AFP-3030 Operations Manual —
P/N DOC-01-033:C 05/12/2018
9
Message Formats
General Information
1.4 Message Formats
This section describes the formats for system normal, device events and system events screens. For a definition of these types of events,
as well as instructions for dealing with them, refer to Section 2, “Operation of the Control Panel” in this manual.
1.4.1 System Normal Screen
The System Normal message appears at the top of the display when no off-normal events exist. It consists of two lines, each 40 charac-
ters long. Line one is a custom network message. Line 2 is a standard message giving the System Normal message. The Main Menu is
selectable using the lower right soft key.
Line 4 indicates the current time and date.
Figure 1.2 System Normal Screen
A custom graphic may be displayed below the system normal message: the graphic must be entered using VeriFire® Tools. The text
“Main Menu” will overlay the graphic, if it extends into the last line of the display.
1.4.2 Event Reporting Format
The message formats used for event reporting appear at the top of the display, replacing the System Normal message. There are two
basic types of message formats: point event formats, which are generated from changes in the state of SLC and panel devices, and sys-
tem event formats, which are generated from system errors and faults.
Disable
Yellow
Illuminates when at least one device on the fire panel is disabled.
Supervisory
Yellow
Illuminates when at least one supervisory event is present on the fire panel.
Alarm Routing
Fault
Yellow
Illuminates when there are any device or system trouble event is present on the A.R.E. Alarm
Routing Equipment
Alarm Routing
Disabled
Yellow
Illuminates when at least one device or zone on the A.R.E. Alarm Routing Equipment is disabled.
Alarm Devices
Silenced
Yellow
Illuminates when devices programmed as Alarm Devices are silenced.
Alarm Devices
Fault
Yellow
Illuminates when any devices designated as Alarm Devices are in fault, including communication
loss with the Alarm Devices or the LCM that has programming containing Alarm Devices.
Alarm Devices Test Yellow
Illuminates when Alarm Devices are activated due to pressing the Alarm Devices Test button.
Alarm Devices
Disable
Yellow
Illuminates when Alarm Devices are disabled due to pressing the Alarm Devices Disable button.
Note: This LED will not illuminate if the Alarm Devices are disabled via the menus or the network.
Smoke Control
Reset
Red
Illuminates when there are fire events present on the fire panel. If the fire panel is programmed with
Latching Fire Mode enabled, this LED will stay on after the fire events are cleared and will remain on
until Smoke Control Reset button is pressed.
Smoke Control
Disable
Yellow
Illuminates when the Smoke Control devices are disabled via the Smoke Control Disable button.
Delays On/Off
Yellow
Illuminates when the Outputs are delayed via the Delays - On/Off button.
Other
Yellow
Illuminate when at least one other fault event is present on the panel.
Pre Alarm
Yellow
Illuminate when at least one prealarm event is present on the panel.
LED INDICATOR
COLOR
FUNCTION
Table 1.2 LED Indicators (2 of 2)
L A K E V I E W G E N E R A L H O S P I T A L
S Y S T E M N O R M A L
1 1 : 5 8 : 4 5 A
T U E J A N 2 2 , 2 0 1 9
M A I N M E N U