33
Table 8. *SD 050U-23EA Blower Data (Cooling Airflow)
COOLING AIRFLOW (CFM)
MODEL NAME
HEATING INPUT
RETURN
AIR VIA:
MOTOR
SPEED
EXTERNAL STATIC PRESSURE (IN. W.C.)
0.1
0.2
0.3
0.4
0.5
0.6
0.7
0.8
(CFM)
(CFM)
(CFM)
(CFM)
(CFM)
(CFM)
(CFM)
(CFM)
-050U-T23A*
50,000 BTU/Hr
Input
50,000 Btuh
Output
Bottom
Only
Tap 9
1,420
1,395
1,360
1,330
1,300
1,280
1,245
1,220
Tap 8
1,310
1,270
1,245
1,215
1,180
1,145
1,120
1,095
Tap 7
1,180
1,145
1,115
1,085
1,050
1,020
990
955
Tap 6 *
1,085
1,050
1,015
985
950
920
890
855
Tap 5 **
970
935
915
880
845
810
780
745
Tap 4
875
835
810
770
735
700
665
630
Tap 3
835
795
765
725
690
655
615
580
Tap 2
650
590
560
520
465
430
380
340
Tap 1 ***
550
485
450
405
330
290
250
195
Left Side Only
(Motor)
Tap 9
1,410
1,380
1,350
1,315
1,285
1,255
1,225
1,200
Tap 8
1,290
1,260
1,230
1,195
1,160
1,135
1,100
1,070
Tap 7
1,145
1,115
1,090
1,055
1,030
995
960
920
Tap 6 *
1,045
1,015
980
950
920
885
855
825
Tap 5 **
935
915
880
845
805
775
745
695
Tap 4
850
815
780
745
715
665
625
585
Tap 3
815
775
740
700
675
620
575
540
Tap 2
605
575
530
495
445
390
325
235
Tap 1 ***
495
470
410
365
320
260
160
*NOTES:
1. Data is shown without filter.
2. Temperature rises in the table are approximate. Actual temperature rises may vary.
3. Individual cells shaded in gray indicate a temperature rise outside of the recommended range.
4. To comply with government mandated efficiency standards, speed settings shaded in gray are not allowed in HEAT mode.
* Denotes the factory (default) COOL setting.
** Denotes the factory (default) HEAT setting.
** Denotes the factory (default) FAN setting. If an alternate speed is to be used, refer to the installation instructions for Speed Tap Selection.