LineTroll

 R400D 

 
Pole Mounted Fault Passage Indicator with built-
in Mobile Data Communication. 
 

-  SMS 
-  GPRS 

 

 

User Manual 

 
 
 
 
 
 
 
 
 

Содержание LineTrol R400D

Страница 1: ...LineTroll R400D Pole Mounted Fault Passage Indicator with built in Mobile Data Communication SMS GPRS User Manual...

Страница 2: ...to change without notice No parts of this documentation may be reproduced in any form by any means without the written permission of Nortroll AS Copyright 2018 Nortroll AS All rights reserved All Nort...

Страница 3: ...SCHARGES 16 4 7 SETTING THE TRIP LEVEL 17 4 8 SENSITIVITY 17 5 EVENT LOG 19 6 FUNCTIONAL DESCRIPTION GSM MODEM 20 INSERTING THE SIM CARD 20 MANUAL ACTIVATION 20 ALARM MESSAGE RECIPIENTS 20 Sending SMS...

Страница 4: ...nality from E is amended into the D version Please note the importance of using the correct configuration template matching the firmware in your field device when configuring the device using NetTroll...

Страница 5: ...r be possible to give an accurate distance as it will be very individual The lens of the indicator can be turned to either side for optimal visibility The indicator does also have separate indications...

Страница 6: ...ppen before it starts indicating a fault and send the alarm to the control center The general sequence is as follows ref fig 2 1 The line should be energised for at least 5 seconds Inrush blocking tim...

Страница 7: ...level Figure 3 magnetic field It is important to notice that the indicator measure a B field which is a product of the current flowing in the feeder The trip setting values for short circuit and earth...

Страница 8: ...and LineTroll R400D can detect PtG faults as low as 2A 2 3 Operation Installation and mounting The indicator must be calibrated to the normal line conditions during the installation of the device Thi...

Страница 9: ...ation not dependent on de energised line 2 4 Indication LED indication The LineTroll R400D is equipped with a separate indication board in the bottom lens of the indicator D1 D2 D3 D4 Figure 5 LED ind...

Страница 10: ...an 15 to 30 seconds Fast Auto Reclosing Fault 15 30 sec SMS with Transient Fault Transient Fault Sending GPRS SMS alarms and messages The built in GSM modem is normally switched off to save battery po...

Страница 11: ...nergized until the indicator is reset can be set The following voltage reset delay selections can be made 5s 10s 15s 20s 25s or 30s 2 Automatic timer reset The timer reset can be set to any value betw...

Страница 12: ...ctionalizing switches NorTroll s actuators for sectionalizing switches 3 1 Suitable networks The LineTroll R400D fault indicator can be used in the following networks 6 132kV distribution networks Rad...

Страница 13: ...s 11kV min 25 meters Figure 7 mounting restrictions When LineTroll R400D is mounted in fused lines special percussions should be taken See section 4 4 for details about fused lines The indicator shoul...

Страница 14: ...in case of switching against a fault t t LINE I NO INDICAT ION 4 2 Faults Permanent fault Permanent faults will be indicated by strong red strobe flash The time out for the indication can be set by t...

Страница 15: ...eset feature must be switched ON if the indicator shall reset upon re energizing of the feeder The reset time is configurable 5 to 30 sec 4 4 Fused lines When the circuit breaker trip criteria are swi...

Страница 16: ...icator is below the pre set trip level for PtG faults in order to avoid the indicator incorrectly activating behind the fault In general capacitive discharge currents can be neglected in solidly earth...

Страница 17: ...setting of trip level especially with regards to capacitive discharge currents Basic rules for setting the trip level IT is To avoid incorrect detection because of capacitive current from the network...

Страница 18: ...e indicator requires that two conditions are satisfied in order to detect a short circuit fault 1 The relative increase dB is greater than a certain level 50 100 or 200 2 The absolute dB T is greater...

Страница 19: ...ed NetLogger Please find details about reading the log in the User Manual for NetLogger The events that can be logged are Power up reset Temperature Logged every time the temperature is read Connectio...

Страница 20: ...that is most economic and suitable for your system please contact your local network service provider We do not recommend using prepaid subscriptions We also recommend disabling voice communication o...

Страница 21: ...number only in if GPRS Connection is used as primary channel and this channel fails SMS Recipient 2 If a number is set in this parameter location the alarm or message is always sent in SMS to this nu...

Страница 22: ...ever this message will appear when the indicator has detected a fault and the alarm message shall be sent even if this message is switched OFF Also when the indicator detects a de energized line and a...

Страница 23: ...MM Month DD Day hh Hours mm Minutes ss Seconds tt Milliseconds Tx When sending a message from NetTroll e g status request a Tx number is added in the message The Tx number send from the indicator in t...

Страница 24: ...usage of the message filter the secondary number can be maintenance central and should keep track on heartbeat messages low battery boot messages etc whereas the primary e g the main SCADA should rec...

Страница 25: ...having sent an alarm or a heartbeat message Setting polling up time Defines the period the GSM modem is connected to the GSM network after having done the regular polling sequence and checked the GSM...

Страница 26: ...between 10 and 3000 Passwords All messages sent to the device must contain a password corresponding to the programmed password It is also a separate configuration password which will lock all configur...

Страница 27: ...o configure the unit A detailed description of the configuration properties is given in the Configuration Manual for the RIS system This manual covers all possible methods of configuration The most im...

Страница 28: ...The LineTroll R400D can be fitted with different types and number of batteries By default the LineTroll R400D is equipped with three KBB 20 batteries which gives a total capacity of 39Ah In the config...

Страница 29: ...ely From SCADA or NetTroll or FDP 10 hand held unit from ground Indication 1 Green LED for transient faults Can be switched off High visibility red strobe flash for permanent fault Low battery indicat...

Страница 30: ...Page 30 User Manual LineTroll R400D 11 Dimensions 98 78 380 11 Figure 11 dimensions...

Страница 31: ...ypically 3 to 5 meters below the conductors 3 5 meter If the bracket has been mounted on the pole with either screws or cable ties with the indicator removed from the bracket the indicator housing can...

Страница 32: ...re than 1 meters below the indicator while the LED s are flashing 3 After approx 9 seconds the adaption to the line conditions will start The LED s will be OFF during the adaption 4 After the adaption...