Notifier  12 Clintonville Rd, Northford, CT 06472-1653  Phone: (203)484-7161

Before Installing

This  detector  must  be  installed  in  compliance  with  the 
control  panel  system  installation  manual. The  installation 
must meet the requirements of the Authority Having Juris-
diction (AHJ). Detectors offer maximum performance when 
installed  in  compliance  with  the  National  Fire  Protection 
Association (NFPA); see NFPA 72. 

General Description

The HPX-751 Smoke Detector uses a small air intake fan 
and  a  high  density  replaceable  filter. Air  and  smoke  are 
drawn into a photoelectric sensing chamber while airborne 
particulate and water mist are removed. The addressable-
analog  detector  transmits  an  analog  representation  of 
smoke  density  over  a  communication  line  to  a  control 
panel. Rotary decade switches are provided for setting the 
sensor’s address. Two LEDs on the sensor are controlled 
by the panel to indicate sensor status.
 

The  HPX-751  smoke  detector  is  intended  for  use  in 
normal environmental conditions, where dust and oth-
er airborne particulate are present at elevated levels. 
These elevated levels tend to cause false alarms and 
high maintenance in standard detectors. HPX-751 pro-
vides a protective enclosure for a photoelectric smoke 
detector chamber and allows smoke detection in areas 
that tended to use exclusively heat detection.
HPX-751 requires compatible addressable communic-
ations  to  function  properly.  Connect  this  detector  to 
listed-compatible control panels

 

only.

Spacing

Notifier recommends spacing detectors in compliance with 
NFPA 72. In low air flow applications with smooth ceilings, 
space  detectors  30  feet  apart.  For  specific  information 
regarding  sensor  spacing,  placement,  and  special  appli-
cations, refer to NFPA 72 or the 

System Smoke Detector 

Application Guide 

available from Notifier.

HPX-751 Intelligent Photoelectronic Smoke Detector

Installation and Maintenance Instructions

Specifications 
Operating Voltage Range:               15 to  32 VDC
Detector Current:                            230 

µ

A @ 24 VDC (without communication)

                                                        285 

µ

A @ 24 VDC (one communication every 5 sec. with LED enabled)

Auxiliary Power Supply Voltage:     15 to 30 VDC filtered; Ripple voltage may not drop below 15 volts.
Auxiliary Power Supply Current –   
              Peak:                                 123 mA max.
              Average:                            27 mA max.
Operating Humidity Range:             10% to 93% Relative  

Humidity, noncondensing

Operating Temperature Range:       0° to 50°C (32° to 122°F)
Height:                                             2.8 inches (43 mm)
Diameter:                                        6.1 inches (155 mm) installed in B710HD
                                                        4.0 inches (102 mm) installed in B524FTXE
Weight:                                             

7.3 oz. (207 g)

Compatibility:                                  Backwards compatible with 700 and 500 series products’ protocol                                    
Mounting Base:                               Requires B710HD (U.S.), B524FTXE (Europe) 

 

N500-59-00                                                                                                   4                                                                                                I56-1250-05R 

                                                                                                                                                                                                                     © 2001 Notifier

Figure 5: Installing detector into base:

1. Grasp  the  housing  with  one  hand  and  the  cover  with 

the other. Turn the cover counterclockwise fully (approx. 
30 degrees) and remove cover by pulling it away from 
detector unit (see Figure 4).  

2. Replace with new filter and cover assembly.

 

The cover 

is keyed so it fits in place only one way. Turn the cover 
clockwise until it stops.

    

NOTE:

 The base is equipped with an optional tamperproof 

feature which can be used to prevent unintentional removal 
of the unit while replacing the filter.

If a clogged filter was the cause of the trouble condition, 
normal  detector  operation  should  resume  automatically 
within  five  minutes.  If  the  trouble  condition  persists,  the 
detector must be returned for repair or replacement.
Installing Detector Into Base
1. Align the detector at a right angle to the base, with the 

five wires and connectors adjacent to the connector re-
ceptacle as shown in Figure 5.

2. Plug the wired connector into the receptacle.
3. Rotate the detector into the base, making sure detector 

and base keyed fit is lined up. Turn the detector clock-
wise until it snaps into place.

IMPORTANT:  HPX-751  will  only  operate with B710HD/

 

B524FTXE Mounting Base.

FCC Statement

This device complies with part 15 of the FCC Rules. Operation is subject to the following two conditions: (1) This device may not cause harmful inter-
ference, and (2) this device must accept any interference received, including interference that may cause undesired operation.
Note: This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to Part 15 of the FCC Rules. These lim-
its are designed to provide reasonable  protection against harmful interference in a residential installation.  This equipment generates,  uses and can  
radiate radio frequency energy and, if not installed and used in accordance with the instructions, may cause harmful interferenc  

  

 

    

 

nications. However, there is no guarantee that interference will not occur in a particular installation.  If this equipment does cause harmful int   
ference to radio or television reception, which can be determined by turning the equipment off and on, the user is encouraged to try to correct the inter-
ference by one or more of the following measures:
           

– Reorient or relocate the receiving antenna.

           

– Increase the separation between the equipment and receiver.

           

– Connect the equipment into an outlet on a circuit different from that to which the receiver is connected.

           

– Consult the dealer or an experienced radio/TV technician for help.

Please refer to insert for the Limitations of Fire Alarm Systems