B616LP PLUG-IN DETECTOR BASE INSTALLATION INSTRUCTIONS
FOR USE WITH THE FOLLOWING SMOKE DETECTOR MODELS:
IN US:
CP-651, SD-651
IN CANADA:
CP-651A, SD-651A
IN EUROPE:
CP-651E, SD-651E
Before installing detectors, please thoroughly read manual I56-407,
Guide for Proper Use of System Smoke Detectors,
which provides detailed information on detector spacing, placement, zoning, wiring, and special applications. Copies of
this manual are available from Notifier or through the Notifier distributor. (For installations in Canada, refer to CAN4-
S524-M86, Standard for the Installation of Fire Alarm Systems and CEC Part 1, Sec. 32.)
NOTICE: This manual should be left with the owner/user of this equipment.
IMPORTANT: The detector used with this base must be tested and maintained regularly following NFPA 72 require-
ments. The detector used with this base should be cleaned at least once a year.
GENERAL DESCRIPTION
The B616LP plug-in detector base is used with Notifier model CP-651, CP-651A, and CP-651E ionization detector
heads and SD-651, SD-651A, and SD-651E photoelectronic detector heads. The capability of plugging these detectors
into a variety of special bases makes them more versatile than equivalent direct-wired models.
The B616LP base is intended for use in 2-wire systems, with screw terminals provided for power and relay contact con-
nections. These bases MUST be current limited by the system control panel in the alarm state.
SPECIFICATIONS
Base Diameter:
6.2 inches (157 mm)
Base Height:
0.95 inches (24 mm)
Weight:
0.3 lb. (130 g)
Mounting:
4-inch square box with or without plaster ring. Min. Depth–1.5 inches
4-inch octagon box. Min. Depth–1.5 inches
3-1/2-inch octagon box. Min. Depth–1.5 inches
50 mm box
60 mm box
70 mm box
Operating Temperature Range: 0° to +49°C (32° to 120°F) US and Canadian Installations
10° to +60°C (14° to 140°F) European Installations
Operating Humidity Range:
10% to 93% Relative Humidity
ELECTRICAL RATINGS – includes base and detector
System Voltage:
24 VDC
Maximum Ripple Voltage:
4 Volts peak to peak
Start-up Capacitance:
0.02
µ
F Maximum
Standby Ratings:
15 VDC Minimum
35 VDC Maximum
120
µ
A Maximum
N550-04-00