Nortek SH1QE4M1SP-24K Скачать руководство пользователя страница 8

8

REFRIGERANT CHARGING

 WARNING:

SH1QE4M1SP split system heat pumps are 

shipped charged with R410A refrigerant and 

ready for installation. If repairs make it necessary 

for evacuation and charging, it should only 

be attempted by qualified trained personnel 

thoroughly familiar with this equipment. Under 

no circumstances should the owner attempt to 

install and/or service this equipment. Failure to 

comply with this warning could result in property 

damage, personal injury, or death.

•  After refrigerant line connections are completed, it is 

required that you leak check and evacuate the indoor 

section and all line connections (using proper methods) 

before finalizing the full system refrigerant charge.

•  To achieve rated capacity and efficiency, the compressor 

must be exposed to refrigerant for at least 24 hours prior 

to running and then the compressor must be run for a 

minimum of 12 hours.

•  Refrigerant charging charts are applicable only to matched 

assemblies of this equipment and listed airflows for the 

indoor coil. For correct system charging, refer to 

Figure 5 

(page  9)

Figure 6 (page 9)

Figure 7 (page 10)

Figure 8 (page 10)

, and 

Figure 9 (page 11)

.

• Refer to the unit's Quick Reference Data sheet to 

determine if additional refrigerant will need to be 

weighed-in to attain the base refrigerant amount for 

the system match that is being installed. Please note 

that the charge additons provided in the QRD are 

estimates based on test data and should only be used 

as a starting point. Complete the steps in the charging 

procdure to obtain the final system charge.

•  Use of SH1QE4M1SP outdoor units with non-AHRI listed 

indoor coils are not recommended and deviations from 

rated airflows or non-listed combinations may require 

modification to the expansion device and refrigerant 

charging procedures for proper and efficient system 

operation.

•  The refrigerant charge can be checked and adjusted 

through the service ports provided external to the outdoor 

unit. Use only gage line sets which have a “Schrader” 

depression device present to actuate the valve. A common 

suction port for heating mode charging is included and 

located on the compressor access panel above the outdoor 

unit service valves.

•  A high-pressure switch is factory-installed and located in the 

compressor discharge line internal to the outdoor unit. The 

switch is designed to de-energize the system when very 

high pressures occur during abnormal conditions. Under 

normal conditions, the switch is closed. If the discharge 

pressure rises above 575 psig, then the switch will open 

and de-energize the outdoor unit. The switch will close 

again once the liquid pressure decreases to 460 psig. 

Please note that the switch interrupts the thermostat inputs 

to the unit. When the switch opens and then closes, there 

will be a 5 minute short cycling delay before the outdoor 

unit will energize.

Charging the Unit in AC Mode

(With Outdoor Temperatures Above 65° F)

1. With the system operating at steady-state, measure the 

liquid refrigerant pressure (in psig) at the outdoor unit 
service valve.

2. Measure the liquid refrigerant temperature (in Fahrenheit) 

at the service valve.

3. Determine the appropriate liquid refrigerant pressure from 

Figure 5

Figure 6

Figure 7

Figure 8

, and 

Figure 9

.

•  If the pressure measured in Step 1 is greater than 

the liquid refrigerant pressure determined in Step 3, 

then there is too much charge in the system. Remove 

refrigerant and repeat Steps 1 through 3 until the system 

is correctly charged.

•  If the pressure measured in Step 1 is less than the 

liquid refrigerant pressure determined in Step 3, there 

is too little charge in the system. Add refrigerant and 

repeat Steps 1 through 3 until the system is correctly 

charged.

Charging Charts & Application Notes

(Cooling Mode Only)

•  This unit’s cooling system contains refrigerant under 

high pressure. Always use safe and environmentally 

sound methods when handling refrigerant handling 

or servicing the unit. Review the factory literature and 

safety warnings prior to servicing.

•  When repairing system leaks, always use a nitrogen (inert) 

gas to protect the refrigerant system and pressure check the 

repair before re-charging. Always replace the filter-dryers 

when performing any repair to the refrigeration system with 

one capable of acid removal. After completing the repairs, 

evacuate the system to 350 - 500 microns and weigh in 

the refrigerant to the amount specified on the unit rating 
label.

•  The charging charts are valid for a variety of indoor, return 

air conditions and are most influenced by the outdoor 

ambient temperature, outdoor fan operation and the unit 

operating voltage.

•  Before using these charts, make sure the unit is in a 

stable operating mode. As shown in the charts the ideal 

system sub-cooling can vary over the range of operation. 

