background image

inStallation / perFormance checKliSt

electrical SyStem

Electrical connections tight?

YES

NO

Line voltage polarity correct?

YES

NO

Rated Voltage: ___________________________________ VOLTS

L1-L2 Volts: _____________________________________ VOLTS

L1-L3 Volts: _____________________________________ VOLTS

L2-L3 Volts: _____________________________________ VOLTS

Avg. Volts: ______________________________________ VOLTS

Max. deviation of voltage
from avg. volts: ___________________________________ VOLTS

% Volt imbalance: ________________________________ VOLTS

Blower Motor HP: ________ Sheave Setting ___________# Turns

Has the thermostat been calibrated?

YES

NO

Is the thermostat level?

YES

NO

Is the heat anticipator setting correct? 

(If Applicable)

YES

NO

709427B (Replaces 709427A)

inStallation addreSS:

CITY ________________________ STATE ________________

UNIT MODEL # ________________________________________

UNIT SERIAL # _______________________________________

inStaller name:

CITY _______________________

STATE ________________

Unit Installed Minimum clearances 

shown on 

page 3

?

YES

NO

Has the owner’s information been 

reviewed with the customer?

YES

NO

Has the Literature Package been left 

with the unit?

YES

NO

reFrigeration SyStem

Was unit given 24 hr warm up period 

for crankcase heaters?

YES

NO

Stage-1 Liquid Pressure (high side) ________________________

Stage-1 Suction Pressure (low side) ________________________

replacement partS

Replacement parts are available through all Nordyne 

distributors. Please have the complete model and serial 

number of the unit when ordering replacement parts.

electrical:
•  Capacitors

•  Temperature Limit Switches

•  Compressors

•  Thermostats

•  Contactors

•  Time Delay Relays

•  Pressure Switches

•  Transformers

•  Relays
motors:
•  Blower Motor
•  Fan Motor
components:
•  Blower Assembly

•  Fan Grille

•  Cabinet Panels

•  Filter/Driers

•  Expansion Valves

propoSition 65 Warning:

Warning: this product contains chemicals known 
to the state of california to cause cancer.

Warning: this product contains chemicals known 
to the state of california to cause birth defects or 
other reproductive harm.

Specifications & illustrations subject to change without notice or incurring obligations (11/15).
O’Fallon, MO, © Nortek Global HVAC LLC 2015. All Rights Reserved.

Содержание S6BF-024 Series

Страница 1: ...allation Return these instructions to the customer s package for future reference DO NOT DESTROY PLEASE READ CAREFULLY KEEP IN A SAFE PLACE FOR FUTURE REFERENCE important SAFETY INFORMATION 2 Air cond...

Страница 2: ...below must be followed during the installation service and operation of this unit Unqualified individuals should not attempt to interpret these instructions or install this equipment Failure to follow...

Страница 3: ...nanceinformation and availability of maintenance contracts Please read all instructions before installing the unit Locating the Air Conditioner Survey the job site to determine the best location for m...

Страница 4: ...rical connections in accordance with all applicable codes and ordinances Overcurrent protection must be provided at the branch circuit distribution panel and sized as shown on the unit rating label an...

Страница 5: ...The thermostat should be mounted about 5 feet above theflooronaninsidewall DONOTinstallthethermostat on an outside wall or any other location where its operationmaybeadverselyaffectedbyradiantheatfrom...

Страница 6: ...the system Add refrigerant and repeat Steps 1 through 3 until the system is correctly charged System Cooling 1 Set the thermostat s system mode to COOL and the fan mode to AUTO Gradually lower the the...

Страница 7: ...sig Liquid Temperature F S6BF 024K Charging Chart Cooling Add refrigerant when below curve Remove refrigerant when above curve Figure 2 Before using these charts make sure the unit is in a stable oper...

Страница 8: ...S6BF 030K Charging Chart Cooling Add refrigerant when below curve Remove refrigerant when above curve Figure 4 200 220 240 260 280 300 320 340 360 380 400 420 440 460 480 500 520 540 560 580 600 75 80...

Страница 9: ...S6BF 042K Charging Chart Cooling Add refrigerant when below curve Remove refrigerant when above curve Figure 6 200 220 240 260 280 300 320 340 360 380 400 420 440 460 480 500 520 540 560 580 600 75 80...

Страница 10: ...L2 OUTDOOR FAN MOTOR C S DUAL CAPACITOR R 3 1 2 START CAPAC START RELAY BLACK BLUE ORANGE YELLOW CONTACTOR YELLOW BLACK RED CRANKCASE HEATER OPTIONAL YELLOW BLACK SEE NOTE 6 RED OR YELLOW BLACK RED O...

Страница 11: ...ction see unit rating plate 6 Connect to 24 vac 40va class 2 circuit See furnace air handler installation instructions for control circuit and optional relay transformer kits 7 Anti Short Cycle Timer...

Страница 12: ...___________ Unit Installed Minimum clearances shown on page 3 YES NO Has the owner s information been reviewed with the customer YES NO Has the Literature Package been left with the unit YES NO REFRIG...

Отзывы: