DC power supply installation
Removing the bottom bezel 312096-A of the 8010co chassis
Use the procedure in this section to remove the bottom bezel 312096-A
from the 8010co chassis to access the power supplies.
See
“Job aid: Bezel models” (page 40)
aid below.
ATTENTION
If you install an 8005DC power supply in an 8010co chassis you must use the
modified air-intake bezel model 321325-A.
Procedure steps
ATTENTION
The procedure only applies to the 8010co chassis with bezel model 312096-A
installed. If you replaced bezel 312096-A with the modified bezel order code
321325-A, you do not need to remove this bezel to access the power supplies.
Step
Action
1
Use a Phillips screwdriver to loosen the two captive screws that
secure the bezel to the chassis (see the following figure).
Nortel Ethernet Routing Switch 8600
Installation — DC Power Supply
NN46205-307
02.02
19 December 2008