46
AFP-3030 Operations Manual —
P/N DOC-01-033:C 05/12/2018
Viewing and Printing History Information
Point Range Select for All Events in Range
Range is selected in the following order:
1.
Loop 1 Detectors
2.
Loop 2 Detectors, etc.…
3.
Loop 10 Detectors
4.
Loop 1 Modules
5.
Loop 2 Modules, etc. …
This FACP can have up to 10 loops, which would all follow the above order for range selection.
20. Loop 10 Modules
The range selected below includes all supervisory event types for every point: the selection begins with the first detector on loop one and
ends with the last module on loop 10.
Figure 4.3 Point Range Select Screen
Display
See description in Section 4.1, “Events History”, on page 44 for lines 1-5.
Soft Keys
START POINT: - Press this key to scroll through the list of various device types: the format will change for each device. Stop at the
desired format/device type, then use the keypad to enter a start point for event viewing.
END POINT: - Press this key to scroll through the list of various device types: the format will change for each device. Stop at the desired
format/device type, then use the keypad to enter an end point for event viewing.
EVENT TYPE: - Press this soft key to scroll through the following: ALL EVENTS, ALARMS ONLY, FAULTS ONLY, SUPERVI-
SORY ONLY, OTHER ONLY. Stop scrolling at the desired event type.
ACCEPT: - When entries are made, press this soft key to proceed to the All Events in Range Screen.
All Events in Range Screen
This screen is the same as the Event History screen, except for its title. Refer to Figure 4.1 on page 44.
L A K E V I E W G E N E R A L H O S P I T A L
S Y S T E M N O R M A L
1 1 : 5 8 : 4 5 A
T U E J A N 2 2 , 2 0 1 9
P O I N T R A N G E S E L E C T
S T A R T P O I N T :
L 0 1 D 0 0 1 ( D E T E C T O R )
E N D P O I N T :
L 1 0 M 1 5 9 ( M O D U L E )
E V E N T T Y P E : S U P E R V I S O R Y
A C C E P T
B A C K