background image

B616LP PLUG-IN DETECTOR BASE INSTALLATION INSTRUCTIONS

FOR USE WITH THE FOLLOWING SMOKE DETECTOR MODELS:
IN US:

CP-651, SD-651

IN CANADA:

CP-651A, SD-651A

IN EUROPE:

CP-651E, SD-651E

Before installing detectors, please thoroughly read manual I56-407, 

Guide for Proper Use of System Smoke Detectors,

which provides detailed information on detector spacing, placement, zoning, wiring, and special applications. Copies of
this manual are available from Notifier or through the Notifier distributor. (For installations in Canada, refer to CAN4-
S524-M86, Standard for the Installation of Fire Alarm Systems and CEC Part 1, Sec. 32.)

NOTICE: This manual should be left with the owner/user of this equipment.

IMPORTANT: The detector used with this base must be tested and maintained regularly following NFPA 72 require-
ments. The detector used with this base should be cleaned at least once a year.

GENERAL DESCRIPTION

The B616LP plug-in detector base is used with Notifier model CP-651, CP-651A, and CP-651E ionization detector
heads and SD-651, SD-651A, and SD-651E photoelectronic detector heads. The capability of plugging these detectors
into a variety of special bases makes them more versatile than equivalent direct-wired models.

The B616LP base is intended for use in 2-wire systems, with screw terminals provided for power and relay contact con-
nections. These bases MUST be current limited by the system control panel in the alarm state.

SPECIFICATIONS

Base Diameter:

6.2 inches (157 mm)

Base Height:

0.95 inches (24 mm)

Weight:

0.3 lb. (130 g)

Mounting:

4-inch square box with or without plaster ring. Min. Depth–1.5 inches
4-inch octagon box. Min. Depth–1.5 inches
3-1/2-inch octagon box. Min. Depth–1.5 inches
50 mm box
60 mm box
70 mm box

Operating Temperature Range: 0° to +49°C (32° to 120°F) US and Canadian Installations

10° to +60°C (14° to 140°F) European Installations

Operating Humidity Range:

10% to 93% Relative Humidity

ELECTRICAL RATINGS – includes base and detector

System Voltage:

24 VDC

Maximum Ripple Voltage:

4 Volts peak to peak

Start-up Capacitance:

0.02

µ

F Maximum

Standby Ratings:

15 VDC Minimum
35 VDC Maximum
120 

µ

A Maximum