WHEN AUDIBLE DEVICES ARE SOUNDING -

FOR AN ALARM

1. Evacuate the protected area

2. Notify the monitoring service and/or the Fire Department immediately. Tell them briefly what happened and what
    your current status is.

Phones: ____________________________     _________________________________

                                       

              Fire Department                                                Monitoring Service

3. If the Fire Department is responding, be prepared to provide directions to arriving firefighters.

FOR TROUBLE ONLY

1. Notify the monitoring service and/or Fire department if this panel is connected to either one, and tell them
    what is happening.

2. Silence audible devices by unlocking and opening the panel and pressing the ACKNOWLEDGE/STEP key. The
    yellow system TROUBLE LED will remain on. Contact authorized service personnel immediately! (See Below).

WARNING!

DO NOT ALLOW TROUBLE CONDITIONS TO REMAIN LOGGED IN THE SYSTEM.  THE PROTECTION

THE SYSTEM OFFERS HAS BEEN COMPROMISED, OR ELIMINATED WHEN A TROUBLE CONDITION

EXISTS.

To return to normal after an alarm

1. Do not enter the protected area until safe to do so.
2. Clear all initiating devices. Smoke detectors will not reset
    if there is still smoke in the area.
3. Reset the control panel (PRESS the RESET key)

Power failure or brownout

If AC power drops too low or fails, the AC POWER LED will go out,
the system TROUBLE LED will turn on, and the panel buzzer and
any other audible trouble devices will sound. Contact authorized
service personnel immediately. See below.

Manual activation (Fire Drill or otherwise)

Notification Appliance Circuits (NACs) can be activated by
pressing and holding the DRILL key for at least two seconds.

NOTE:

 You may want to disconnect municipal box by sliding

DISCONNECT switch, located on 4XTM module, to its
disconnect position (to the right). If a DACT is
connected, notify the monitoring service before
conducting any fire drills or tests.

 FireWarden-100-2/E Fire Alarm Control Panel

Operating Instructions

PANEL KEY

 - The key to open the panel can be found at the

following location:

NORMAL

 - Only the GREEN A.C. POWER LED is on.

All other LED's are off.  LCD display will read SYSTEM ALL
NORMAL.

Document #52781      Rev. A     11/15/05     ECN 06-086

THIS SHEET SHALL BE FRAMED ADJACENT TO

THE CONTROL PANEL

To test the lamps, LCD display and piezo sounder

Press and release the RESET key and check all LED's. Every LED
should be on, LCD shows all pixels on, piezo sounder beeps.

For more information, refer to the FireWarden-100-2/E Manual,
Document #52778. It is kept in the following location:

Alarm Silencing

Notification Appliance Circuits may be silenced by pressing the
ALARM SILENCE key. The ALARM SILENCED LED will turn on.
Subsequent alarms will reactivate circuits. Press the RESET key
to clear the "silenced" condition.

NOTE:

 Notification Appliance Circuits may be programmed as

nonsilenceable.  Also, Signal Silence Inhibit, if enabled, will
prevent silencing of NACs for one minute after an alarm (see
manual).

Name: _____________________________________

Company: _________________________________

Address: ___________________________________

Telephone Number: ________________________

In the event of trouble, contact the
local Notifier Service Representative

Service Representative