AFP-3030 Operations Manual —
P/N DOC-01-033:C 05/12/2018
Read Status
Heat Detector
FAULT
INACTIVE
<Fault Status>*
FAULT
ACTIVE
<Fault Status>*
FAULT
PREALARM
<Fault Status>*
*The field <Fault Status> will contain one of the device fault messages listed in Table 2.1, “Point (Device) Faults,” on page 20.
Line 7 - The custom label for this point.
Line 8 - Continuation of the point’s custom label, first zone, and device type.
Lines 9,10 - a display of all the zones that contain the current point being read. These lines will have values in them only if the device is
a detector.
Lines 11 through 14 - These lines display only if the device being read is a smoke, heat, or aspiration detector. Refer to Section 1.6.2,
“More Information”, on page 14 for an explanation of these fields.
Line 16 - BACK - Press to return to the previous screen.
3.3 Heat Detector
When a detector address is entered into the Point Select Screen and the ACCEPT soft key is pressed, the following screen will display if
the detector is a heat detector.
Figure 3.3 Heat Detector Screen - Read Status
Display
Lines 1 through 10 - Refer to the descriptions in Section 3.2, “Smoke Detector”, on page 35.
Line 11 - VALUES - This field indicates the percentage of alarm value being read by the detector.
Line 15 - The current time and date are displayed in this line.
Line 16 - Press BACK to return to the previous screen.
L A K E V I E W G E N E R A L H O S P I T A L
S Y S T E M N O R M A L
1 0 : 2 2 : 3 4 A
T U E J A N 2 2 , 2 0 1 9
R E A D A D D R E S S : N 1 2 4 L 0 3 D 0 5 2
A U T O M A T I C
I N A C T I V E
E L E V A T O R L O B B Y
E A S T W I N G
F I F T H F L O O R
Z 0 0 5
H E A T
Z 0 0 5 ,
Z 0 2 7 ,
Z 0 6 6 ,
,
,
,
,
,
,
,
V A L U E S : 0 2 3 % O F A L A R M
A L A R M 2 = 5 7
o
C
T E M P E R A T U R E = 2 1
o
C
1 0 : 2 2 : 3 4 A
T U E J A N 2 2 , 2 0 1 9
B A C K