Chapter 3 — System and site requirements
553-3121-210
Standard 3.0
January 1999
Receptacles
Receptacle requirements are as follows:
•
When mounted on the wall, they must be installed within reach of the
cabinet power cords (the power cord from each cabinet is 9 ft 10 in. [3000
mm] long).
•
All receptacles served by the secondary must be of the isolated ground
type
•
The ground prong of each outlet must be connected by an insulated
conductor to the system SPG
If the transformer has an isolated secondary ground lug, use it as the Single
Point Ground (SPG). If it doesn’t, use the chassis ground of the transformer
as the SPG.
Transformers with pluggable power cords
See the following for installation instructions.
1
Connect the power cords of all Option 11C Compact system
equipment to the outlets on the transformer secondary.
2
Secure an insulated conductor between the ground lug on the main
cabinet of the Option 11C Compact system and the SPG lug on the
transformer. Place a “DO NOT DISCONNECT” tag on it.
Do not fasten or tie this conductor to the power cable feeding the
NTMW11 power supply.
Note: All equipment associated with the Option 11C Compact system
should be powered exclusively from the secondary of the transformer
and grounded to the secondary isolated ground lug. Do not connect
equipment unrelated to the Option 11C Compact system to an isolation
transformer powering it.
Содержание Meridian Meridian 1
Страница 3: ...553 3121 210 Standard 3 0 January 1999 ...
Страница 17: ...xiv Contents 553 3121 210 Standard 3 0 January 1999 ...
Страница 89: ...Page 70 of 536 Chapter 6 Bracing cabinets against earthquakes 553 3121 210 Standard 3 0 January 1999 ...
Страница 97: ...Page 78 of 536 Chapter 8 Installing a new system 553 3121 210 Standard 3 0 January 1999 ...
Страница 107: ...Page 88 of 536 Chapter 10 Installing the system ground 553 3121 210 Standard 3 0 January 1999 ...
Страница 113: ...Page 94 of 536 Chapter 11 Installing the power supply 553 3121 210 Standard 3 0 January 1999 ...
Страница 125: ...Page 106 of 536 Chapter 12 Adding an expansion cabinet 553 3121 210 Standard 3 0 January 1999 ...
Страница 139: ...Page 120 of 536 Chapter 13 Installing the circuit cards 553 3121 210 Standard 3 0 January 1999 ...
Страница 157: ...Page 138 of 536 Chapter 15 Installing and connecting SDI and Ethernet ports 553 3121 210 Standard 3 0 January 1999 ...
Страница 175: ...Page 156 of 536 Chapter 16 Starting up and testing the system 553 3121 210 Standard 3 0 January 1999 ...
Страница 209: ...Page 190 of 536 Chapter 18 Connecting the trunks 553 3121 210 Standard 3 0 January 1999 ...
Страница 323: ...Page 304 of 536 Chapter 21 Installing Hospitality 553 3121 210 Standard 3 0 January 1999 ...
Страница 419: ...Page 400 of 536 Chapter 23 Pre programmed data 553 3121 210 Standard 3 0 January 1999 ...
Страница 455: ...Page 436 of 536 Chapter 24 Changing pre programmed data 553 3121 210 Standard 3 0 January 1999 ...
Страница 555: ...Page 536 of 536 Chapter 25 Fault locating and clearing 553 3121 210 Standard 3 0 January 1999 ...