N200-06-00                                                                                                     1                                                                                                    I56-057-02R

Notifier 12 Clintonville Road, Northford, CT 06472 (203) 484-7161

This sensor must be installed in compliance with the control panel system installation manual. The installation must meet the requirements of the Authority 
Having Jurisdiction (AHJ). Sensors offer maximum performance when installed in compliance with the National Fire Protection Association (NFPA); see NFPA 
72.. 

GENERAL DESCRIPTION

Model FSL-751 is a plug-in type smoke sensor that uses a laser based photoelectronic sensing chamber. The sensor uses analog-addressable communications 

to transmit smoke density and other information to the control panel.
Two LEDs on each sensor light to provide a local, visible sensor indication. Remote LED annunciator capability is available as an optional accessory (Part No. 
RA400Z).
Notifier panels offer different features sets across different models. As a result, certain features of the product may be available on some control panels, but not 

on others. The possible features available in the product, if supported by the control unit are:
1. The panel controls the LED operation on the sensor. Operational modes are RED blink, RED continuous, GREEN blink, and off.
2. The remote output may be synchronized to the LED operation or controlled independent of the LEDs.
Please refer to the operation manual for the UL listed control unit for specific operation of the FSL-751.

SPECIFICATIONS

Operating Voltage                      
Range:                                        15 to  32 VDC
Standby Current:                         330

µ

A

 

@ 24 VDC (one

 

                                                    communication every 5 seconds
                                                    with LED blink enabled)
Max.  Alarm Current (LED on):   6.5 mA @ 24  VDC
Operating Humidity Range:         10% to 93% Relative Humidity,
                                                    noncondensing
Operating Temperature Range:  0° to 38°C (32° to 100°F); U.S.
                                                    -10° to 50°C (14° to 122°F); Europe
Height:                                         1.7 inches (43 mm) installed
                                                    in B710LP Base
Diameter:                                    6.1 inches (155 mm) installed
                                                    in B710LP Base
                                                    4.1 inches (104 mm) installed
                                                    in B501 Base
Weight:                                        5.0 oz. (142 g)

SPACING

Notifier recommends spacing sensors in compliance with NFPA 72. In low air flow applications with smooth ceilings, space sensors 30 feet apart. For specific 
information regarding sensor spacing, placement, and special applications, refer to NFPA 72 or Notifier’s 

System Smoke Detector Application Guide

 , available 

at no charge from Notifier.

WIRING INSTRUCTIONS

All  wiring  must  be  installed  in  compliance  with  the  National  Electrical  Code,  applicable  local  codes,  and  any  special  requirements  of  the Authority  Having 
Jurisdiction. Proper wire gauges should be used. The installation wires should be color-coded to limit wiring mistakes and ease system troubleshooting. Improper 
connections will prevent a system from responding properly in the event of a fire.

Disconnect power from the communication line before installing sensors.

All wiring must conform to applicable local codes, ordinances, and regulations.
1.   Wire the sensor base (supplied separately) per the wiring diagram (Figure 1).
2.   Set the desired address on the sensor address switches.
      NOTE: Some panels support extended addressing. In order to set the sensor above address 99 

on  compatible  systems,  carefully  remove  the  stop  on  the  upper  rotary  switch  with  thumb  as 
shown in Figure 2.

3.   Install the sensor into the sensor base. Push the sensor into the base while turning it clockwise 

to secure it in place.

4.   After all sensors have been installed, apply power to the control unit and activate the commu-

nication line.

5.   Test the sensor(s) as described in the 

TESTING

 section of this manual.

CAUTION

Dust covers provide limited protection against airborne dust particles during shipping. Dust covers 
must be removed before the sensors can sense smoke. Remove sensors prior to heavy remodeling 
or construction.

TESTING

Before  testing,  notify  the  proper  authorities  that  the  system  is  undergoing  maintenance,  and  will 

A78-2461-00

Figure 1. Wiring Diagram

A78-2462-02

Figure 3.

Do not loop wire under terminal 
1  or  2.  Break  wire  to  provide 
supervision of connection.

CAUTION

Figure 2. Rotary Address Switches

FSL-751 Intelligent Laser Smoke Sensor

Installation and Maintenance Instructions