background image

4

ELECTRICAL WIRING

 WARNING:

ELECTRICAL SHOCK OR FIRE HAZARD

To avoid risk of electrical shock, personal injury, 

or death, disconnect all electrical power to the unit 

before performing any maintenance or service. The 

unit may have more than one electrical supply.
Label all wires prior to disconnection when 

servicing the unit. Wiring errors can cause improper 

and dangerous operation.

• All electrical connections must be in compliance with 

all applicable local codes and ordinances, and with 

the current revision of the National Electric Code  

(ANSI/NFPA 70).

•  For Canadian installations the electrical connections and 

grounding shall comply with the current Canadian Electrical 

Code (CSA C22.1 and/or local codes).

Pre-Electrical Checklist

  Verify that the voltage, frequency, and phase of the supply 

source match the specifications on the unit rating plate.

 Verify that the service provided by the utility is sufficient 

to handle the additional load imposed by this equipment. 

Refer to the unit wiring label for proper voltage wiring.

  If replacing an existing unit, verify that the: current wiring, 

unit disconnect and circuit breaker is properly sized and 

rated for the new units requirements.  Verify that information 

with the MCA and MOP values on the unit nameplate.

 Verify factory wiring is in accordance with the unit wiring 

diagram. See 

Figure 4, (page 6)

, & 

Figure 5, (page 6)

Inspect for loose connections.

Line Voltage

•  A wiring diagram is located on the inside cover of the 

electrical box of the outdoor unit. The installer should 

become familiar with the wiring diagram before making 

any electrical connections to the outdoor unit.

• 

An electrical disconnect must be located within sight 
of and readily accessible to the unit

. This switch shall 

be capable of electrically de-energizing the outdoor unit.

•  Line voltage to the unit should be supplied from a dedicated 

branch circuit containing the correct fuse or circuit breaker 

for the unit. Incoming field wiring and minimum size of 

electrical conductors and circuit protection must be in 

compliance with information listed on the outdoor unit 

data label. Any other wiring methods must be acceptable 

to authority having jurisdiction.

•  The outdoor unit requires both power and control circuit 

electrical connections. Refer to the wiring diagram / 

schematic for identification and location of outdoor unit 

field wiring interfaces. See 

Figure 4, (page 6)

, & 

Figure 5, 

(page 6)

. Make all electrical connections in accordance 

with all applicable codes and ordinances.

•  Overcurrent protection must be provided at the branch 

circuit distribution panel and sized as shown on the unit 

rating label and according to applicable local codes. See 

the unit rating plate for minimum circuit ampacity (MCA) 

 CAUTION:

When performing brazing operations always 

protect the system components and  seals from 

the possibility of heat damage.  Remove all 

caps, plugs and Schrader valve cores on piping 

system components just prior to assembly and 

brazing.  Use good brazing practices to protect 

components from the heat and flame of the 

brazing torch.

After outdoor and indoor unit placement has been determined, 

route refrigerant tubing between the equipment in accordance 

with sound installation practices.
• Refrigerant tubing should be routed in a manner that 

minimizes the length of tubing and the number of bends 

in the tubing. If precise forming of refrigerant lines is 

required, a copper tubing bender is recommended. Avoid 

sharp bends and contact of the refrigerant lines with metal 

surfaces.

•  Refrigerant tubing should be supported in a manner that the 

tubing will not vibrate or abrade during system operation.

• Tubing should be kept clean of foreign debris during 

installation.

•  Every effort should be made by the installer to ensure that 

the field installed refrigerant containing components of 

the system have been installed in accordance with these 

instructions and sound installation practices to insure 

reliable system operation and longevity.

•  The maximum recommended interconnecting refrigerant 

line lengths is 75 ft. and the vertical elevation difference 

between the indoor and outdoor sections should not exceed 

20 ft.

•  A filter dryer is provided with the unit and must be installed 

in the liquid line of the system. If the installation replaces a 

system with a filter dryer already present in the liquid line, 

the filter dryer must be replaced with the one supplied with 

the unit. The filter dryer must be installed in strict accordance 

with the manufacturer’s installation instructions.

•  Optional equipment such as liquid line solenoid valves, 

low ambient, etc., should be installed in strict accordance 

with the manufacturer’s installation instructions.

•  After the completion of all brazing operations and when 

the components have been properly cooled, replace 

all the seals, Shrader cores and caps which had been 

previously removed.  It is recommended that all seals 

be either lubricated with a light coat of refrigerant oil.  

Always verify that oil applied matches the oil type listed 

on the compressor nameplate.  A thread sealant which 

is compatible with the system refrigerant and oil can be 

sparingly applied if desired.

 CAUTION:

If repairs are necessary to the refrigerant line-

set or indoor setup after the initial installation, 

then when servicing, cover or seal openings to 

minimize the exposure of the refrigerant system 

to air to prevent accumulation of moisture and 

other contaminants.

Содержание RN24K Series

Страница 1: ...el for this type of equipment Please read all instructions carefully before starting the installation Return these instructions to the customer s package for future reference DO NOT DESTROY PLEASE REA...

Страница 2: ...nstallation requirements All electrical wiring must be completed in accordance with local state and national codes and regulations and with the National Electric Code ANSI NFPA 70 or in Canada the Can...

Страница 3: ...d onesideofthe unit adjacent to the service panel may have its air side clearance reduced to a minimum of 6 inches The other side adjacent to the service panel requires 24 inches for service access Th...

Страница 4: ...nit rating label and according to applicable local codes See the unit rating plate for minimum circuit ampacity MCA CAUTION When performing brazing operations always protect the system components and...

Страница 5: ...t the power supplied by branch circuits for both the indoor and outdoor equipment is the proper voltage for the equipment and that the overcurrent protection device is properly sized and that the supp...

Страница 6: ...ness at the beginning of each heating and cooling season Service as necessary Do not attempt to add additional oil or grease to motors unequipped with oil tubes or grease fittings Most outdoor unit mo...

Страница 7: ...orm the following steps 1 Determinetherecommendedchargeaddition ifapplicable for the system being installed This information is in the unit s QRD Quick Reference Data sheet 2 Calculate the amount of a...

Страница 8: ...5 For ampacities and overcurrent protection see unit rating plate 6 Connect to 24 VAC 40VA class 2 circuit See furnace airhandler installation instructions for control circuit and optional relay trans...

Страница 9: ...Connect to 24 VAC 40VA class 2 circuit See furnace airhandler installation instructions for control circuit and optional relay transformer kits 7 Caution The Low Voltage wiring in this unit shall not...

Страница 10: ...10...

Страница 11: ...11...

Страница 12: ...number of the unit when ordering replacement parts ELECTRICAL Capacitors Temperature Limit Switches Compressors Thermostats Contactors Time Delay Relays Pressure Switches Transformers Relays MOTORS B...

Отзывы: