With the batteries in the back box, connect the mains/
battery supply wiring plug to the power socket,
between the mains fuse (FS1) on the left and the
battery fuse (FS2) to the right. Turn on the mains
supply. The panel will display CPU RESTART with the
buzzer sounding, and the FAULT, SYSTEM FAULT
and POWER LEDs will illuminate.
3
Connect the battery power supply (refer to
Section 4.5.2 Batteries
).
4
When powered up, press the RESET button (then
enter an appropriate access code if required). The
panel should settle to a quiescent state. The LCD
should display the Status: NORMAL message unless
fault(s) are present on the system.
Note:
If the panel indicates fault(s) are present, clear
them before you proceed further with the
commissioning procedure.
5
When all fault LEDs have been extinguished, the panel
is ready to test the system, see
Section 4.7,
Commissioning Tests
.
FAULT
01/01
00:00
CPU RESTART
4
3
2
1
4.5.1 Start-up Language Selection
At panel start-up, and with a non-configured memory, you
will be prompted to select the appropriate panel language
from a displayed screen similar to the one below:
Press the appropriate numeric pushbutton to select the
desired language. If a selection is not made within 30
secs the panel will use the first language listed. The list
of languages may vary from those listed above.
Note:
If the memory is unlocked (refer to
Section 4.3.1
Jumper Link Options
) selection of the desired
language will be stored and this language will be
used the next time the panel is re-started. If the
memory is locked when a language selection is
made, the panel will not store this change and the
Startup Language screen will be displayed again
at the next panel startup. However, the language
can be changed at any other time using the
Language setup menu (refer to
Section 5.5.1
).
1: English
2: España
3: Portugues
4: Islanska
5: Italiano
Содержание ID50 SERIES
Страница 1: ...ID50 60 installation commissioning configuration manual 997 263 Issue 4 September 2002...
Страница 2: ......