Reference 

Figure 5 (page 9)

Figure 6 (page 9)

Figure 7 (page 10)

Figure 8 (page 10)

, and 

Figure 9 

(page 11)

 to determine the ideal amount of sub-cooling 

for a given liquid pressure. Units charged to other values 

will not perform at the rated unit efficiency (EER) or rated 
Coefficient of Performance (COP) in heating mode.

•  To inspect a systems operation using quality instruments, 

match the measured liquid temperature to the units chart. 

The measured liquid pressure reading should be within 
3% of the charts value for most installations.

•  For systems that are operating with more than a 5% 

deviation, inspect the unit for the proper voltage and phase 

balance and the refrigeration system for leaks.

•  Units that are operating at less then 95% of the nominal 

voltage or with a 2% phase imbalance may see a more 

significant deviation than the amount stated above.

• 

DO NOT use the charts in systems that have a fan cycling 

under low-ambient control. Refer to the low-ambient kit 

instructions for more information. (If applicable)

Содержание SH1QE4M1SP-24K

Страница 1: ...FE PLACE FOR FUTURE REFERENCE INSTALLATION INSTRUCTIONS HEAT PUMP MAINTENANCE 7 Panel Removal 7 Panel Installation 7 REFRIGERANT CHARGING 8 Charging the Unit in AC Mode 8 Charging Charts Application N...

Страница 2: ...er refrigerant may damage the unit WARNING The information listed below and the next page should be followed during the installation service and operation of this product Failure to follow safety reco...

Страница 3: ...h the carrier Please consult your dealer for maintenance information and availability of maintenance contracts Please read all instructions before installing the unit Locating the Heat Pump Survey the...

Страница 4: ...ling union nut to the bulkhead then tighten an additional 1 6 turn See Table 1 for torque values Repeat for all couplings ELECTRICAL WIRING WARNING ELECTRICAL SHOCK OR FIRE HAZARD To avoid risk of ele...

Страница 5: ...Electrical Code Use the grounding lug provided in the control box for grounding the unit Thermostat Low Voltage Connections Thermostat connections should be made in accordance with the instructions su...

Страница 6: ...nected to the correct leads on the low voltage terminal strip Verify that the power supply branch circuit overcurrent protection is sized properly Verify that the thermostat is wired correctly Start U...

Страница 7: ...lectrical connections for tightness at the beginning of each heating and cooling season Service as necessary CAUTION The unit should never be operated without a filterinthereturnairsystem Replacedispo...

Страница 8: ...ing delay before the outdoor unit will energize Charging the Unit in AC Mode With Outdoor Temperatures Above 65 F 1 With the system operating at steady state measure the liquid refrigerant pressure in...

Страница 9: ...move refrigerant if above curve Add refrigerant if below curve SH1QE4M1SP24K CHARGING CHART COOLING 90 95 100 105 110 115 120 125 130 Liquid Temperature F Liquid Pressure psig 75 80 85 200 220 240 260...

Страница 10: ...elow curve SH1QE4M1SP42K CHARGING CHART COOLING Figure 8 Charging Chart for 3 5 Ton Models TXV Matches 90 95 100 105 110 115 120 125 130 Liquid Temperature F Liquid Pressure psig 75 80 85 200 220 240...

Страница 11: ...Pressure psig 75 80 85 200 220 240 260 280 300 320 340 360 380 400 420 440 460 480 500 520 540 560 580 600 135 Remove refrigerant if above curve Add refrigerant if below curve SH1QE4M1SP48K CHARGING C...

Страница 12: ...shown and the ambient temperature is above 50 F then a more accurate way to inspect the system for proper charge is with the cooling mode charging charts Switch the unit into cooling mode and allow i...

Страница 13: ...88 141 112 301 312 153 128 325 336 164 36 216 227 108 51 235 245 115 66 253 263 123 81 271 282 130 96 284 295 139 113 308 319 148 129 332 343 158 37 223 234 106 52 240 251 113 67 258 268 121 82 275 28...

Страница 14: ...311 120 98 340 347 125 114 372 379 129 129 405 412 134 Table 9 Verification Table for 3 5 Ton Models Table 10 Verification Table for 4 Ton Models OUTDOOR TEMPERATURE DEG F 0 10 20 30 40 50 60 SUC PRE...

Страница 15: ...For replacement wires use conductors suitable for 105 C 5 For ampacities and overcurrent protection see unit rating plate 6 Connect to 24 vac 40va class 2 circuit See furnace air handler installation...

Страница 16: ...hermostat level YES NO Is the heat anticipator setting correct If Applicable YES NO REFRIGERATION SYSTEM Wasunitgiven24hrwarmupperiod for crankcase heaters YES NO Stage 1 Liquid Pressure high side Sta...

Отзывы: